2.9.6 THE OPERATIONAL REGISTERS
7KH2SHUDWLRQDO5HJLVWHUVDUHWKUHHELWUHJLVWHUVZKRVHELWVDUHQRWGH¿QHGE\WKH,(((VSHFL¿
-
FDWLRQEXWDUHVSHFL¿FWRWKH,(((GHYLFH
The bit assignments for the Operational Registers are:
BIT
NUMBER
DECIMAL
VALUE
BIT
SYMBOL DESCRIPTION
0
1
CV
Set high if Constant Voltage Operation
1
2
CC
Set high if Constant Current Operation
2
4
NFLT
No fault
3
8
0
Not used
4
16
AST
Auto Start Enabled
5
64
FBE
Foldback Enabled
6
64
0
Not Used
7
128
LOC
Remote/Local Mode
8 to 15
N/A
0
Not used
Table 3.
The Operational Registers
2.9.6.1 THE OPERATIONAL CONDITION ‘CONDITION’ REGISTER
See the READ OPERATIONAL CONDITION ‘CONDITION’ REGISTER COMMAND
67$78623(5$7,21&21',7,21"DQG7DEOH7KHELWVDVOLVWHGLQ7DEOHUHÀHFWWKHFRQGL
-
tions under which the power supply is operating.
2.9.6.2 THE OPERATIONAL CONDITION ‘ENABLE’ REGISTER
See the READ OPERATIONAL CONDITION ‘ENABLE’ REGISTER COMMAND
(STATUS:OPERATION:ENABLE?),
the SET OPERATIONAL CONDITION ‘ENABLE’ REGISTER COMMAND
(STATUS:OPERATION:ENABLE) and Table 3.
The OPERATIONAL CONDITION ‘ENABLE’ REGISTER is a mirror of the OPERATIONAL
CONDITION ‘CONDITION’ REGISTER.
If any bit is set in the Operational Condition ‘Condition’ Register and enabled in this register, the
condition will propagate to the Operational Condition ‘Event’ Register as an event.
2.9.6.3 THE OPERATIONAL CONDITION ‘EVENT’ REGISTER
See the READ OPERATIONAL CONDITION ‘EVENT’ REGISTER COMMAND
(STATUS:OPERATION:EVENT?) and Table 3.
The OPERATIONAL CONDITION ‘EVENT’ REGISTER is a mirror of the OPERATIONAL CONDITION
‘CONDITION’ REGISTER.
If any event is set in this Register, it will propagate to the Status Byte Register as an Operational
Summary event.
Содержание Genesys Series
Страница 1: ...6 3 3 0XOWL URS QWHUIDFH 2SWLRQ...
Страница 2: ...USER MANUAL FOR IEEE PROGRAMMING INTERFACE FOR GENESYSTM POWER SUPPLIES 5HY...
Страница 3: ...7KLV SDJH LQWHQWLRQDO OHIW EODQN...
Страница 40: ...NOTES...