MONITORING FUNCTIONS

7.1  Animal Inventory / Starting

a New Batch

The animal inventory allows keeping track

of the number of animals in the barn. If

drops are controlled individually (without

actuator), the number of animals is moni-

tored separately for each drop.

Select

5. Animal Inventory

Select Drop #

If the drops are controlled individually

(without actuator), the animal inventory is

monitored separately for each one of them.

Select a drop then adjust the following

parameters.

Accessible if drops are controlled individually

(actuator is disabled in section 5.3).

If the drops are controlled indi-

vidually (without actuator), the

following parameters must be

set separately for each drop.

Animal inventory

Exit: Press BACK

Change: Press Modify

Press   to Select an item

Select Drop #

1

Start new batch ?

No

New Entered

0

New Mortality

0

New Delivered

0

Entered

5

Mortality

2

Delivered

10

Total Entered

105

Total Mortality

2

Total Delivered

10

Remaining

93

Start New Batch ?

When a new batch starts, the controller

clears all histories of the previous batch

and resets the animal age.  Select “Yes”

to start a new batch.

New entered:

Enter the initial number of animals. In ad-

dition, if new animals are added in the

course of the batch, you must specify the

number of new animals in this menu. Once

a value is posted to this menu, it automati-

cally returns to “0” after a few seconds.

It is then transferred to the 

Entered

 menu

and is added to the 

Total Entered 

and 

Re-

maining 

menus.

New Mortality / New Delivered:

Post up the number of mortalities and the

number of shipped animals as it occurs.

Once a value is posted to this menu, it au-

tomatically returns to “0” after a few sec-

onds. The value is then transferred to the

proper inventory menus.

Entered / Mortality / Delivered:

These menus show today’s animal entries,

mortalities and deliveries (for consultation

only).

Total Entered / Total Mortality /
Total Delivered:

These menus show the total number of

animal entries, mortalities and deliveries

since the beginning of the batch (for con-

sultation only).

Remaining Count:

This menu displays the number of remain-

ing animals (for consultation only). The re-

maining count is calculated as follows: 

To-

tal Entered - Total Mortality - Total Deliv-

ered.

17

TARGET ECO I FEEDING,  rev.09

TARGET ECO I FEEDING

5.3

Installation Setup

The following section shows how to cus-

tomize the controller for your particular

application. Normally, this setup needs to

be done only once.

Select:

11. Installation *

1. Settings

*

Accessible by the installer only (sec. 5.2).

Number of rations:

Select the number of feed rations in use.

This number usually corresponds to the

number of bins in use. It can be adjusted

from 1 to 8 rations.

Use actuator:

Select “Yes” if the drops are controlled by

an actuator; select “No” if they are con-

trolled individually (1 relay per drop).

Number of ration curves:

Select the number of ration curves in use

(0 to 4 curves).

* Accessible if more than 1 ration is used and if
drops are controlled individually (the actuator is

disabled above).

Installation

Exit: Press BACK

Change: Press Modify

Press   to Select an item

# of ration:

3

Use actuator ?

No

# ration curves:

2

# of drops

10

Number of feed cycles/day

6

Active feed cycles in curves ? Yes
# of time clocks

8

Use Proxy switch?

Yes

use Proxy switch module?

Yes

Prox switch off delay

1:00 (m:s)

Prox switch bypass delay 1:00 (m:s)
Use feed gap delay?

Yes

Proxy switch contact type

N.O.

Ration History

Consumpt.

Weight units:

lbs

Number of drops:

Select the total number of drops in use (1

to 96 drops).

* Accessible if drops are controlled individually
(the actuator is disabled above).

Number of feed cycle(s) / day:

Select the highest number of feed cycles

that can be performed in a day. Adjust-

able from 1 to 8 cycles.

Active feed cycles in curves ?

Select “Yes” to get an automatic selection

of the active feed cycles over time; select

“No” to always use same feed cycles.

* Available if the ration curve is enabled above.

Number of Time Clocks:

Select the number of time clock outputs.

Adjustable from 0 to 8 outputs.

Use Proxy Switch?

Select "Yes" if one or many proximity sen-

sors are used to detect the presence of

feed in the feed line.

Use Proxy Switch module ?

Select “Yes” if there is more than one prox-

imity sensor on the feeder. The Proxy

switch module allows using up to 8 prox-

imity sensors.

Prox Switch Off Delay:

Specify after how many seconds of con-

tinuous feed detection the feeder motor

must stop.

Accessible if a proximity sensor is enabled above.

Prox Switch Bypass Delay:

When a feeding cycle ends, a certain

amount of feed is likely to remain in the

line. Proximity sensors will ignore the pres-

ence of these leftovers during this period

of time at the beginning of each cycle. Set

the bypass delay to the desired value (from

0 to 30 minutes).

Accessible if a proximity sensor is enabled above.

Содержание ECO I FEEDING

Страница 1: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Страница 2: ...09 TARGET ECO I FEEDING NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice du...

Страница 3: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 4: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 5: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 6: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 7: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 8: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 9: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 10: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 11: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 12: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 13: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 14: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 15: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 16: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 17: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 18: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 19: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 20: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 21: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 22: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 23: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 24: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 25: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 26: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 27: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 28: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 29: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 30: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 31: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 32: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 33: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 34: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 35: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 36: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 37: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 38: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 39: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 40: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 41: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 42: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 43: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Отзывы: