8. Indication of Detector number
The Detector number, which is used when communicating to the host system, is set by use of the rotary switch below.
Setable the range of the Detector number is between 1 and 15 by use of the rotary switch.
* The factory setting is 0 (no indication).
When setting the 16 to 127, set by operating
“Alarm Cancel Switch” and “Buzzer Stop Switch”.
See the accompanying sheet for details.
The Detector number is indicated on the upper left of the LCD.
0
1
4
8
C
2
3
5
6
7
9
A
B
D
E
F
No.001
SL 1500m
Buzzer Stop
Reset
Length
Leak Point
Detector number
Drawing 15 Indication of Detector Number
9. Detection Sensitivity Setting
Changing operational setting switches changes the detection sensitivity level.
* The water leakage sensor detects water leakage even it is caused by only a small amount of water
(condensation, for example). Therefore, if the sensor is installed in a location subject to high temperature
and high humidity, set the sensitivity level lower.
* In the case in which it is necessary to detect fluid with high electrical resistance, such as pure water, in an
environment where the temperature and humidity are stable, such as a clean room, it is recommended to
set the sensitivity level high.
10. Buzzer Setting
Changing operational setting switches changes not to sound the buzzer.
It is possible to change the above setting from the host system by the Modbus communication.
11. Specifications
11-1 Ratings
For the ratings, refer to Table 2.
Table 2 Ratings
Item
Specification
Rated voltage
AC24V or DC24V
Supply voltage fluctuation
± 10% of each
Power consumption
5W max.
Control output contact
See Section 11-2 Control Output Contact Specifications.
Sensor applied voltage
AC12.5V (maximum value)
Working ambient temperature
-10 to 50
˚C (no icing)
Working ambient humidity
35 to 95%RH *(no condensation)
*
86% or more is the storage humidity.
11-2 Control Output Contact Specifications
For the control output contact, refer to Table 3.
Table 3 Control Output Contact Specifications
Item
Resistance load
Inductive load
Rated load
AC 220V, 0.2 A
DC 24V, 2.0 A
AC 220V, 0.1 A
DC 24V, 1.0 A
Minimum applied load
DC 10mV, 10μA
(reference value)
(Relay contact: G6E-134P-US Catalogue values by OMRON Corporation)
-9-
SL 400m
No.001