background image

PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT.MAN-102T 

 

 

PAGE 4

 

Issue: 1.1      Authorised: GH         Date: 06/11/02 

 
3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM 
SYSTEM, INCLUDING THE FACP & ITS INTEGRAL PSE 

 
EN54: Pt 1: 1988 is the British Standard Code for the Design, Installation and Servicing of Fire Detection and 
Alarm Systems for Commercial Buildings.  Section Four of the Code (User Responsibilities) states that the 
owner or person having control of the premises should appoint a responsible person to oversee the effective 
operation of the Fire Alarm System (Clause 28.1). 

 

Highlighted below is a summary of the main functions the Responsible ‘Person is expected to carry out.  Please 
note, this summary does not replace Section Four of EN54: Pt 1: 1988 (copies of which are available at your 
local reference library or from the BSI).  It is hoped this summary will help the User gain a greater 
understanding of his or her responsibilities with regard to the safe upkeep of the Fire Alarm System.  The 
bracketed number (xx) identifies the EN54: Pt 1: 1988 clauses to which the summary refers. 

 

The responsible person must 

 

1.  Ensure that all necessary work is carried out to guarantee the effective operation of the system, the 

maintenance of records and the servicing of the system (28.1.1). 

2.  Devise procedures for dealing with fire alarms, faults, etc, for approval by the appropriate fire authority 

before implementation (28.1.2). 

3.  Ensure all users of the system are trained in how to use the system properly and that all building 

occupants are aware of the action(s) to be taken in the event of a fire situation (28.1.3) 

4.  Effectively communicate with building/security personnel to ensure that cleaning, maintenance or building 

work does not interfere with the functioning and reliability of the system (28.1.4). 

5.  Ensure that the operation of the system is not hampered by obstacles, i.e. detectors and manual call points 

should be completely unobstructed (28.1.5). 

6.  Ensure that records, drawings and instructions are updated on a regular basis and are readily available for 

reference purposes (28.2.1). 

7.  Keep a Log Book to record all relevant details relating to the operation of the system (28.2.2). 
8.  Prevent false alarms by ensuring that: 

a)  staff and visitors to the building are aware that a fire alarm system is in operation (28.4.1.). 
b)  notices are displayed in all areas where detectors are sited (28.4.2). 
c)  contractors take appropriate precautions while working in protected areas (28.4.3). 
d)  precautions against dust and smoke are taken when temporary work is carried out in areas protected 

by smoke detectors (28.4.4) 

e)  the system is properly reinstated after temporary work has been completed (28.4.5) 

9.  Ensure that the system is attended to regularly on a routine basis, i.e. testing procedure is carried out, 

wiring check, etc (29.2). 

10.  Ensure that the system is correctly serviced at Daily, Weekly, Quarterly, Annual and Five Yearly intervals 

(29.2) and also in special circumstances, i.e. following a fire, false alarm, etc, (29.3) 

With the Premier SX Range of Fire Alarm Panels, we suggest the following tests are carried out as specified: - 

 

Daily Inspection 

• 

Check that the supply present indicator is lit. 

• 

Report any faults to the designated site maintenance engineer. 

 

Weekly Test (you may wish to temporarily disable the Remote Output during the following Tests) 

• 

Carry out an Indicator lamp test to check all Zone lights shown and the buzzer sounds. 

• 

Operate a manual call point or sensor to test the Fire Alarm. 

• 

Check that the Alarm sounders operate. 

• 

Reset the System by pressing the Silence/Activate Sounders button and Control Panel Reset button. 

• 

Verify that no call points or smoke/heat detectors are obstructed in any way. 

• 

Test a different zone each week using a different call point or detector so all are tested in rotation. 

 

Quarterly Test (to be carried out by authorised service personnel only) 

• 

Check all previous logbook entries and verify remedial action has been taken. 

• 

Visually inspect the batteries and connections and check it is capable of supplying the alarm sounders. 

• 

Operate a call point or detector in each zone to test the fire alarm as in the weekly test above. 

 

Annual Test (to be carried out by authorised service personnel only) 

• 

As for the weekly and quarterly test but check every detector, call point, sounder and all auxiliary 
equipment for correct operation. 

• 

Check Transformer output Voltage (32 VAC), Charger Voltage (27.8V off load, adjusted with VR1) & 
Battery Voltage (25-27V) 

 

Every Five Years (to be carried out by authorised service personnel only) 

• 

Carry out a complete wiring check in accordance with the testing and inspection requirements of the 
relevant National wiring regulations (in the UK this is the IEE Wiring Regulations). The Batteries should be 
replaced because SLA batteries have a working life of 5 years. 

Содержание Premier SX

Страница 1: ...35 0 5 6 5 50 21752 3 1 86 5 0 18 0 17 1 1 8 2 22...

Страница 2: ...ALARM SOUNDERS 5 3 NEW ZONE IN ALARM 5 4 MANUALLY ACTIVATING THE ALARM SOUNDERS 5 5 RESETTING THE PANEL 6 Fault Conditions 8 6 1 DIFFERENT TYPES OF FAULT 6 2 IN THE EVENT OF A FAULT CONDITION 7 Disabl...

Страница 3: ...Brigade of the Fire Condition An Auxiliary Output normally used to trigger local fire fighting equipment such as magnetic door release systems to automatically close fire doors plant shutdown systems...

Страница 4: ...em is in operation 28 4 1 b notices are displayed in all areas where detectors are sited 28 4 2 c contractors take appropriate precautions while working in protected areas 28 4 3 d precautions against...

Страница 5: ...e on the opposite page The only functions that can be performed by the User when the Panel is in its Normal state are Overriding any Delays which may have been programmed into the Panel by pressing th...

Страница 6: ...STEADYYELLOW A processor fault has occurred To reset turn keyswitch on then back off If problem persists consult your dealer GEN FIRE ONLY STEADYRED A manual evacuation has occurred The sounders will...

Страница 7: ...The Alarm Sounders and the Panel s Internal buzzer will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit All other Alarm outputs i e the Auxiliary Fi...

Страница 8: ...ht which conveys more precise information on the type of Fault detected If this light is lit by itself it indicates a keyswitch fault Zone Fault The relevant Zone Fault light flashes when there is a w...

Страница 9: ...d position Note the Fault s down in the Log Book at the back of this Manual and take appropriate action to correct it them See User Responsibilities section on Page 5 When a fault has been rectified t...

Страница 10: ...again and this will cause Zone 1 Disablement LED to light steady 5 Pressing scroll No 4 switch will cause the zone disablement LED to toggle to zone 2 and so on 32 5 1 5 1 8 7 6833 7 6 67 0 7 1 6 1 2...

Страница 11: ...a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To override this delay press Delay Override Switc...

Страница 12: ...Yes No Yes No Yes No LENGTH OF DELAY 1 TO 9 MINUTES IF APPLICABLE OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL...

Страница 13: ...ding fire alarm conditions failures tests temporary disconnections disablements enablements dates of installing engineers visits together with a note of any outstanding work or conditions You are advi...

Страница 14: ...REMIER SX USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 102T PAGE 14 Issue 1 1 Authorised GH Date 06 11 02 DATE TIME ZONE BRIEF DETAILS OF EVENT ACTION REQUIRED COMPLETED INITIAL...

Страница 15: ...ce with EN54 1 26 4 for compliance The PSE mains feed from a 3A spur should be checked The PSE Charger voltage should be checked adjusted if necessary 27 8V with batteries disconnected The battery vol...

Страница 16: ...______________________________________________________________________________________ _______________________________________________________________________________________________ _________________...

Страница 17: ...35 0 5 6 5 50 21752 3 1 167 7 21 0 18...

Страница 18: ...BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 DEVICE TERMINATION 9 5 1 CONNECTING THE DETECTOR SOUNDER CIRCUITS 5 2 CONNECTING THE AUXILIARY INPUTS AND OUTPUTS 6 SOUNDER AC...

Страница 19: ...ondensing It will withstand vibrations between 5 150 Hz It has a maximum capacity of 32 devices per zone The PSE is linear with a 1 1A output at system voltage 18 32V The mains supply is filtered befo...

Страница 20: ...erly terminated at the Panel However the System specification may demand the use of a particular type of cable and due regard should be paid to this fact 2 2 MAINS WIRING The requirement for the Mains...

Страница 21: ...ers own instructions The wiring for each Detector circuit should be connected to the relevant termination block on the Main Control PCB and their screens terminated at the Panel s base earth tag see p...

Страница 22: ...is no fault and open when there is a fault This should be taken into account when any device is connected to the fault relay Typical auxiliary output wiring 12 0 1 8 7 5 8 7 1 7 21 9 127 7 1 217 7 6...

Страница 23: ...ble gland Any unused knockouts must be securely blanked off It is essential that the 230Va c Mains cable is fed into the enclosure via one of the inlets at the top right hand corner of the enclosure F...

Страница 24: ...les to help minimise mains interference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the P...

Страница 25: ...the steel EMC cable grounding plate Incoming Detector and Sounder circuits should be connected to the relevant connector block on the Main Control PCB as shown in Figure 6 below All screens should be...

Страница 26: ...ing triggered to its Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where t...

Страница 27: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Страница 28: ...mode 6 Once testing of that zone is completed press scroll button to move to another Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open...

Страница 29: ...rong Charging Voltage The charging voltage should be 28 4V off load at 25 o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage...

Страница 30: ...zone devices As a guideline the quiescent current of most modern detectors is typically 0 00005A 50uA and that of manual call points is zero To obtain the most accurate figures consult the devices ma...

Страница 31: ...ivate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATTERY Connect 2 x 12V SLA batteries in SERIES ie...

Страница 32: ...OMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELA...

Отзывы: