background image

PREMIER SX INSTALLATION MANUAL.  

 

 

 

 

 

Approved Document No: GLT.MAN-101T 

 

 

PAGE 12

 

Issue : 1.6s         Authorised: GH      Date: 06/11/2002 

 

8. ZONE TEST 

 
8.1 WHY USE ZONE TEST
 

 

To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is 
available. 
 
When a detector or manual call point is triggered on any zone in Test, the Alarm sounders operate for 
approximately seven seconds on and seven seconds off.  This cycle continues until the cause of the 
Alarm is removed (either by the test smoke clearing from the detector or the manual call point being 
reset), at which point, the detector circuit also automatically resets. 
 
Should an Alarm occur on a zone that is not programmed to test, the Alarm will be processed in the 
normal way.  The testing of the zone in test will temporarily be suspended until the Alarm(s) from the 
other zones are reset.  At this point, zone retesting may resume. 
 
8.2 TO PROGRAMME ZONE IN TEST 
 
NOTE:  Only one zone can be programmed in test at any one time. 
 
1.  Insert and turn control key to enabled position; 

 

2.  Press engineer switch until the General Zone test LED is on (flashing fast); 

 

3.  Enter Engineer Code 4114 and then the General Zone Test LED is on (flashing slow); 

 

4.  Press scroll switch and Zone one fault LED will flash in synchronisation with the General Zone 

test; 

 

5.  Press scroll button to the desired Zone for test.  Once the desired Zone LED is flashing, this 

Zone is now in test mode. 

 

6.  Once testing of that zone is completed, press scroll button to move to another Zone or turn the 

control key switch to off position to exit test mode. 

 

9. GENERAL FAULT FINDING 

 
9.1 ZONE FAULTS
 
 
Open circuit faults will be indicated by zone(s) fault LED flashing.  In case of a short circuit fault, then 
the Zone(s) Fault LED will be accompanied by the Short Circuit Fault LED.  In both cases, the 
internal Fault Buzzer will sound and the General Fault LED will be lit. 
 
The Zone Faults are non-latching faults.  That is, if the fault disappears, the panel will automatically 
reset itself. (after a short delay of up to a minute) 
 
Suggested Action 
 
a) 

Disconnect the faulting detector zone completely and refit the end of line diode at that zone 
terminal in the panel.  If the fault condition for that zone clears, this confirms there is a wiring 
fault. 

 
b) 

Double-check and refit the wiring and the end of line diode on the zone.  Trace the fault with 
consideration for the type of fault indicated.(HINT: splitting the cable half way down the zone, 
and fitting the end of line diode to the new end point helps to determine which section of cable 
is giving the fault) 

 

Note:  A common fault is a detector head badly seated in a base that is not making the 
connection. 
 

d) 

A short circuit on a zone could be caused by the end of line diode being fitted backwards. 

 
c) 

Check that the detectors are compatible with this FACP. Note that some makes of detector will 
require a series resistor or diode to be fitted to work properly. There is usually a spare 
connector on the base to accommodate this (check instructions that came with the detector). 

Содержание Premier SX

Страница 1: ...35 0 5 6 5 50 21752 3 1 86 5 0 18 0 17 1 1 8 2 22...

Страница 2: ...ALARM SOUNDERS 5 3 NEW ZONE IN ALARM 5 4 MANUALLY ACTIVATING THE ALARM SOUNDERS 5 5 RESETTING THE PANEL 6 Fault Conditions 8 6 1 DIFFERENT TYPES OF FAULT 6 2 IN THE EVENT OF A FAULT CONDITION 7 Disabl...

Страница 3: ...Brigade of the Fire Condition An Auxiliary Output normally used to trigger local fire fighting equipment such as magnetic door release systems to automatically close fire doors plant shutdown systems...

Страница 4: ...em is in operation 28 4 1 b notices are displayed in all areas where detectors are sited 28 4 2 c contractors take appropriate precautions while working in protected areas 28 4 3 d precautions against...

Страница 5: ...e on the opposite page The only functions that can be performed by the User when the Panel is in its Normal state are Overriding any Delays which may have been programmed into the Panel by pressing th...

Страница 6: ...STEADYYELLOW A processor fault has occurred To reset turn keyswitch on then back off If problem persists consult your dealer GEN FIRE ONLY STEADYRED A manual evacuation has occurred The sounders will...

Страница 7: ...The Alarm Sounders and the Panel s Internal buzzer will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit All other Alarm outputs i e the Auxiliary Fi...

Страница 8: ...ht which conveys more precise information on the type of Fault detected If this light is lit by itself it indicates a keyswitch fault Zone Fault The relevant Zone Fault light flashes when there is a w...

Страница 9: ...d position Note the Fault s down in the Log Book at the back of this Manual and take appropriate action to correct it them See User Responsibilities section on Page 5 When a fault has been rectified t...

Страница 10: ...again and this will cause Zone 1 Disablement LED to light steady 5 Pressing scroll No 4 switch will cause the zone disablement LED to toggle to zone 2 and so on 32 5 1 5 1 8 7 6833 7 6 67 0 7 1 6 1 2...

Страница 11: ...a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To override this delay press Delay Override Switc...

Страница 12: ...Yes No Yes No Yes No LENGTH OF DELAY 1 TO 9 MINUTES IF APPLICABLE OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL...

Страница 13: ...ding fire alarm conditions failures tests temporary disconnections disablements enablements dates of installing engineers visits together with a note of any outstanding work or conditions You are advi...

Страница 14: ...REMIER SX USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 102T PAGE 14 Issue 1 1 Authorised GH Date 06 11 02 DATE TIME ZONE BRIEF DETAILS OF EVENT ACTION REQUIRED COMPLETED INITIAL...

Страница 15: ...ce with EN54 1 26 4 for compliance The PSE mains feed from a 3A spur should be checked The PSE Charger voltage should be checked adjusted if necessary 27 8V with batteries disconnected The battery vol...

Страница 16: ...______________________________________________________________________________________ _______________________________________________________________________________________________ _________________...

Страница 17: ...35 0 5 6 5 50 21752 3 1 167 7 21 0 18...

Страница 18: ...BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 DEVICE TERMINATION 9 5 1 CONNECTING THE DETECTOR SOUNDER CIRCUITS 5 2 CONNECTING THE AUXILIARY INPUTS AND OUTPUTS 6 SOUNDER AC...

Страница 19: ...ondensing It will withstand vibrations between 5 150 Hz It has a maximum capacity of 32 devices per zone The PSE is linear with a 1 1A output at system voltage 18 32V The mains supply is filtered befo...

Страница 20: ...erly terminated at the Panel However the System specification may demand the use of a particular type of cable and due regard should be paid to this fact 2 2 MAINS WIRING The requirement for the Mains...

Страница 21: ...ers own instructions The wiring for each Detector circuit should be connected to the relevant termination block on the Main Control PCB and their screens terminated at the Panel s base earth tag see p...

Страница 22: ...is no fault and open when there is a fault This should be taken into account when any device is connected to the fault relay Typical auxiliary output wiring 12 0 1 8 7 5 8 7 1 7 21 9 127 7 1 217 7 6...

Страница 23: ...ble gland Any unused knockouts must be securely blanked off It is essential that the 230Va c Mains cable is fed into the enclosure via one of the inlets at the top right hand corner of the enclosure F...

Страница 24: ...les to help minimise mains interference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the P...

Страница 25: ...the steel EMC cable grounding plate Incoming Detector and Sounder circuits should be connected to the relevant connector block on the Main Control PCB as shown in Figure 6 below All screens should be...

Страница 26: ...ing triggered to its Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where t...

Страница 27: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Страница 28: ...mode 6 Once testing of that zone is completed press scroll button to move to another Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open...

Страница 29: ...rong Charging Voltage The charging voltage should be 28 4V off load at 25 o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage...

Страница 30: ...zone devices As a guideline the quiescent current of most modern detectors is typically 0 00005A 50uA and that of manual call points is zero To obtain the most accurate figures consult the devices ma...

Страница 31: ...ivate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATTERY Connect 2 x 12V SLA batteries in SERIES ie...

Страница 32: ...OMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELA...

Отзывы: