45
Pickup overfrequency-, Hz
OFp-
50.01 - 55.00 for Frated=50Hz
60.01 - 65.00 for Frated=60Hz
50.50 for Frated=50Hz
60.50 for Frated=60Hz
Autoreclosing Timeout (ART)
Reclosing will be made only if the voltage from source side of protection device (protection device is Open)
meets the requirements of VRC element. Otherwise, device will not reclose. If the voltage did not recover until
Autoreclosing timeout is expired, protection device will go to lockout.
ART settings are described in Table 60.
Table 60
– ART element settings
Settings
Designation
Range
Step size
Default
Autoreclosing timeout, min
ART
00.00.01
–06.00.00
00.00.01
00.01.00
Undervoltage (UV)
This element provides a trip command when the voltage falls below a set value.
UV settings are described in Table 61 and Table 62.
Table 61
– Radial line recloser UV element settings
Settings
Designation
Range
Step size
Default
Operating mode
Mode
Enable/Disable
n.a.
Disable
Pickup voltage multiplier
Up
0.60
–1.00
0.01
0.80
Tripping time, s
Tt
0.10
–100.00
0.01
10.00
Table 62
– Ring line recloser UV element settings
Settings
Designation
Range
Step size
Default
Operating mode+
Mode+
Enable/Disable
n.a.
Disable
Pickup voltage mul
Up+
0.60
–1.00
0.01
0.80
Tripping time+, s
Tt+
0.10
–100.00
0.01
10.00
Operating mode-
Mode-
Enable/Disable
n.a.
Disable
Pickup voltage multiplier-
Up-
0.60
–1.00
0.01
0.80
Tripping time-, s
Tt-
0.10
–100.00
0.01
10.00
Undervoltage Reclosing (AR UV)
This element provides reclosing initiated by the UV element operation.
AR UV settings are described in Table 63 and Table 64.
Table 63
– Radial line recloser AR UV element settings
Settings
Designation
Range
Step size
Default
Number of trips to lockout
Nt
1/2
n.a.
1
Reclose time, s
Tr
0.10
–180.00
0.01
10.00
Table 64
– Ring line recloser AR UV element settings
Settings
Designation
Range
Step size
Default
Number of trips to
Nt+
1/2
n.a.
1
Reclose time+, s
Tr+
0.10
–180.00
0.01
10.00
Number of trips to lockout-
Nt-
1/2
n.a.
1
Reclose time-, s
Tr-
0.10
–180.00
0.01
10.00
Содержание Rec15
Страница 1: ......
Страница 5: ...1 Introduction...
Страница 9: ...2 Technical Parameters...
Страница 14: ...3 Product Description...
Страница 26: ...26 Figure 25 Anti vandal housing...
Страница 27: ...4 Functionality...
Страница 56: ...5 Product Handling...
Страница 69: ...6 Installation...
Страница 81: ...7 Commissioning...
Страница 84: ...8 Operation...
Страница 99: ...99 Figure 76 Settings uploading wizard...
Страница 100: ...9 Maintenance and Troubleshooting...
Страница 114: ...114 Figure 90 Securing the trip hook shaft against rotation...
Страница 115: ...10 Product Coding...
Страница 122: ...11 Appendices...
Страница 128: ...128 Appendix 4 Recloser Control Drawings Figure 99 Dimensions of RC5_4...
Страница 131: ...131 Figure 103 Dimensions of substation recloser package Figure 104 Placement of substation recloser components in a box...
Страница 133: ...133 Figure 106 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Страница 134: ...134 Figure 107 Dimensions of interface bracket...
Страница 135: ...135 Figure 108 Dimensions of OSM mounting kit with M16 pole interface front installation...
Страница 136: ...136 Figure 109 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Страница 137: ...137 Figure 110 Dimensions of OSM mounting kit with M20 pole interface front installation...
Страница 138: ...138 Figure 111 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Страница 139: ...139 Figure 112 Dimensions of OSM mounting kit for installation through the pole front installation...
Страница 140: ...140 Figure 113 Dimensions of OSM mounting kit for installation through the pole lateral installation...
Страница 149: ...149 Figure 122 Dimensions of OSM substation mounting kit...
Страница 150: ...150 Figure 123 Dimensions of RC mounting kit for around the pole installation 500 mm U profiles 450 mm M16 threaded rods...
Страница 152: ...152 Figure 125 Dimensions of RC mounting kit for through the pole installation...
Страница 153: ...153 Figure 126 Dimensions of RC substation mounting kit...
Страница 154: ...154 Figure 127 Dimensions of VT mounting kit One VT holder...
Страница 157: ...157 Figure 132 Dimensions of VT mounting kit Two VT holders two 500 mm U profiles and M16 threaded rods...
Страница 158: ...158 Figure 133 Dimensions of VT mounting kit Two VT holders two 700 mm U profiles and M20 threaded rods...
Страница 159: ...159 Figure 134 Dimensions of VT mounting kit Two VT holders four 500 mm U profiles and M16 threaded rods...
Страница 163: ...163 Appendix 8 Connectors Drawings Figure 141 Dimensions of aerial connector...
Страница 164: ...164 Figure 142 Dimensions of bird guards for aerial connector...
Страница 165: ...165 Figure 143 Dimensions of two hole NEMA connector...
Страница 166: ...166 Figure 144 Dimensions of bird guards for two hole NEMA connector...
Страница 167: ...167 Figure 145 Dimensions of four hole NEMA connector...
Страница 168: ...168 Figure 146 Dimensions of bird guards for four hole NEMA connector...
Страница 169: ...169 Figure 147 Dimensions of Burndy NEMA connector...
Страница 170: ...170 Appendix 9 Recloser Control Wiring Diagram Figure 148 RC5_4 wiring diagram...
Страница 172: ......