Target ECO I FEEDING Скачать руководство пользователя страница 27

18

TARGET ECO I FEEDING,  rev.09

TARGET ECO I FEEDING

Use Feed Gap Delay?

A delay can be used to put an end to the

cleanout period as soon as the feed line

becomes empty (instead of having to wait

for the end of the Cleanout period). Select

“Yes” if you want to use this delay or se-

lect “No” to disable this function.

Accessible if a proximity sensor is enabled above.

Proxy Switch Contact Type:

Select the type of contact used by all prox-

imity sensors: normally open (NO) or nor-

mally closed (NC). By default, this param-

eter is set to “NO”.

Ration History

Select which information you want to see

in the ration history menu:
- Run time of each ration feeder;
- Feed consumption of each ration.

Weight units

If the consumption history is enabled

above, choose the desired units of mea-
surement used to display the amount of

feed: pounds (lbs) or kilograms (kg).

Rations #1-8:

Adjust the following parameters for each

ration in use.

Rest Period:

Specify the duration of the rest period.

This delay represents the time required

for animals to eat the feed ration. It

can be adjusted from 0 to 8 hours.

Use Cleanout Auger?

Select “Yes” if a cleanout auger is used.

Cleanout Time:

Specify the duration of the cleanout

period (0 to 4 hours).

Maximum Run Time:

If proximity sensors are used, the Max

Run Time represents the run time over

which an alarm is triggered: the alarm

is generated when no feed is detected

in the line over the Maximum Run Time

delay. This type of alarm generally oc-

curs when a bin is empty. Set the Max

Run Time alarm limit to the desired value

(from 1 minute to 8 hours).

Note that if the controller uses many

proximity sensor, the proximity sensor

used to monitor the Maximum Run Time

is the one associated with the current

ration (from 1 minute to 8 hours).

If proximity sensors are not used, the

Max Run Time represents the period of

time required to fill-up the drops. Feed

cycles stop at the end of this delay. Set

the maximum run time of each ration

separately.

Installation

Exit: Press BACK

Change: Press Modify

Press   to Select an item

# of ration:

3

Use actuator ?

No

# ration curves:

2

# of drops

10

Number of feed cycles/day

6

Active feed cycles in curves ? Yes
# of time clocks

8

Use Proxy switch?

Yes

use Proxy switch module?

Yes

Prox switch off delay

1:00 (m:s)

Prox switch bypass delay 1:00 (m:s)
Use feed gap delay?

Yes

Proxy switch contact type

N.O.

Ration History

Consumpt.

Weight units:

lbs

Ration #1-8

Rest period:

1:00 (h:m)

Use cleanout auger?

Yes

Cleanout time:

1:00 (h:m)

Max run time:

1:00 (h:m)

Feed gap delay:

1:00 (h:m)

Flow Rate weight/min: 100 lbs
Use proxy switch:      1

Max current               9.5 A
Window size               2.0 A
Actual current            0.0 A
Over-current delay

3:00 (m:s)

Fill auger start delay:

0:05 (m:s)

Time display

AM/PM

Time of Reset

11:59P

27

TARGET ECO I FEEDING,  rev.09

TARGET ECO I FEEDING

6.4

Time Clock Settings

The controller has 8 timer outputs to con-

trol various devices using the real-time

clock. Each outputs can use up to 24 start

and stop times.

Select

7. Time clocks*

* Available if time clock outputs are enabled (s.
5.3).

• Select a clock output

The following parameters are associated

with the chosen clock output and must be

set separately for each clock output in use.

Set the start and stop times for all

24 cycles of the selected clock output. If

24 cycles are not necessary, set the start

and stop times of unused cycles to the same

value.

Time Clocks

Exit: Press BACK

Change: Press Modify

Press   to Select an item

Select Time clock #

1

Start Time 1

12:00A

Stop Time 1

12:00A

Start Time 2

12:00A

Stop Time 2

12:00A

Start Time 3

12:00A

Stop Time 3

12:00A

(...)

Start Time 24

12:00A

Stop Time 24

12:00A

Содержание ECO I FEEDING

Страница 1: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Страница 2: ...09 TARGET ECO I FEEDING NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice du...

Страница 3: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 4: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 5: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 6: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 7: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 8: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 9: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 10: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 11: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 12: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 13: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 14: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 15: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 16: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 17: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 18: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 19: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 20: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 21: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 22: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 23: ...Actuator Module ID 3 Output 7 Close Actuator Module ID 3 Output 7 Hysteresis 3 Current actuator position This is the current position of the actuator s potentiometer Use it as a reference to assign an...

Страница 24: ...cles are active during the selected curve point Accessible if the Active feed cycles in curve option is enabled s 5 3 Ration Curves Exit Press BACK Change Press Modify Press to Select an item Select R...

Страница 25: ...lay strip 25 TARGET ECO I FEEDING rev 09 TARGET ECO I FEEDING 6 2 Drop Settings The following procedure shows how to adjust the particular settings of each drop Select 3 Drop Settings Accessible if dr...

Страница 26: ...ected This de lay ranges from 0 to 30 minutes Note that if the controller uses many proximity sensors the proximity sen sor used to monitor the Feed Gap De lay is the one associated with the cur rent...

Страница 27: ...associated with the current ration from 1 minute to 8 hours If proximity sensors are not used the Max Run Time represents theperiod of time required to fill up the drops Feed cycles stop at the end of...

Страница 28: ...ING 5 3 Installation Setup The following section shows how to cus tomize the controller for your particular application Normally this setup needs to be done only once Select 11 Installation 1 Settings...

Страница 29: ...r password and write it down in a safe place Password Exit Press BACK Change Press Modify Press to Select an item Current user User 1 Change the user Change the password Confirm the password 29 TARGET...

Страница 30: ...nabled s 5 3 Ration 1 8 Consumption Today s feed consumption is displayed separately for each ration Current Status Exit Press BACK Press to Select an item Start feed cycle None Feeder motor Auto Actu...

Страница 31: ...y start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in au tomatic mode Pilot lights of the CDM 1 module The following table gives the meaning of each status LED of CDM...

Страница 32: ...ECO I FEEDING rev 09 TARGET ECO I FEEDING 4 USER INTERFACE 4 1 Location of the Controls Main LCD Screen The large LCD screen is used to display the various parameters and menus The Current Conditions...

Страница 33: ...pment and within easy reach of the operator It shall be marked as the disconnecting device for theequipment 3 2 2 Alarm Connection There are two types of alarms on the mar ket One type activates when...

Страница 34: ...nt name CONTROLLER 2 DMP for instance This way the controller will never erase a file on the card 3 Update Firmware Choose 3 Update Firmware to download a new firmware file into your controller This p...

Страница 35: ...ontrolled by an actuator Cleanout Auger optional Cleanout valves for rations 1 8 if a cleanout auger is used Cleanout Master Valve if a cleanout au ger is used Air compressor if a cleanout auger is us...

Страница 36: ...D 2 to ID 19 Drop 3 _________ ID 2 to ID 19 Drop 4 _________ ID 2 to ID 19 Drop 5 _________ ID 2 to ID 19 Drop 6 _________ ID 2 to ID 19 Drop 7 _________ ID 2 to ID 19 Drop 8 _________ ID 2 to ID 19 D...

Страница 37: ...anout auger can also be used to send feed left overs back to their original bin During the cleanout period the feeder motor and the optional cleanout auger are activated in order to evacuate feed from...

Страница 38: ...p 85 _________ ID 2 to ID 19 Drop 86 _________ ID 2 to ID 19 Drop 87 _________ ID 2 to ID 19 Drop 88 _________ ID 2 to ID 19 Drop 89 _________ ID 2 to ID 19 Drop 90 _________ ID 2 to ID 19 Drop 91 ___...

Страница 39: ...type of ration that is distributed to the animals over time It is thus pos sible to increase the number of feed cycles or to switch rations as the animals grow up Cleanout Cleanout periods allow evacu...

Страница 40: ...circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C For Indoor use only To avoid exposing the controller to harmful gases or excessive hu...

Страница 41: ...sor Conditions current 30 Configuration module 34 Connections 12 Consumption see Feed consumption Contrast LCD screen 13 34 Controller Backup see Memory card Features 6 Installation setup 17 19 Locati...

Страница 42: ...see Clock output Toggle switch 10 Transfer Configuration transfer 34 U USB Drive 34 User password 16 V Valves see Cleanout valve or Fill augers Version software 23 W Weighing error 31 Window size Sett...

Страница 43: ...REV 11 M 890 00035 rev 09 TARGET ECO I FEEDING Feed Distribution System for Hogs USER S MANUAL...

Отзывы: