The algorithm provides the set-up simplicity of a traditional sectionalizer and at the same time reducing the
fault clearing time and network reconfiguration time application in far more complex networks and provide an
unlimited number of sections to limit the number of customers affected.
Rezip is applicable in meshed grid automation schemes together with ABR functionality. Rezip enables the
building of self-healing networks where it is not possible with conventional reclosers and sectionalizers.
Zone Sequence Coordination
The AR OC provides Zone Sequence Coordination (ZSC). ZSC forces the AR OC element to step to the next
count in the reclose sequence on reset of all protection elements if it detects a downstream protection device
has operated. This functionality is required for applications where a fuse-saving philosophy is used.
Hot Line (HL)
This element consists of two sub-elements which provide protection against short circuit faults during Hot Line
maintenance. It generally has more sensitive settings than corresponding OCR settings and it has no reclosing
functions. HL consists of two Overcurrent elements, one for Phase Overcurrent (HLOC) and one for Earth
Fault (HLEF). Operation of either element results in the trip to lockout.
HL settings are described in Tables 43-46.
Table 38
– Radial line recloser HLOC element settings
Settings
Designation
Range
Step size
Default
Pickup current, A
Ip
10-1280
1
10
Tripping time, s
Tt
0.00
–2.00
0.01
0.00
Table 39
– Ring line recloser HLOC element settings
Settings
Designation
Range
Step size
Default
Pickup , A
Ip+
10-1280
1
10
Tripping time+, s
Tt+
0.00
–2.00
0.01
0.00
Pickup current-, A
Ip-
10-1280
1
10
Tripping time-, s
Tt-
0.00
–2.00
0.01
0.00
Table 40
– Radial line recloser HLEF element settings
Settings
Designation
Range
Step size
Default
Pickup current, A
Ip
4-1280
1
4
Tripping time, s
Tt
0.00
–2.00
0.01
0.00
Table 41
– Ring line recloser HLEF element settings
Settings
Designation
Range
Step size
Default
Pickup , A
Ip+
4-1280
1
4
Tripping time+, s
Tt+
0.00
–2.00
0.01
0.00
Pickup current-, A
Ip-
4-1280
1
4
Tripping time-, s
Tt-
0.00
–2.00
0.01
0.00
Sensitive Earth Fault (SEF)
This element provides protection against high impedance earth faults.
SEF settings are described in Table 42 and Table 43.
SEF TD and custom time current curves settings are described in Table 44 and Table 45.
Table 42
– Radial line recloser SEF element settings
Settings
Designation
Range
Step size
Default
Operating mode
Mode
Disable/Alarm/Trip
Trip
Содержание Rec15
Страница 1: ......
Страница 5: ...1 Introduction...
Страница 9: ...2 Technical Parameters...
Страница 14: ...3 Product Description...
Страница 26: ...26 Figure 25 Anti vandal housing...
Страница 27: ...4 Functionality...
Страница 56: ...5 Product Handling...
Страница 69: ...6 Installation...
Страница 81: ...7 Commissioning...
Страница 84: ...8 Operation...
Страница 99: ...99 Figure 76 Settings uploading wizard...
Страница 100: ...9 Maintenance and Troubleshooting...
Страница 114: ...114 Figure 90 Securing the trip hook shaft against rotation...
Страница 115: ...10 Product Coding...
Страница 122: ...11 Appendices...
Страница 128: ...128 Appendix 4 Recloser Control Drawings Figure 99 Dimensions of RC5_4...
Страница 131: ...131 Figure 103 Dimensions of substation recloser package Figure 104 Placement of substation recloser components in a box...
Страница 133: ...133 Figure 106 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Страница 134: ...134 Figure 107 Dimensions of interface bracket...
Страница 135: ...135 Figure 108 Dimensions of OSM mounting kit with M16 pole interface front installation...
Страница 136: ...136 Figure 109 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Страница 137: ...137 Figure 110 Dimensions of OSM mounting kit with M20 pole interface front installation...
Страница 138: ...138 Figure 111 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Страница 139: ...139 Figure 112 Dimensions of OSM mounting kit for installation through the pole front installation...
Страница 140: ...140 Figure 113 Dimensions of OSM mounting kit for installation through the pole lateral installation...
Страница 149: ...149 Figure 122 Dimensions of OSM substation mounting kit...
Страница 150: ...150 Figure 123 Dimensions of RC mounting kit for around the pole installation 500 mm U profiles 450 mm M16 threaded rods...
Страница 152: ...152 Figure 125 Dimensions of RC mounting kit for through the pole installation...
Страница 153: ...153 Figure 126 Dimensions of RC substation mounting kit...
Страница 154: ...154 Figure 127 Dimensions of VT mounting kit One VT holder...
Страница 157: ...157 Figure 132 Dimensions of VT mounting kit Two VT holders two 500 mm U profiles and M16 threaded rods...
Страница 158: ...158 Figure 133 Dimensions of VT mounting kit Two VT holders two 700 mm U profiles and M20 threaded rods...
Страница 159: ...159 Figure 134 Dimensions of VT mounting kit Two VT holders four 500 mm U profiles and M16 threaded rods...
Страница 163: ...163 Appendix 8 Connectors Drawings Figure 141 Dimensions of aerial connector...
Страница 164: ...164 Figure 142 Dimensions of bird guards for aerial connector...
Страница 165: ...165 Figure 143 Dimensions of two hole NEMA connector...
Страница 166: ...166 Figure 144 Dimensions of bird guards for two hole NEMA connector...
Страница 167: ...167 Figure 145 Dimensions of four hole NEMA connector...
Страница 168: ...168 Figure 146 Dimensions of bird guards for four hole NEMA connector...
Страница 169: ...169 Figure 147 Dimensions of Burndy NEMA connector...
Страница 170: ...170 Appendix 9 Recloser Control Wiring Diagram Figure 148 RC5_4 wiring diagram...
Страница 172: ......