8.  Indication  of  Detector  number 

The Detector number, which is used when communicating to the host system, is set by use of the rotary switch below. 

Setable the range of the Detector number is between 1 and 15 by use of the rotary switch. 

*  The factory setting is 0 (no indication). 

When  setting  the  16  to  127,  set  by  operating 

“Alarm  Cancel  Switch”  and  “Buzzer  Stop  Switch”.

 

See  the  accompanying  sheet  for  details.

 

The  Detector  number  is  indicated  on  the  upper  left  of  the  LCD. 

 

0

1

4

8

C

2

3

5

6

7

9

A

B

D

E

F

No.001
SL      1500m

Buzzer Stop

Reset

Length

Leak Point

 

Detector number

 

Drawing 15 Indication of Detector Number

 

9.  Detection  Sensitivity  Setting 

Changing operational setting switches changes the detection sensitivity level.   

*  The water leakage sensor detects water leakage even it is caused by only a small amount of water 

(condensation, for example). Therefore, if the sensor is installed in a location subject to high temperature 
and high humidity, set the sensitivity level lower.   

*  In the case in which it is necessary to detect fluid with high electrical resistance, such as pure water, in an 

environment where the temperature and humidity are stable, such as a clean room, it is recommended to 
set the sensitivity level high.

 

10.  Buzzer  Setting 

Changing  operational  setting  switches  changes  not  to  sound  the  buzzer. 

It  is  possible  to  change  the  above  setting  from  the  host  system  by  the  Modbus  communication. 

11.  Specifications 

11-1  Ratings 

For the ratings, refer to Table 2. 

Table  2  Ratings 

Item 

Specification 

Rated  voltage 

AC24V  or  DC24V 

Supply  voltage  fluctuation 

±  10%  of  each 

Power  consumption 

5W  max. 

Control  output  contact 

See  Section  11-2  Control  Output  Contact  Specifications. 

Sensor  applied  voltage 

AC12.5V  (maximum  value) 

Working  ambient  temperature 

-10  to  50 

˚C  (no  icing) 

Working  ambient  humidity 

35  to  95%RH  *(no  condensation)

 

 *

86%  or  more  is  the  storage  humidity.

 

                                                                                                                               

 

11-2  Control  Output  Contact  Specifications 

For the control output contact, refer to Table 3. 

Table 3 Control Output Contact Specifications 

Item 

Resistance  load 

Inductive  load 

Rated  load 

AC  220V,  0.2  A 
DC  24V,  2.0  A 

AC  220V,  0.1  A 
DC  24V,  1.0  A 

Minimum  applied  load 

DC  10mV,  10μA

 

(reference  value) 

         

                                       

  

(Relay  contact:  G6E-134P-US  Catalogue  values  by  OMRON  Corporation) 

-9- 

SL      400m 

No.001 

Содержание AD-AS-1LDMA

Страница 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LDMA Operation Manual System Equipment Division Electronic Material System Equipment Group Tatsuta Electric Wire Cable Co Ltd...

Страница 2: ...Locations easily accessible to the general public Locations close to sources of vibration organic gas or strong electromagnetic induction Locations subject to excessive waste and dust Locations where...

Страница 3: ...ks 3 17 Osadano cho Fukuchiyama City Kyoto 620 0853 Tel 81 773 45 6500 Fax 81 773 45 6501 Tatsuta Technical Center 6 5 1 Kunimidai Kizugawa City Kyoto 619 0216 Tel 81 774 66 5550 Fax 81 774 66 5556 Sh...

Страница 4: ...ection Function 7 Operation Chart 7 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Modbus Address 9 9 Detection Sensitivity Setting 9 10 Buzzer S...

Страница 5: ...stallation The Water Leakage Location Detector AD AS 1LDMA shall be securely installed in a strong housing on the wall etc inside a building Be sure to follow the following instructions when installin...

Страница 6: ...sor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA Reports to the host system by Modbus communication Drawing 2 Water Leakage Loc...

Страница 7: ...ring make sure that the power is switched off Drawing 4 AD LS Sensor Structure Table 1 AD LS Sensor Configuration Element Configuration Braided wire 0 33mm2 tinned soft copper wire covered with red pl...

Страница 8: ...a Output Connection 5 5 1 Connection The AD AS 1LDMA has a function that outputs the water leakage location by DC electrical current Option Use an analog input device with an input resistance of 500 o...

Страница 9: ...l analog input devices are broken 2 The input resistance for the external analog input devices is more than 500 If there is no problem with the items above the detector may be out of order Contact the...

Страница 10: ...unction 1 Drop tap water on the sensor 2 The buzzer sounds the Alarm Indicator LED lights up and the contacts for water leakage detection function 3 LCD indicates as shown in Drawing 12 Example In the...

Страница 11: ...indication No indication 1 Indication Indicating 1 Indication 1 The sensor length and the water leakage location is indicated alternately Lighting out Lighting out 20 Water leakage location data outp...

Страница 12: ...er leakage location indication Water leakage location data output 4 20 mA output 6 0 03 x water leakage location indication m mA 4 16 x water leakage location indication m 250 m mA or Drawing 14 Opera...

Страница 13: ...o detect fluid with high electrical resistance such as pure water in an environment where the temperature and humidity are stable such as a clean room it is recommended to set the sensitivity level hi...

Страница 14: ...larm buzzer Average sound pressure 90 dB 10 cm catalogue value by manufacturer Control output contact Contact Configuration Contacts For specifications refer to Section 11 2 Water leakage 1 for 1a Bre...

Страница 15: ...ak Point AD AS 1LDMA Power E 1 2 3 Sensor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA mm Approved by N a m e Prepared by Check...

Страница 16: ...I n s u l a t e d w i r e R e s i s t a n c e w i r e C O M N O Power source AC24V or DC24V G r o u n d i n g c o n n e c t i o n E H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Atta...

Страница 17: ...N Available OFF Contact a ON Contact b Operational setting OFF OFF OFF OFF OFF Activated ON Not activated Alarm hold for water leakage location indication 1 2 3 4 Terminal resistance setting Setting o...

Страница 18: ...et Length Leak Point AD AS 1LDMA Modbus address LIT Indication in the case of water leakage detection No 001 SL 400m LEAKAGE LOCATION DETECTOR Buzzer Stop Reset Length Leak Point AD AS 1LDMA Modbus ad...

Страница 19: ...ws Addresses 1 to 9 Dials 1 to 9 Address 10 Dial A Address 11 Dial B Address 12 Dial C Address 13 Dial D Address 14 Dial E Address 15 Dial F To set an address between 16 and 127 set the dial at 0 and...

Страница 20: ...sing the Reset switch allow the desired number to appear Each time you push the switch the figure increases one by one in order 0 1 2 3 4 5 6 7 8 9 0 When the address you desire is indicated press and...

Отзывы: