Energier pro User Manual
28
Using DIP Switch 7, you can set the system in power save mode. Please refer to chapter 2.12 for explanation.
This configuration will adjust the minimum quality of AC input which Energier pro Inverter Charger Combination will
qualify and pass through to your AC appliance. Voltage or frequency variation might cause damage for particular load.
Before adjusting these setting, refer to electrical rating of connected load. Failure to follow the instruction can cause
damage over appliance connected.
4.7 Power Save mode (PS mode)
Through DIP Switch 1 and 8, you could configure the system to different modes for different appliance. For explanation, please refer
to chapter 2.11.
Through RCF supplied, you can set the AC input current. This configuration can be done only after Energier pro Inverter Charger Combination
was switched on.
Please refer to chapter 7.2 for detail instruction.
4.8 Weak Grid and GEN mode
4.9 AC input current setting
Dip switch 1
Dip switch 8
Mode
Voltage range
Frequency range
Waveform
On
On
Off
Off
Off
On
Off
On
Weak Grid
GEN & Weak Grid
Standard
GEN
167 VAC-264 VAC
167 VAC-276 VAC
184 VAC-264 VAC
173 VAC-276 VAC
45 Hz-65 Hz
40 Hz-70 Hz
45 Hz-65 Hz
40 Hz-70 Hz
sensitive
less sensitive
sensitive
less sensitive
Содержание Energier Pro CF2060L
Страница 1: ...User Manual Energier Pro series Inverter Charger Combination TBB Power CO ltd www tbbpower com A3 4...
Страница 2: ...Energier pro User Manual...
Страница 23: ...Energier pro User Manual 16 3 1 2 RCF remote 3 1 3 Vision Lite 3 1 4 AGS 3 1 5 TAI...
Страница 25: ...Energier pro User Manual 18 3 CF4080M CF50100M CF5050S CF6060S CF8080S 3 2 2 RCF remote 3 2 3 Vision Lite...
Страница 26: ...Energier pro User Manual 19 3 2 4 AGS 3 2 5 TAI...