PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-102T
PAGE 10
Issue: 1.1 Authorised: GH Date: 06/11/02
7. DISABLEMENTS
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM.
Certain Fire Alarm Panels can be temporarily disabled (i.e. switch off) to suit prevailing conditions. For example, if there is
a risk of a False Alarm in a zone, say from vehicle exhaust smoke in a loading bay, it is possible for the user to disable
that zone during the risk period and then enable it again afterwards. During a disablement of a zone(s), no fire or fault
signal will be processed for that zone(s). A zone(s) in a non-alarm state can only be disabled, that is zones already in fire
cannot be disabled.
External sounders can also be disabled as could be required in certain conditions.
7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1.
Turn control key to “Controls Enable” position;
2. Press
“Engineer” switch momentarily, this will cause General Disablement LED to flash (fast). This means the
panel is in disable/enable mode;
3.
Press scroll (No. 4) switch once and this will cause the General Disablement LED to flash (slow);
4.
Press scroll (No. 4) switch once again and this will cause Zone 1 Disablement LED to light steady;
5.
Pressing scroll (No. 4) switch will cause the zone disablement LED to toggle to zone 2 and so on;
32:(5
*(1),5(
*(1)$8/7
6833/< )/7
6<67(0 )/7 *(16&
'(/
*(1=21( 7(67
*(1',6$%/(0(17
),5( =21(6
=21$/ )$8/7 ',6$%/(0(17 7(67
(1*,1((5
672367$57
6,/(1& (
5(6(7
6&52//
/(' 7(67
)/7 721(
'(/$<
29(55,'(
)/7
6.
Select zone to be disabled. For example, if Zone 3 is selected and with Zone 3 disablement LED lit (steady) and
General Disablement LED flashing slow, pressing “Engineer” will cause General Disablement LED light to change
to steady. This means that zone 3 is now disabled;
7.
Switch controls key to off position, then both the disabled Zone Disablement LED and the General Disablement
LED will remain lit (steady.
7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1.
Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED
with stay lit (steady);
2. Press
“Engineer” switch once and this will cause the General Disablement LED to flash (fast);
3.
Press scroll (No. 4) switch until the light is steady at the disabled zone;
4. Press
“Engineer” and this will cause the General Disablement LED to flash (slow);
5.
Turn control Key to “Off” position and this will turn off the General Disablement and Zone Disablement LEDs.
NOTES:
The option of disabling or enabling zones 3, 4, 5, 6, 7 and 8 is only available if these zones are present on the
panel