background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

11

DELAY ON POWER UP 

The SZ1022, SZ1031, and SZ1035 have an adjustable 

delay on power up. When several thermostats are used 

at one location, and the power goes out, most thermo-

stats turn all of the units back on at the same time on 

regain of power, creating a peak. The thermostat allows 

you to set a value, in seconds, where no outputs are 

allowed to turn on for that length of time on power up. 

Setting each unit to a different delay allows you to soft 

start your system, and thus prevent this peak.  

Note, this

 

delay is also applied to the start of occupied time.

DAYLIGHT SAVINGS TIME

Beginning in 2007, Daylight Saving Time (DST) in the 

U.S. will be extended by having an earlier change to 

DST in spring and a delay in switching back to standard 

time in fall. However, this change may only be tempo-

rary, as this "new" schedule is only in effect for a 2 year 

trial period. After that, the DST schedule may revert 

back, stay the same, or be something completely differ-

ent. Products shipped starting in 2007 with firmware ver-

sion 1.5 or higher accommodate the new DST schedule. 

Products shipped starting in 2008 with firmware version 

2.0 or higher accommodate the new DST schedule and 

have the ability to be programmed to accommodate any 

future schedules that may be used. Should the schedule 

change and you need to customer program the DST 

start and end dates, simply enable the "Daylight Savings 

Time" option within the software and enter the starting 

month + week and the ending month + week.

Checkout & Troubleshooting          

CHECKOUT
Note: 

The fan has a minimum on and off time of 30 sec-

onds.  The heating and cooling stages have a minimum 

on and off time of 2 minutes. 
You may verify the status of heating and cooling stages 

and fan in monitoring screens #5, #6, and #7, which are 

accessed by pressing the SERVICE STATUS button. 
1.  Verify all wiring prior to powering the thermostat.
2. Turn power on.  The thermostat will display a momen-

tary screen with the model number , and then the 

main monitoring screen with the time, day, date 

(SZ1031 and SZ1035 only), and current temperature. 

3. Press the PROGRAM SETUP button until you reach 

the screen #14 which allows you to set the occupant 

P + I OPTION 

The SZ1022, SZ1031, and SZ1035 also have a P+I 

option. Without enabling this option, stages turn on 

and off based on temperature vs. setpoint alone, as 

described above. By enabling this option, you allow a 

time factor to be added. This is useful when you are 

forced to have a large differential due to equipment size. 

At times when the building load is low, the tempera-

ture could potentially sit a few degrees off setpoint for 

some time. With the time factor added, the thermostat 

would compensate for this, turning on the equipment 

even though the temperature had not reached the limits 

described above. 

DI2 COOL LOCKOUT

DI2 may be set as cool lockout for operation with econo-

mizers. An outdoor temperature switch may be wired in 

such that when DI2 is closed, the second stage of cool-

ing is disabled.

SMART RECOVERY 

“Smart Recovery” may be enabled to insure occupant 

comfort while saving money. It takes the building load 

into consideration and ramps the setpoint when going 

from the unoccupied mode to the occupied mode. At the 

beginning of the occupied mode, the occupied setpoint 

will be reached, many times without the need for the 

second stage to come on. This feature is automatically 

disabled when DI3 is set to external time clock.

AUXILIARY OUTPUT 

An auxiliary relay output is available to output a signal 

based on the occupancy status. It is commonly used 

with an economizer minimum position control, or to sig-

nal an outdoor air damper to open in occupied times in 

lieu of an economizer. It may also be used for lighting 

or hot water heaters. Keep in mind that although it is an 

isolated relay (separate common terminal), it is rated 

at 24 VAC. For loads that exceed this, use an external 

relay. It may be set to be open (NO) or closed (NC) 

when the thermostat is operating in the occupied mode, 

and will be the opposite during the unoccupied mode. 

BUILT-IN DELAYS 

The SZ1022, SZ1031, and SZ1035 have delays built 

into the programming sequences to protect equipment. 

The fan has a minimum on and off time of 30 seconds. 

When the fan is in AUTO mode, it will come on 30 sec-

onds before the heating or cooling stages are allowed 

to sequence on, and remain on for 2 minutes after the 

heating or cooling stages sequence off. Each stage has 

a minimum on and off time of two minutes. There is a 

minimum of two minutes between when one stage turns 

on until the next stage is allowed to turn on, as well as 

when one stage turns off until the next stage is allowed 

to turn off. 

MON 

11-19-07

12:00  AM                72F

* SZ1022 *

TCS V2.0 (C)   

Содержание SZ1022

Страница 1: ...or limited with the use of an access code Fahrenheit or Celsius temperature display Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500...

Страница 2: ...install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit transformer Wiring The SZ1022 SZ1031 and SZ1035 use standard terminal designation...

Страница 3: ...sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1031 and SZ1035 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock...

Страница 4: ...aud Rate Screen If using a PC to do programming all controllers on a network must be set to the same baud rate Choose between 2 4K 4 8K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and...

Страница 5: ...4TH STAGE AS COOL 25 program setup ENABLE THIRD STAGE AS DISABLE 26 program setup HEAT STAGE 1 OFFSET 0F 27 program setup OCCUPIED COOL SETPOINT B 75F 16 program setup OCCUPIED COOL SETPOINT C 75F 17...

Страница 6: ...etup ENABLE OUTDOOR AIR FUNCT YES 44 DISCHARGE AIR LOW LIMIT 45F ENABLE DISCHARGE AIR FUNCT YES program setup 41 program setup TIMECLOCK OUTPUT OCCUPIED CLOSED program setup 40 DISCHARGE AIR HIGH LIMI...

Страница 7: ...CONDS DI3 USED FOR FILTER SERVICE program setup 50 program setup SET DI2 SETPOINT SHIFT 00F program setup 49 ENABLE SMART RECOVERY NO 52 program setup 51 program setup SET ACCESS CODE 248 55 MON 11 19...

Страница 8: ...ed Times Screen Set hours and minutes of start and end times for up to two occupied periods Schedule Announcement Screen Announces the next screen Copy Schedule Screen Indicate whether or not to use t...

Страница 9: ...such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to set the DI3 to external override and use the timed override button to put the...

Страница 10: ...ment to the building load The offset value is the amount away from the setpoint a stage will turn off By assign ing a stage a value other than zero you anticipate that the residual heat or cooling in...

Страница 11: ...35 also have a P I option Without enabling this option stages turn on and off based on temperature vs setpoint alone as described above By enabling this option you allow a time factor to be added This...

Страница 12: ...support you may be able to use the on board adjustment pots Refer to the Thermostat Sensor Calibration Tech Bulletin 1005 for details setpoint adjustment limits Change this to 20 F 11 1 C Press the P...

Страница 13: ...the override is active and if so how many minutes remain ing service status MON 11 19 01 12 00 AM 72F service status SERVICE STATUS OK 1 service status OUTDOOR AIR TEMP 75F 3 service status DISCHARGE...

Страница 14: ...allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedul...

Отзывы: