2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

4

Programming                          

The SZ1022, SZ1031, and SZ1035 may be programmed 

through the keypad on the face, or with a PC. 
If programming with a PC, the following must be set via 

the display and keypad 

prior

 to programming:

• Address (step #2)

• Baud rate (step #3)

• Temperature scale (step #4) 

 

For more information on programming through the PC, 

consult your TCS software manual. 

PROGRAMMING THROUGH THE KEYPAD

To access the programming screens, press the program 

setup button.  To make changes, use the warmer and 

cooler keys.  Access may be locked out with dipswitch-

es, or an access code may be required. 

fan

Occupied

Heating

Cooling

Fan

Service

Program/

COOLER

WARMER

Data

switch

system

switch

program

setup

clock

setup

override

service

status

Main Monitoring Screen.

  Press the pro-

gram setup button to access the following 

screens.  (Date not shown on SZ1022.)

    

    

    

Access Code Entry Screen.

  Will appear  

if access code is required for program-

ming.  Use 248 as the default.  If the 

wrong code is entered, it will revert to the 

previous screen.   

 

 

    

Controller Address Screen.

  If using 

a PC to program, set a unique address 

from 0 to 255, excluding 248.  All control-

lers on a network must have a separate 

and  unique communications address. 

 

Communication Baud Rate Screen.  

 

If using a PC to do programming, 

all 

controllers on a network must be set to 

the same baud rate

.  Choose between 

2.4K, 4.8K, 9.6K and 19.2K.  

 

 
 
Display Type Screen.  

Choose between 

FAHRENHEIT and CELSIUS for tem-

perature indication.

    

 

System Access Screen.  

Choose 

whether or not to enable user’s access 

to the system switch to set the system 

mode. 

 

System Mode Screen.  

Choose from 

AUTO, HEAT, COOL, or OFF for your 

system mode.  In the OFF mode, no 

contacts shall close. 

Fan Access Screen.  

Choose whether 

or not to enable the user’s access to the 

fan switch to set the occupied fan mode.   

(See page 8.)

   

 

 

Occupied Fan Mode Screen.  

Choose 

between ON (continuous), COOL (gas 

heat or no heat), or AUTO for your fan 

run times during the occupied modes. 

    

  

Unoccupied Fan Mode Screen.  

Choose from ON, COOL, or AUTO for 

your fan run times in the unoccupied 

mode.  

 

   

Occupied Heat Setpoint Screen.  

Set 

the heat setpoint for this occupied  

period.  

Occupied Heat Setpoint Screen.  

Set 

the heat setpoint for this occupied  

period.  

 

   

SET ADDRESS:

000

program

setup

program

setup

2.

ENTER ACCESS 

CODE 

000

program

setup

1.

MON 

11-19-07

12:00 AM            72F

program

setup

SET BAUD RATE:

9.6k

3.

program

setup

TEMP SHOWN IN:

FAHRENHEIT

4.

program

setup

OCCUPIED HEAT

SETPOINT A:       70F

10.

program

setup

SET UNOCCUPIED

FAN MODE:       AUTO

9.

program

setup

SET OCCUPIED FAN

MODE:                      ON

8.

program

setup

USER ACCESS TO

FAN  MODE?      YES

7.

program

setup

SET SYSTEM

MODE: 

AUTO

6.

program

setup

USER ACCESS TO

SYSTEM MODE? YES

5.

program

setup

OCCUPIED HEAT

SETPOINT B:       70F

11.

Содержание SZ1022

Страница 1: ...or limited with the use of an access code Fahrenheit or Celsius temperature display Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500...

Страница 2: ...install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit transformer Wiring The SZ1022 SZ1031 and SZ1035 use standard terminal designation...

Страница 3: ...sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1031 and SZ1035 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock...

Страница 4: ...aud Rate Screen If using a PC to do programming all controllers on a network must be set to the same baud rate Choose between 2 4K 4 8K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and...

Страница 5: ...4TH STAGE AS COOL 25 program setup ENABLE THIRD STAGE AS DISABLE 26 program setup HEAT STAGE 1 OFFSET 0F 27 program setup OCCUPIED COOL SETPOINT B 75F 16 program setup OCCUPIED COOL SETPOINT C 75F 17...

Страница 6: ...etup ENABLE OUTDOOR AIR FUNCT YES 44 DISCHARGE AIR LOW LIMIT 45F ENABLE DISCHARGE AIR FUNCT YES program setup 41 program setup TIMECLOCK OUTPUT OCCUPIED CLOSED program setup 40 DISCHARGE AIR HIGH LIMI...

Страница 7: ...CONDS DI3 USED FOR FILTER SERVICE program setup 50 program setup SET DI2 SETPOINT SHIFT 00F program setup 49 ENABLE SMART RECOVERY NO 52 program setup 51 program setup SET ACCESS CODE 248 55 MON 11 19...

Страница 8: ...ed Times Screen Set hours and minutes of start and end times for up to two occupied periods Schedule Announcement Screen Announces the next screen Copy Schedule Screen Indicate whether or not to use t...

Страница 9: ...such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to set the DI3 to external override and use the timed override button to put the...

Страница 10: ...ment to the building load The offset value is the amount away from the setpoint a stage will turn off By assign ing a stage a value other than zero you anticipate that the residual heat or cooling in...

Страница 11: ...35 also have a P I option Without enabling this option stages turn on and off based on temperature vs setpoint alone as described above By enabling this option you allow a time factor to be added This...

Страница 12: ...support you may be able to use the on board adjustment pots Refer to the Thermostat Sensor Calibration Tech Bulletin 1005 for details setpoint adjustment limits Change this to 20 F 11 1 C Press the P...

Страница 13: ...the override is active and if so how many minutes remain ing service status MON 11 19 01 12 00 AM 72F service status SERVICE STATUS OK 1 service status OUTDOOR AIR TEMP 75F 3 service status DISCHARGE...

Страница 14: ...allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedul...

Отзывы: