6.  Operation  Check 

6-1  Power-On 

When the detector is powered on, the Power Indicator LED and the LCD Backlight are Lighting up.   

(Refer to Drawing 10.) 

In the case in which either or both of the LEDs does not light up, the detector may be out of order. Power off 
the detector promptly and contact the manufacturer. 

 

 
 
 
 
 
 
 
 
 

 

Drawing 10 Power-On Operation

 

6-2  Check  for  Break  Detection  Function 

1) 

After powering off the detector

, remove the water leakage sensor from the trunk terminal block and then 

power on the detector. 

2)  The buzzer sounds, the Alarm Indicator LED flashes and the contacts (for break detection) function. 

3)  LCD 

indicates “----m“. (Refer to Drawing 11.) 

4)  After the operation check, 

power off the detector

 and then connect the sensor to the terminal block again.   

 

 
 
 
 
 
 
 

 

 

 

Drawing 11. Indication in the Case of Break Detection¥ 

6-3  Check  for  Water  Leakage  Detection  Function 

1)  Drop tap water on the sensor. 

2)  The buzzer sounds, the Alarm Indicator LED lights up and the contacts (for water leakage detection) 

function. 

3)  LCD indicates as shown in Drawing 12. 

Example: In the case in which a sensor with a length of 1500 meters is connected and a point at 1000 
meters is wetted.   

4)  Wipe the tap water dropped on the sensor with dry rags, etc. and check that the water leakage status 

returns to normal. 

 
 
 
 
 
 
 
 
 

Drawing 12 Indication in the Case of Water Leakage Detection

 

-6- 

  No.000
  SL   1500m

Length

Leak Point

Lighting up

Lighting up(Lighting out at a certain time)

  No.000
  SL  ----m

Length

Leak Point

Lighting up

Lighting up(Lighting out at a certain time)

No.001
SL      1500m

LEAKAGE LOCATION DETECTOR

Buzzer Stop

Reset

Length

Leak Point

AD-AS-1LDM

Dector 

Number

Lighting out

LP      1000m
SL      1500m

LEAKAGE LOCATION DETECTOR

Buzzer Stop

Reset

Length

Leak Point

AD-AS-1LDM

Flashing

Sensor 

Length

Water leakage 
location

displayed alternately

Sensor
Length

Lighting up(Lighting out at a certain time)

SL      400m 

No.000 

No.001 
SL      400m 

LP      200m 
SL      400m 

Содержание AD-AS-1LDMA

Страница 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LDMA Operation Manual System Equipment Division Electronic Material System Equipment Group Tatsuta Electric Wire Cable Co Ltd...

Страница 2: ...Locations easily accessible to the general public Locations close to sources of vibration organic gas or strong electromagnetic induction Locations subject to excessive waste and dust Locations where...

Страница 3: ...ks 3 17 Osadano cho Fukuchiyama City Kyoto 620 0853 Tel 81 773 45 6500 Fax 81 773 45 6501 Tatsuta Technical Center 6 5 1 Kunimidai Kizugawa City Kyoto 619 0216 Tel 81 774 66 5550 Fax 81 774 66 5556 Sh...

Страница 4: ...ection Function 7 Operation Chart 7 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Modbus Address 9 9 Detection Sensitivity Setting 9 10 Buzzer S...

Страница 5: ...stallation The Water Leakage Location Detector AD AS 1LDMA shall be securely installed in a strong housing on the wall etc inside a building Be sure to follow the following instructions when installin...

Страница 6: ...sor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA Reports to the host system by Modbus communication Drawing 2 Water Leakage Loc...

Страница 7: ...ring make sure that the power is switched off Drawing 4 AD LS Sensor Structure Table 1 AD LS Sensor Configuration Element Configuration Braided wire 0 33mm2 tinned soft copper wire covered with red pl...

Страница 8: ...a Output Connection 5 5 1 Connection The AD AS 1LDMA has a function that outputs the water leakage location by DC electrical current Option Use an analog input device with an input resistance of 500 o...

Страница 9: ...l analog input devices are broken 2 The input resistance for the external analog input devices is more than 500 If there is no problem with the items above the detector may be out of order Contact the...

Страница 10: ...unction 1 Drop tap water on the sensor 2 The buzzer sounds the Alarm Indicator LED lights up and the contacts for water leakage detection function 3 LCD indicates as shown in Drawing 12 Example In the...

Страница 11: ...indication No indication 1 Indication Indicating 1 Indication 1 The sensor length and the water leakage location is indicated alternately Lighting out Lighting out 20 Water leakage location data outp...

Страница 12: ...er leakage location indication Water leakage location data output 4 20 mA output 6 0 03 x water leakage location indication m mA 4 16 x water leakage location indication m 250 m mA or Drawing 14 Opera...

Страница 13: ...o detect fluid with high electrical resistance such as pure water in an environment where the temperature and humidity are stable such as a clean room it is recommended to set the sensitivity level hi...

Страница 14: ...larm buzzer Average sound pressure 90 dB 10 cm catalogue value by manufacturer Control output contact Contact Configuration Contacts For specifications refer to Section 11 2 Water leakage 1 for 1a Bre...

Страница 15: ...ak Point AD AS 1LDMA Power E 1 2 3 Sensor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA mm Approved by N a m e Prepared by Check...

Страница 16: ...I n s u l a t e d w i r e R e s i s t a n c e w i r e C O M N O Power source AC24V or DC24V G r o u n d i n g c o n n e c t i o n E H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Atta...

Страница 17: ...N Available OFF Contact a ON Contact b Operational setting OFF OFF OFF OFF OFF Activated ON Not activated Alarm hold for water leakage location indication 1 2 3 4 Terminal resistance setting Setting o...

Страница 18: ...et Length Leak Point AD AS 1LDMA Modbus address LIT Indication in the case of water leakage detection No 001 SL 400m LEAKAGE LOCATION DETECTOR Buzzer Stop Reset Length Leak Point AD AS 1LDMA Modbus ad...

Страница 19: ...ws Addresses 1 to 9 Dials 1 to 9 Address 10 Dial A Address 11 Dial B Address 12 Dial C Address 13 Dial D Address 14 Dial E Address 15 Dial F To set an address between 16 and 127 set the dial at 0 and...

Страница 20: ...sing the Reset switch allow the desired number to appear Each time you push the switch the figure increases one by one in order 0 1 2 3 4 5 6 7 8 9 0 When the address you desire is indicated press and...

Отзывы: