Target ECO I FEEDING Скачать руководство пользователя страница 26

26

TARGET ECO I FEEDING,  rev.09

TARGET ECO I FEEDING

6.3

Feeding Schedule

The feeding schedule is composed of many

feed cycles; up to 8 of these can be per-

formed every day. Refer to section 5.3. to

enable the proper number of cycles.

The following procedure shows how to

adjust the feed cycles. Note that these

cycles operate differently depending if the

drops are controlled by an actuator or not:

Drops that are controlled by an actuator:

If drops are controlled by an actuator, you

must define which ration must be deliv-

ered during each cycle.

Drops that are controlled individually (with-

out actuator):

If drops are controlled individually, you

must specify during which cycles feed is

being delivered to each drop (refer to the

previous section to assign feed cycles to

the drops). In addition, the controller can

automatically adjust the number of active

feed cycles as the animals grow up. Refer

to section 6.1 for further information about

this Ration Curve function.

Only one cycle can operate at a

time.  If many cycles simulta-

neously ask for feed, the con-

troller finishes the ongoing cycle

before stepping to the next.

Feeding Schedule

Select Cycle #

1

Status

On

Start time

12:00 A

Use Ration #1 ?

Yes

Use Ration #2 ?

No

...

Select:

4. Feeding Schedule

Select Cycle #:

Select the desired feed

cycle. All following parameters are related

to the chosen cycle:

Status: 

Select “Yes” to enable the chosen

feed cycle; select “No” to stop using it.

Start Time: 

Set the time at which the feed

cycle starts.

!

Cycles must be activated fol-

lowing the numerical order,

starting with feed cycle #1, fol-

lowed by cycle #2, etc.

Use Ration #X:

Select which rations are

distributed during the selected feed cycle.

Accessible if drops are controlled by an actuator.

19

TARGET ECO I FEEDING,  rev.09

TARGET ECO I FEEDING

Feed Gap Delay:

Proximity sensors can be used to stop

the cleanout period when the feed line

becomes empty (instead of having to

wait for the end of the Cleanout pe-

riod). If this option is used, select after

how many time the cleanout period can

end when no feed is detected. This de-

lay ranges from 0 to 30 minutes.

Note that if the controller uses many

proximity sensors, the proximity sen-

sor used to monitor the Feed Gap De-

lay is the one associated with the cur-

rent ration.

Accessible if a proximity sensor and the Feed

Gap option are enabled above.

Flow Rate (weight/min)

If the feed consumption history is en-

abled above, you must specify the flow

rate of the ration auger. This value is

expressed as an amount of feed per

minute. Set the flow rate to the desired

value.

Accessible if the consumption history is en-

abled above.

Use  proxy switch?

Assign a proximity sensor to each ra-

tion.

Accessible if the proximity sensor module is

enabled above.

Maximum Current

Select the maximum allowable current that

can be consumed by the feeder motor.

Adjustable from 1 to 14 Amp.

Window Size

The auger motor restarts at

: Max Current

- Window Size. 

The window size can be

adjusted from 0.5 to 3.0 Amp.

Actual Current:

This reading indicates the current that is

presently consumed by the feeder motor.

Over Current Delay

An alarm is set off when the current con-

sumption of the feeder motor exceeds the

Maximum Current 

limit for this delay. The

Over Current Delay 

can be adjusted from

30 seconds to 15 minutes.

Time Display

AM/PM or 24 hours.

Time of reset

The time of reset should normally be set

to 11h59PM. It represents the time at

which the animal age is increased by 1 day;

the controller also logs the fill auger run

times in the histories at that time.

Installation

Exit: Press BACK

Change: Press Modify

Press   to Select an item

# of ration:

3

Use actuator ?

No

# ration curves:

2

# of drops

10

Number of feed cycles/day

6

Active feed cycles in curves ? Yes
# of time clocks

8

Use Proxy switch?

Yes

use Proxy switch module?

Yes

Prox switch off delay

1:00 (m:s)

Prox switch bypass delay 1:00 (m:s)
Use feed gap delay?

Yes

Proxy switch contact type

N.O.

Ration History

Consumpt.

Weight units:

lbs

Ration #1-8

Rest period:

1:00 (h:m)

Use cleanout auger?

Yes

Cleanout time:

1:00 (h:m)

Max run time:

1:00 (h:m)

Feed gap delay:

1:00 (h:m)

Flow Rate weight/min: 100 lbs
Use proxy switch:      1

Max current               9.5 A
Window size               2.0 A
Actual current            0.0 A
Over-current delay

3:00 (m:s)

Fill auger start delay:

0:05 (m:s)

Time display

AM/PM

Time of Reset

11:59P

Содержание ECO I FEEDING

Страница 1: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Страница 2: ...09 TARGET ECO I FEEDING NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice du...

Страница 3: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 4: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 5: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 6: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 7: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 8: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 9: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 10: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 11: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 12: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 13: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 14: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 15: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 16: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 17: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 18: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 19: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 20: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 21: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 22: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 23: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 24: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 25: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 26: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 27: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 28: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 29: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 30: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 31: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 32: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 33: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 34: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 35: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 36: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 37: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 38: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 39: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 40: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 41: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 42: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 43: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Отзывы: