11-3  Performances 

 

For performances, refer to Table 4. 

 

Table 4 Performances 

Item 

Specification 

Number  of  sensor  circuit 

1

 

 

Length  of  sensor  connection  1  to  1500  m 
Detection  sensitivity  level   
setting 

Low 

Standard 

High 

Highest 

Water  leakage  detection 
sensitivity 

10  ±  2.0

kΩ 

25  ±  2.5

kΩ 

50  ±  5.0

kΩ 

100  ±  10.0

kΩ 

Sensitivity  in  the  case  of   
recovery  from  water  leakage 

16  ±  3.0

kΩ 

37  ±  3.7

kΩ 

68k

Ω  ±  6.8kΩ 

125  ±  12.5

kΩ 

Detection  accuracy 

1  to  100  m:  ±1  m 
101  to  400  m:  sensor  length  ±

 

1% 

Surface  panel  operation   
switch  function 

Buzzer  stop  switch:  1 
Alarm  cancel  switch:  1 

Surface  panel 

  LED  indication 

 

Power  source  indication,  green:  1  (lighting  up) 

 

Alarm  indication,  red:  1  (flashing  in  the  case  of  water  leakage  detection) 

(lighting  up  in  the  case  of  break  detection) 

  Meintenance  indication:  1 

Surface  panel 
LCD  indication 

 

Modbus  Address:  1  to  127 

Sensor  length  and  water  leakage  location  indication:   
meter  display  or  feet  display 

Surface  panel  operational   
setting  switch 

 

Used  for  setting  change  of  indication,  control  output  contacts,  detection 

  sensitivity  level,  etc. 

 

For  details,  refer  to  Attached  Drawing  3. 

Alarm  buzzer 

Average  sound  pressure:  90  dB/10  cm  (catalogue  value  by  manufacturer) 

Control  output  contact 

Contact   
Configuration 

Contacts  (For  specifications,  refer  to  Section  11-2.) 

Water  leakage:  1  for  1a 
Break:  1  for  1a 
*Setting  change  of  the  operation  switchs  shifts  to   
Contact  b. 

Water  leakage  location  data 
output 

4-20  mA  current  loop  output  (external  load  resistance:  500

Ω  max.)  x1 

Under  normal  sensor  conditions:  4  mA 
In  the  case  of  sensor  break  detection:  20  mA 
In  the  case  of  water  leakage  detection:  6  +  0.03  x  water  leakage   
location  indication  (m)  mA

 

±  1% 

*Changing  operational  setting  switches  changes  operation  in  the  case  of 
  water  leakage  detection.  (Refer  to  Attached  Drawing  3.) 

In  the  case  of  water  leakage  detection:  16  x  water  leakage  location 
indication  (m)  /  250  (m)  +  4  mA  ±  1% 

Withstand  voltage 

AC  1500V  (50/60  Hz)/  1  minute 
(between  the  power  source  terminal  and  the  body  case) 

Insulation  resistance 

10M

Ω  min.  (With  DC  500V  Megger)/1  minute 

(between  the  power  source  terminal  and  the  body  case) 

Noiseproofing  property 

±  1000V  Pulse  width:  1

μSEC  (noise  simulator)/1  minute 

(berween  each  phase  and  the  grounding  terminal) 
Power  source:

 

2  kV,  5  kHz 

Sensor:  1  kV,  5  kHz 
*IEC61000-4-4 

Outside  dimensions 

(W)  106  x  (H)  94  x  (D)  57  (unit:  mm)  (Refer  to  Attached  Drawing  1.) 

Weight  and  color 

Approx.  260  g,  gray 

 

 
 
 

-10- 

Содержание AD-AS-1LDMA

Страница 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LDMA Operation Manual System Equipment Division Electronic Material System Equipment Group Tatsuta Electric Wire Cable Co Ltd...

Страница 2: ...Locations easily accessible to the general public Locations close to sources of vibration organic gas or strong electromagnetic induction Locations subject to excessive waste and dust Locations where...

Страница 3: ...ks 3 17 Osadano cho Fukuchiyama City Kyoto 620 0853 Tel 81 773 45 6500 Fax 81 773 45 6501 Tatsuta Technical Center 6 5 1 Kunimidai Kizugawa City Kyoto 619 0216 Tel 81 774 66 5550 Fax 81 774 66 5556 Sh...

Страница 4: ...ection Function 7 Operation Chart 7 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Modbus Address 9 9 Detection Sensitivity Setting 9 10 Buzzer S...

Страница 5: ...stallation The Water Leakage Location Detector AD AS 1LDMA shall be securely installed in a strong housing on the wall etc inside a building Be sure to follow the following instructions when installin...

Страница 6: ...sor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA Reports to the host system by Modbus communication Drawing 2 Water Leakage Loc...

Страница 7: ...ring make sure that the power is switched off Drawing 4 AD LS Sensor Structure Table 1 AD LS Sensor Configuration Element Configuration Braided wire 0 33mm2 tinned soft copper wire covered with red pl...

Страница 8: ...a Output Connection 5 5 1 Connection The AD AS 1LDMA has a function that outputs the water leakage location by DC electrical current Option Use an analog input device with an input resistance of 500 o...

Страница 9: ...l analog input devices are broken 2 The input resistance for the external analog input devices is more than 500 If there is no problem with the items above the detector may be out of order Contact the...

Страница 10: ...unction 1 Drop tap water on the sensor 2 The buzzer sounds the Alarm Indicator LED lights up and the contacts for water leakage detection function 3 LCD indicates as shown in Drawing 12 Example In the...

Страница 11: ...indication No indication 1 Indication Indicating 1 Indication 1 The sensor length and the water leakage location is indicated alternately Lighting out Lighting out 20 Water leakage location data outp...

Страница 12: ...er leakage location indication Water leakage location data output 4 20 mA output 6 0 03 x water leakage location indication m mA 4 16 x water leakage location indication m 250 m mA or Drawing 14 Opera...

Страница 13: ...o detect fluid with high electrical resistance such as pure water in an environment where the temperature and humidity are stable such as a clean room it is recommended to set the sensitivity level hi...

Страница 14: ...larm buzzer Average sound pressure 90 dB 10 cm catalogue value by manufacturer Control output contact Contact Configuration Contacts For specifications refer to Section 11 2 Water leakage 1 for 1a Bre...

Страница 15: ...ak Point AD AS 1LDMA Power E 1 2 3 Sensor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA mm Approved by N a m e Prepared by Check...

Страница 16: ...I n s u l a t e d w i r e R e s i s t a n c e w i r e C O M N O Power source AC24V or DC24V G r o u n d i n g c o n n e c t i o n E H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Atta...

Страница 17: ...N Available OFF Contact a ON Contact b Operational setting OFF OFF OFF OFF OFF Activated ON Not activated Alarm hold for water leakage location indication 1 2 3 4 Terminal resistance setting Setting o...

Страница 18: ...et Length Leak Point AD AS 1LDMA Modbus address LIT Indication in the case of water leakage detection No 001 SL 400m LEAKAGE LOCATION DETECTOR Buzzer Stop Reset Length Leak Point AD AS 1LDMA Modbus ad...

Страница 19: ...ws Addresses 1 to 9 Dials 1 to 9 Address 10 Dial A Address 11 Dial B Address 12 Dial C Address 13 Dial D Address 14 Dial E Address 15 Dial F To set an address between 16 and 127 set the dial at 0 and...

Страница 20: ...sing the Reset switch allow the desired number to appear Each time you push the switch the figure increases one by one in order 0 1 2 3 4 5 6 7 8 9 0 When the address you desire is indicated press and...

Отзывы: