7. Operation Chart
7-1 Standard Operation Chart
(Factory setting)
For the operation chart, refer to Drawing 13.
Power
Power Indicator LED
Water leakage
detection function
Alarm Indicator LED
Break detection function
Buzzer Stop Switch
Buzzer sounding
OFF
ON
Lighting
out
Lighting
up
OFF
Lighting
out
OFF
OFF
OFF
ON
OFF
Flashing
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
Open
Open
Closed
Open
Closed
Open
Control output contact
(water leakage: COM-NO)
Control output contact
(break: COM-NO)
Lighting up
Sensor length indication
No
indication
Water leakage
location indication
No
indication
*1 Indication
Indicating ---
*1 Indication
*1 The sensor length and the water leakage location is indicated alternately.
Lighting
out
Lighting
out
20
mA
Water leakage location
data output
(4-20 mA output)
4
mA
4
mA
4
mA
OFF
6 + 0.03 x water leakage location indication (m) mA
4 + 16 x water leakage location indication (m) / 250 (m) mA
or
Drawing 13 Operation Chart-1
Regarding Buzzer
Pressing the buzzer stop switch stops the buzzer.
When the system detects another water leakage or a break, the buzzer sounds again. Turning No.1 operational
setting switch ON prevents the buzzer from sounding at any time.
It is possible to set the buzzer from the host system by the Modbus communication.
-7-