background image

PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT.MAN-102T 

 

 

PAGE 3

 

Issue: 1.1      Authorised: GH         Date: 06/11/02 

 

1. SAFETY 

 

This Fire Alarm Panel is safe to operate provided it has been installed in compliance with the Manufacturers 
instructions and used in accordance with the Manual. 

 

Do not open the Fire Alarm Panel  enclosure .  There is no need to open the enclosure except to carry out 
commissioning, maintenance and remedial work.  This work must only be carried out by competent service 
personnel who are fully conversant with the contents of the separate engineering manual for this product. 

 

If the enclosure is damaged in any way, expert advice should be sought regarding its repair. 

 

Regular Servicing of the Fire Alarm System is highly recommended, preferably on a continuous maintenance 
contract and by a competent organisation.  A fully-itemised report of the installation should be obtained at least 
annually. 
 

& (

& (

(XURSHDQ 8QLR

(XURSHDQ 8QLRQQ 'LUHFWLYHV &RQIRUPDQFH

'LUHFWLYHV &RQIRUPDQFH 6WDWHPHQW

6WDWHPHQW

This product has been manufactured in conformance with the requirements of all 
applicable EU Council Directives.  The Declaration of Conformance for this 
product is located at the following Address:  GLT Exports Ltd, 72-78 Morfa Road, 
Hafod, Swansea, SA1 2EN, United Kingdom 
 

 

2. FIRE ALARM SYSTEMS – AN OVERVIEW 

 

The primary purpose of a Fire Alarm System is to provide an early warning of a fire so that people and animals 
can be evacuated and action taken to stop the fire as soon as possible – all according to a predetermined plan. 

 

Alarms may be raised automatically by Smoke or Heat Detectors, or manually be a person operating a Manual 
Call Point. 

 

To ensure an Alarm is dealt with in an orderly manner, it is important to know where the alarm is coming from.  
To do this, Fire Alarm systems are usually split into Zones, each covering a different area of a building. 

 

When an Alarm has been raised, the Fire Alarm Panel responds by indicating the Zone in which the Alarm has 
occurred and activating all relevant Sounders, Bells and other Alarm Outputs to provide a warning of the fire. 

• 

A Remote Output:  normally used to transmit an Alarm condition to an off-site permanently manned 
monitoring centre.  On receipt of the Alarm signal, the Centre notifies the local Fire Brigade of the Fire 
Condition. 

• 

An Auxiliary Output:  normally used to trigger local fire fighting equipment such as magnetic door 
release systems (to automatically close fire doors), plant shutdown systems (to automatically switch off 
potentially hazardous machines), sprinkler systems, etc. 

 

Fault Monitoring 

 

For obvious reasons the reliability of the Fire Alarm System is paramount.  To this end, the fire alarm panel 
continuously monitors all connections between Detectors, Manual Call Points and Sounders and checks its own 
power supply and back-up batteries for faults. 

 

If a fault is detected anywhere on the System, the Panel responds by illuminating one or more of the fault 
light(s) located on the front of its enclosure and by sounding its internal fault buzzer.  The Panel’s Fault Output 
is also activates, sending notification of the fault (if connected) to a remote  manned monitoring centre or other 
electronic equipment, as required. 

 

Delays 

 

A Fire Alarm System can be prone to conditions that lead to frequent and unavoidable false alarms, a common 
example being a waiting room filled with cigarette smoke.  In areas such as these, it is acceptable to apply a 
Delay to the Panel, which postpones the activation of the Alarm Sounders for a predetermined time.  This Delay 
period gives a responsible person time to investigate the cause of the Alarm and override the Delay if the cause 
is found to be a true fire hazard to reset the Panel if the cause is found to be a False Alarm. 

 

Disablements 

 

In abnormal conditions, certain parts of the Fire Alarm System can be temporarily turned off (disabled) to suit 
prevailing conditions.  For example, if there is a risk of a false alarm occurring in a zone from vehicle exhaust 
smoke in a loading bay, it is possible to disable that Zone during the risk period, then enable it again 
afterwards.  Another example of the disablement of outputs is during a routine test, or temporary fault. 

 

Power Supply Equipment- General Description. 

 

The NPSX FACP has an integral linear power supply capable of supplying 1.2 amps in total. It contains a current 
limited output for charging sealed lead acid batteries (7 Ah maximum). The PSE is monitored for main supply 
failure, the battery not taking a charge and low battery voltage. If the battery voltage drops below approximately 
20VDC (a fault condition), the battery charging current will be turned off , thus stopping charging. This PSE is 
only capable of supplying power to the CIE, and is not designed for any other use. 

Содержание Premier SX

Страница 1: ...35 0 5 6 5 50 21752 3 1 86 5 0 18 0 17 1 1 8 2 22...

Страница 2: ...ALARM SOUNDERS 5 3 NEW ZONE IN ALARM 5 4 MANUALLY ACTIVATING THE ALARM SOUNDERS 5 5 RESETTING THE PANEL 6 Fault Conditions 8 6 1 DIFFERENT TYPES OF FAULT 6 2 IN THE EVENT OF A FAULT CONDITION 7 Disabl...

Страница 3: ...Brigade of the Fire Condition An Auxiliary Output normally used to trigger local fire fighting equipment such as magnetic door release systems to automatically close fire doors plant shutdown systems...

Страница 4: ...em is in operation 28 4 1 b notices are displayed in all areas where detectors are sited 28 4 2 c contractors take appropriate precautions while working in protected areas 28 4 3 d precautions against...

Страница 5: ...e on the opposite page The only functions that can be performed by the User when the Panel is in its Normal state are Overriding any Delays which may have been programmed into the Panel by pressing th...

Страница 6: ...STEADYYELLOW A processor fault has occurred To reset turn keyswitch on then back off If problem persists consult your dealer GEN FIRE ONLY STEADYRED A manual evacuation has occurred The sounders will...

Страница 7: ...The Alarm Sounders and the Panel s Internal buzzer will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit All other Alarm outputs i e the Auxiliary Fi...

Страница 8: ...ht which conveys more precise information on the type of Fault detected If this light is lit by itself it indicates a keyswitch fault Zone Fault The relevant Zone Fault light flashes when there is a w...

Страница 9: ...d position Note the Fault s down in the Log Book at the back of this Manual and take appropriate action to correct it them See User Responsibilities section on Page 5 When a fault has been rectified t...

Страница 10: ...again and this will cause Zone 1 Disablement LED to light steady 5 Pressing scroll No 4 switch will cause the zone disablement LED to toggle to zone 2 and so on 32 5 1 5 1 8 7 6833 7 6 67 0 7 1 6 1 2...

Страница 11: ...a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To override this delay press Delay Override Switc...

Страница 12: ...Yes No Yes No Yes No LENGTH OF DELAY 1 TO 9 MINUTES IF APPLICABLE OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL...

Страница 13: ...ding fire alarm conditions failures tests temporary disconnections disablements enablements dates of installing engineers visits together with a note of any outstanding work or conditions You are advi...

Страница 14: ...REMIER SX USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 102T PAGE 14 Issue 1 1 Authorised GH Date 06 11 02 DATE TIME ZONE BRIEF DETAILS OF EVENT ACTION REQUIRED COMPLETED INITIAL...

Страница 15: ...ce with EN54 1 26 4 for compliance The PSE mains feed from a 3A spur should be checked The PSE Charger voltage should be checked adjusted if necessary 27 8V with batteries disconnected The battery vol...

Страница 16: ...______________________________________________________________________________________ _______________________________________________________________________________________________ _________________...

Страница 17: ...35 0 5 6 5 50 21752 3 1 167 7 21 0 18...

Страница 18: ...BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 DEVICE TERMINATION 9 5 1 CONNECTING THE DETECTOR SOUNDER CIRCUITS 5 2 CONNECTING THE AUXILIARY INPUTS AND OUTPUTS 6 SOUNDER AC...

Страница 19: ...ondensing It will withstand vibrations between 5 150 Hz It has a maximum capacity of 32 devices per zone The PSE is linear with a 1 1A output at system voltage 18 32V The mains supply is filtered befo...

Страница 20: ...erly terminated at the Panel However the System specification may demand the use of a particular type of cable and due regard should be paid to this fact 2 2 MAINS WIRING The requirement for the Mains...

Страница 21: ...ers own instructions The wiring for each Detector circuit should be connected to the relevant termination block on the Main Control PCB and their screens terminated at the Panel s base earth tag see p...

Страница 22: ...is no fault and open when there is a fault This should be taken into account when any device is connected to the fault relay Typical auxiliary output wiring 12 0 1 8 7 5 8 7 1 7 21 9 127 7 1 217 7 6...

Страница 23: ...ble gland Any unused knockouts must be securely blanked off It is essential that the 230Va c Mains cable is fed into the enclosure via one of the inlets at the top right hand corner of the enclosure F...

Страница 24: ...les to help minimise mains interference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the P...

Страница 25: ...the steel EMC cable grounding plate Incoming Detector and Sounder circuits should be connected to the relevant connector block on the Main Control PCB as shown in Figure 6 below All screens should be...

Страница 26: ...ing triggered to its Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where t...

Страница 27: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Страница 28: ...mode 6 Once testing of that zone is completed press scroll button to move to another Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open...

Страница 29: ...rong Charging Voltage The charging voltage should be 28 4V off load at 25 o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage...

Страница 30: ...zone devices As a guideline the quiescent current of most modern detectors is typically 0 00005A 50uA and that of manual call points is zero To obtain the most accurate figures consult the devices ma...

Страница 31: ...ivate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATTERY Connect 2 x 12V SLA batteries in SERIES ie...

Страница 32: ...OMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELA...

Отзывы: