Table 75
– Radial line recloser AR OF element settings
Settings
Designation
Range
Step size
Default
Number of trips to lockout
Nt
1/2
n.a.
1
Reclose time, s
Tr
0.10
–180.00
0.01
10.00
Table 76
– Ring line recloser AR OF element settings
Settings
Designation
Range
Step size
Default
Number of trips to
Nt+
1/2
n.a.
1
Reclose time+, s
Tr+
0.10
–180.00
0.01
10.00
Number of trips to lockout-
Nt-
1/2
n.a.
1
Reclose time-, s
Tr-
0.10
–180.00
0.01
10.00
Automatic Backfeed Restoration (ABR)
Automatic Backfeed Restoration is used to automatically close a normally open recloser if it detects a source
(via the SD element) on the either side of the recloser and absence of a source on the other side.
ABR function is designed to provide maximum safety for operators and equipment. Restoration disarm function
will prevent circuit-breaker closing for the ABR function in case power supply is absent from both sides longer
than specified Restoration disarm timeout (Trd) setting.
This element is only applicable for ring line type reclosers.
ABR element settings are described in Table 77.
Table 77
– ABR element settings
Settings
Designation
Range
Step size
Default
Operating mode
Mode
Disable/Both/Only+/Only-
n.a.
Disable
Restoration disarm mode
RD mode
Enable/Disable
n.a.
Disable
Restoration disarm timeout
Trd
00.00.01
–06.00.00
00.00.01
00.00.10
Restoration time+, s
Tr-
0.10
–180.00
0.01
60.00
Restoration time-, s
Tr-
0.10
–180.00
0.01
60.00
Close Condition Verifier (CCV)
The Close Condition Verifier element controls breaker closing requests generated from local or remote
interfaces, an input/output module, or protection elements. If the network situation complies with the CCV
closing settings, closing is unblocked and vice versa.
A Hot tag for side + or
– is generated if the Source Detector identifies that a source is found and the Voltage
Reclosing Control element identifies that the power quality is within the acceptable limits.
A Dead tag for side + or
– is generated if the Source Detector identifies that a source is lost.
The CCV functionality can be Enabled or Disabled via the configuration menu. The CCV element settings are
described in Table 78.
Table 78
– CCV element settings
Settings
Designation
Range
Step size
Default
CCV enabled/disabled
Hot+ / Dead- allowed
Hot+ / Dead- allowed
Enable/Disable
n.a.
Disable
Hot- / Dead+ allowed
Hot- / Dead+ allowed
Enable/Disable
n.a.
Disable
Dead- / Dead+ allowed
Dead- / Dead+ allowed
Enable/Disable
n.a.
Disable
Hot+ / Hot- allowed
Hot+ / Hot- allowed
Enable/Disable
n.a.
Disable
Synchronization Indicator (SI)
The Synchronization Indicator is active only if the CCV setting Hot+ / Hot- allowed = Enabled. The SI element
monitors voltage magnitude and phase angle differences from both sides of the recloser. The CCV element
Содержание Rec15
Страница 1: ......
Страница 5: ...1 Introduction...
Страница 9: ...2 Technical Parameters...
Страница 14: ...3 Product Description...
Страница 26: ...26 Figure 25 Anti vandal housing...
Страница 27: ...4 Functionality...
Страница 56: ...5 Product Handling...
Страница 69: ...6 Installation...
Страница 81: ...7 Commissioning...
Страница 84: ...8 Operation...
Страница 99: ...99 Figure 76 Settings uploading wizard...
Страница 100: ...9 Maintenance and Troubleshooting...
Страница 114: ...114 Figure 90 Securing the trip hook shaft against rotation...
Страница 115: ...10 Product Coding...
Страница 122: ...11 Appendices...
Страница 128: ...128 Appendix 4 Recloser Control Drawings Figure 99 Dimensions of RC5_4...
Страница 131: ...131 Figure 103 Dimensions of substation recloser package Figure 104 Placement of substation recloser components in a box...
Страница 133: ...133 Figure 106 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Страница 134: ...134 Figure 107 Dimensions of interface bracket...
Страница 135: ...135 Figure 108 Dimensions of OSM mounting kit with M16 pole interface front installation...
Страница 136: ...136 Figure 109 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Страница 137: ...137 Figure 110 Dimensions of OSM mounting kit with M20 pole interface front installation...
Страница 138: ...138 Figure 111 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Страница 139: ...139 Figure 112 Dimensions of OSM mounting kit for installation through the pole front installation...
Страница 140: ...140 Figure 113 Dimensions of OSM mounting kit for installation through the pole lateral installation...
Страница 149: ...149 Figure 122 Dimensions of OSM substation mounting kit...
Страница 150: ...150 Figure 123 Dimensions of RC mounting kit for around the pole installation 500 mm U profiles 450 mm M16 threaded rods...
Страница 152: ...152 Figure 125 Dimensions of RC mounting kit for through the pole installation...
Страница 153: ...153 Figure 126 Dimensions of RC substation mounting kit...
Страница 154: ...154 Figure 127 Dimensions of VT mounting kit One VT holder...
Страница 157: ...157 Figure 132 Dimensions of VT mounting kit Two VT holders two 500 mm U profiles and M16 threaded rods...
Страница 158: ...158 Figure 133 Dimensions of VT mounting kit Two VT holders two 700 mm U profiles and M20 threaded rods...
Страница 159: ...159 Figure 134 Dimensions of VT mounting kit Two VT holders four 500 mm U profiles and M16 threaded rods...
Страница 163: ...163 Appendix 8 Connectors Drawings Figure 141 Dimensions of aerial connector...
Страница 164: ...164 Figure 142 Dimensions of bird guards for aerial connector...
Страница 165: ...165 Figure 143 Dimensions of two hole NEMA connector...
Страница 166: ...166 Figure 144 Dimensions of bird guards for two hole NEMA connector...
Страница 167: ...167 Figure 145 Dimensions of four hole NEMA connector...
Страница 168: ...168 Figure 146 Dimensions of bird guards for four hole NEMA connector...
Страница 169: ...169 Figure 147 Dimensions of Burndy NEMA connector...
Страница 170: ...170 Appendix 9 Recloser Control Wiring Diagram Figure 148 RC5_4 wiring diagram...
Страница 172: ......