5.4.2

Relay Assignment for the
Actuator

If the drops are controlled by an actuator,

you must assign an actuator position to each

ration. The following procedure show how

to make this assignment and how to assign

the actuator’s open and close relays.

Select:

11. Installation *

2. Relay Assignment
6. Actuator **

*

Accessible from the installer mode (s. 5.2).

*

Accessible if the actuator is enabled (s. 5.3).

Ration #X Actuator Position:

Specify the actuator position that is asso-

ciated with the delivery of each type of

ration as follows:

1. Open the actuator to a position that is

used for the distribution of a ration (use

the bypass switches of your relay panel to

open the actuator).

2. Once the actuator is correctly posi-

tioned, assign its position to the proper

ration. The current actuator position is dis-

played below.

3. Repeat for each ration in use.

Relay Assignment – Actuator

Exit: Press BACK

Change: Press Modify

Press   to Select an item

Ration #1 – Actuator position:

0

Ration #2 – Actuator position:  50
Ration #3 – Actuator position: 100
Current actuator position:       0
Open Actuator  – Module ID

3

          – Output #

7

Close Actuator – Module ID

3

          – Output #

7

Hysteresis:                  3 %

Current actuator position:

This is the current position of the actuator’s

potentiometer. Use it as a reference to

assign an actuator position to each ration.

Open / Close actuator
Module ID:

Select on which relay panel the actuator’s

opening and closing relays are located. The

relay panel is identified by its ID number

(ID #2 to ID #19).  Tables are also avail-

able at the end of this manual to write down

the identification number of each panel.

Open / Close Actuator
Output #:

Select which relays of the relay panel are

used to open and to close the actuator (out-

puts 1-16). If a device is connected to re-

lays 17-32 of a 32-output relay panel, se-

lect to which relay of the second 16-relay

strip this corresponds (i.e., relay 17=1,

relay 18=2... relay 32=16. Refer to sec-

tion 5.4 for further information).

Hysteresis:

The hysteresis is the acceptable offset in

the actuator’s position. It can be adjusted

from 0 to 4%.

23

TARGET ECO I FEEDING,  rev.09

TARGET ECO I FEEDING

5.5

Version

This menu shows the version number of

your controller program. This piece of in-

formation is useful to get technical sup-

port.

Select:

11. Installation*

3. Version

*

Accessible from the installer mode (s. 5.2).

Exit: Press BACK

ECO I Feeding

SETTINGS V. X.X

PCXX

Содержание ECO I FEEDING

Страница 1: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Страница 2: ...09 TARGET ECO I FEEDING NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice du...

Страница 3: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 4: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 5: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 6: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 7: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 8: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 9: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 10: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 11: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 12: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 13: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 14: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 15: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 16: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 17: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 18: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 19: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 20: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 21: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 22: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 23: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 24: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 25: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 26: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 27: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 28: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 29: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 30: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 31: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 32: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 33: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 34: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 35: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 36: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 37: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 38: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 39: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 40: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 41: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 42: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 43: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Отзывы: