background image

7

5. Installation

5.1 General - Heat Pump

5.2 Acoustic emissions

5.3 General - HydroBox

The  Heat  Pump  outdoor  unit  must  be  installed  on  a  permanently  even, 

smooth and horizontal surface (concrete slab). The base should be sized so 

the entire outdoor unit is directly supported.  The recommended minimum 

concrete  slab  dimensions  are  42"  long  x  32"  wide  x  6"  deep  (107  x  32 

x 15.25 cm) for mounting hardware clearances. To prevent small animals 

from  entering  the  inside  of  the  device,  the  connection  holes  in  the  base 

plate should be sealed where necessary.
The outdoor unit is designed for installation close to walls on even ground, 

and must always be fixed in place at the installation site (see dimension 

drawing, Section 12). The heat pump profile is tall and slender, so it must 

be attached permanently to the base for safety reasons.  The responsibility 

for the heat pump installation lies with the specialist system construction 

company.  During  the  installation,  local  requirements  such  as  building 

regulations, siesmic considerations, the static load of the building, and wind 

exposure must be accounted for.
If  the  unit  will  see  a  condition  where  snow  levels  exceed  15  inches  (.5 

meters) it is recommended that a snow stand be used to elevate the heat 

pump.  The snow stand must be permanently attached to the base and the 

heat pump secured to the stand for safety reasons.
If there is risk of snow or ice falling from a roof, a protective roof or cover 

must be constructed to protect the heat pump, pipes, and wiring.
It must be possible to carry out maintenance work without hindrance. This is 

ensured if the clearances displayed below are maintained.

The heat pump operates silently due to efficient sound insulation. Internal 

insulation measures should be carried out to prevent vibrations from being 

transmitted to the foundation or to the heating system.

The placement of the unit must be indoors. The HydroBox is not designed 

for outdoor or wet environments.  It is recommended that the unit be placed 

near where the interconnected piping to the outdoor unit enters the building 

to keep the piping distance to a minimum.  A maximum of 100

 

feet of 1" pipe 

can be used between the indoor and outdoor unit. For longer distances 1 

1/4" pipe can be used. However, a resistance head calculation should be 

performed based on the supplied Taco 0034e circulating pump to maintain 

the target 8gpm flow rate with the chosen pipe size and pipe.
All electrical connections can be accessed by removing the left side panel 

of the HydroBox.  Although all panels can be removed, the HydroBox was 

designed to be able to access all serviceable components and access all 

wiring connections by just removing the side panels.
It must be possible to carry out maintenance work without hindrance. This 

is ensured if the clearance displayed below is maintained.

The specified dimensions are valid for single unit installation only. (See Fig. 

6)
If multiple outdoor units are set up next to each other, the required minimum 

distance at the side adds up. Ensure that the cold expelled air is not sucked 

in again.

Note:

 The cold air is blown out downwards at the side of the heat pump 

and can result in black ice on paths and platforms.

1.3 ft

(0,4 m)

Back of Unit

1.6 ft

(0,5 m)

1.6 ft

(0,5 m)

3.3 ft

(1 m)

Air Flow

Note:

 Do not restrict or block the area around the intake or the air outlet 

area.

Note:

 Observe all local building regulations!

Note:

 The physical impacts must be observed for installation close to 

walls. No windows or doors should be present in the area surrounding 

the air outlet of the fan.

Note:

 In cases of installation close to walls, there may be more sediment 

in the intake and air outlet area due to the air flow. The colder outside air 

outlet should discharge in such a way as to not increase the heat losses 

in heated neighboring rooms.

Note:

 Installation in a hollow or in an inner courtyard is not permitted 

because cooled air collects at ground level and is drawn in again by the 

heat pump during extended periods of operation.

Note:

 Do not locate where the air intake is near vented appliances (e.g. 

driers,  furnaces,  fireplaces),  moisture  producing  equipment,  vehicle 

exhaust, subject to direct salty atmospheres, where metal, powder like 

substances or chemicals are in the air that could effect the unit (include 

livestock breading areas and hot springs). 

Fig. 6

Fig. 7

FORMAT REV 9-1-17

THIS DOCUMENT CONTAINS INFORMATION THAT IS CONFIDENTIAL 

AND PROPRIETARY TO TACO, INC. (“TACO”). IT IS PROVIDED FOR USE 

ONLY FOR THE PURPOSES EXPRESSLY STATED BY TACO. BY USING 

THIS DOCUMENT, YOU AGREE THAT TACO WILL HAVE NO LIABILITY 

FOR ANY DAMAGES ARISING OUT OF YOUR USE OR MODIFICATION TO 

IT AND YOU AGREE TO RETURN THE DOCUMENT, TOGETHER WITH 

ALL COPIES MADE, IMMEDIATELY WHEN REQUESTED BY TACO.

APP

QA

INCHES [MM]

07/16/2020

aco

Inc.

6

OF

SHEET

UNLESS OTHERWISE SPECIFIED:

ANGLES     ±  1°

FEATURE

CONTROL

SYMBOLS PER

ANSI Y14.5

R.005[.127]TO.015[.38]

BREAK SHARP EDGES

125

FINISHES

FRACTIONS±1/64[.397]
.XX   ± .02[.508]
.XXX  ± .005[.127]
.XXXX ± .0005[.0127]

ECO/Submittal

SCALE

VOL

DATE

APP

ENG

APP

MFG

DR

BY

PRELIMINARY

REV

D

1

SIZE

CRANSTON, R.I.

3A

Outdoor 

Heat 

Pump

HydroBox

(0.5 m)

(0.5 m)

(0.4 m)

Содержание Glen Dimplex System M

Страница 1: ... M Air to Water Heat Pump Outdoor Unit HydroBox Building User Interface Indoor Unit Installation and Operating Instructions Document 802 001 Plant 001 5040 Effective Date July 15 2022 Powered By Glen Dimplex ...

Страница 2: ... Side 6 4 Domestic Hot Water Connection 6 5 Temperature Sensor Connection 6 6 Electrical Connection 7 Touch Screen User Interface and App 7 1 Installing the GDTS Home App 7 2 Set up of the System M 7 3 Navigation of the User Interface UHI 8 AirPurging 9 Cleaning Maintenance 9 1 Maintenance 9 2 Cleaning Heat Pump 9 3 Cleaning the HydroBox 10 Faults Troubleshooting 3 4 5 6 7 8 21 23 23 23 11 Decommi...

Страница 3: ... thus also intended for use by non professionals for heating shops offices and other similar working environments agricultural establishments and hotels guesthouses and other residential buildings The construction and design of the heat pump complies with all relevant EU and North American directives including DIN VDE UL FCC and CSA regulations When connecting the heat pump to the power supply the...

Страница 4: ...orator cools the air i e extracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increasing its pressure with the aid of the electrically driven compressors It is then transferred to the heating water via the liquefier heat exchanger Electrical energy is used to raise the temperature level...

Страница 5: ...ressor 5 Liquefier 3 2 Chiller heat pump manager The chiller heat pump manager included in the scope of supply must be used to operate the reversible air water chiller heat pump The chiller heat pump manager is a convenient electronic reg ulation and control device It controls and monitors the entire heating system based on the outdoor temperature or room temperature as well as domestic hot water p...

Страница 6: ...not be tilted more than 45 in any direction Caution Before commissioning the transport fastening must be removed www glendimplex de 452169 66 04 FD 0007 5 4 Transport 4 1 Monoblock A pallet should be used to transport the chiller heat pump to its final installation location The basic device can be transported with a lift truck hand truck or by means of 3 4 pipes fed through the holes in the basepl...

Страница 7: ...connections can be accessed by removing the left side panel of the HydroBox Although all panels can be removed the HydroBox was designed to be able to access all serviceable components and access all wiring connections by just removing the side panels It must be possible to carry out maintenance work without hindrance This is ensured if the clearance displayed below is maintained The specified dim...

Страница 8: ... condensate pipe laid in an area which is not frost free can destroy the evaporator 1 Supply Connection to HydroBox 1 1 4 NPT 2 Return Connection from HydroBox 1 1 4 NPT 3 Feedthrough for Condensate Hose 4 Feedthrough for Electrical Communications Lines 5 Optional Knockouts for Side Electrical Connections The supply and return piping between the heat pump and the HydroBox should be a minimum of 1 ...

Страница 9: ... floor drain or other means of water collection dispersement as required by code A Taco 4900 Air Separator is internal to the piping and a Taco Hy Vent is connected at the top of the buffer tank Both provide secondary air elimination within the HydroBox Both vents are shipped closed and should not be relied upon for main purging of the distribution system Additional vents should be located at the ...

Страница 10: ...10 Fig 12A System M Heating Cooling DHW Typical Application Mechancial Drawing ...

Страница 11: ...11 Fig 13A System M Heating Cooling DHW Typical Application Electrical Drawing ...

Страница 12: ...12 Fig 12B System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating boiler back up not DHW Mechanical Drawing ...

Страница 13: ...13 Fig 13B System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating boiler back up not DHW Electrical Drawing ...

Страница 14: ...14 Fig 12C System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating DHW boiler back up Mechanical Drawing ...

Страница 15: ...15 Fig 13C System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating DHW boiler back up Electrical Drawing ...

Страница 16: ...he DHW tank call always has priority Field wiring is required between the HydroBox indoor unit and the DHW tank sensor shipped with the System M see section 6 6 5 Separate 120v and 240v power connections and a field supplied contactor is also required to activate the SMT85 DHW tank and the immersion heater see section 6 6 1 A domestic hot water recirculation system can be used as part of the overa...

Страница 17: ...ng Mount the outdoor sensor loosen the bottom nut then push the thermostat sensor wire through nut and the into each of the terminal blocks tighten them down with the screws Re tighten the nut Run the wiring back to the HydroBox wiring hub terminals numbers 4 and 5 The connections are not polarity sensitive so either wire can go to either terminal Outdoor Temperature and DHW Sensor Design Paramete...

Страница 18: ...N ACCESSORY BAG WITH THE HEAT PUMP OUTDOOR UNIT CLIP ON FERRITE PART F60 02 TO BE FIELD INSTALLED WITH ON LINE AND NEUTRAL E LEADS OF THE 120V POWER INPUT TO THE HEAT PUMP OUTDOOR UNIT INCLUDED IN ACCESSORY BAG WITH THE HEAT PUMP OUTDOOR UNIT G L1 L2 GND A B 1 2 1 2 1 2 1 2 1 2 DOMESTIC HOT WATER CIRCULATING PUMP M18 1 2 M18 X2 N0 L N PE L N GND J11 Rx T Rx T GND DI8 L N G L N G L G N Y2 N L N L 1...

Страница 19: ...r Unit Indoor Unit Indirect Water Heater w 4 5kW Electrical Back up Immersion Heater Electrical Disconnects per code 240 1 60 L1 L2 PE L1 L2 PE 240 1 60 L1 L2 PE L1 L2 PE 240 1 60 L1 L2 PE L1 L2 PE Optional M13 Heating Cooling Circuit Pump 0 10VDC 15 Amp Circuit Breaker 35 Amp 2 Pole Circuit Breaker 30 Amp 2 Pole Circuit Breaker 30 Amp 2 Pole Circuit Breaker Ethernet Cable Power to Back up Electri...

Страница 20: ... UNIT TERMINAL N0 J11 B 1 2 1 2 1 2 1 2 1 2 N L N L 8 AWG GND GND GND GND L1 L2 OUTDOOR TEMPERATURE SENSOR DHW TEMPERATURE SENSOR HEATING DEMAND SMART GRID 2 FORCED COOLING CHANGE OVER HEAT COOL CIRC PUMP 0 10 VDC SIGNAL POWER OUTPUT CONTACTOR FOR DHW IMMERSION HEATER 120 VAC 1A POWER INPUT 120 VAC 5A GROUND BUFFER TANK IMMERSION HEATER 240 VAC 26A 710 1048 GND A COMMUNICATION TO HEAT PUMP OUTDOOR...

Страница 21: ...tween an external router A350 and the LAN plug on the back panel of the HydroBox indoor unit See section 11 The heat pump circulating pump M16 and domestic hot water tank circulating pump M18 are powered with 120v and designed to be operated in variable speed mode controlled through a 0 10 VDC signal Both circulator pumps are Taco 0034e SF A temperature sensor is installed in the return line befor...

Страница 22: ...Screen Reference Name LOCK1 Lock Screen Clock The default display is a clock showing the date and current outdoor temperature Touch anywhere on the screen to begin If the user interface is left idle for more than 5 minutes it will return to this screen time is adjustable in SETTINGS LS screen LOGIN1 Login Screen Drawn a M pattern starting from the bottom left dot to access the general menu and set...

Страница 23: ...ow is maintained To ensure proper drainage from the condensate tray it must be regularly inspected and cleaned if necessary To prevent faults due to sediment in the heat exchangers care must be taken to ensure that no impurities can enter either the heat source system or the heating system In the event that operating malfunctions due to contamination occur nevertheless the system should be cleaned...

Страница 24: ...44 in F m h Pa gal min psig 1 40 10 600 6 16 1 54 3 4 Sound level according to EN 12102 with A7 W55 in C A45 W131 in F outdoors Normal operation reduced operation 7 dB A 59 57 3 5 Sound level at a distance of 10 m outdoors 8 Normal operation reduced operation 7 dB A 29 27 3 6 Air flow Normal operation reduced operation 7 dB A 3 800 3 000 2 237 1 766 4 Dimensions weight and filling quantity 4 1 Dev...

Страница 25: ... metals powder like substances or chemicals e g in the nearness of livestock breeding hot springs etc 2 For air temperatures between 22 C 7 F and 5 C 23 F flow temperature increasing from 45 C 113 F to 60 C 140 F 3 For details see performance curves General tolerance for heating or cooling capacity power consumption coefficient of performance 10 General tolerance for temperature conditions 2K 4 By...

Страница 26: ...es Hatched area footprint heatpump 55 2 2 70 2 7 110 4 3 1 2 3 4 1 2 Drain pipe P 50 mm flush with foundation 97 3 8 60 2 4 Condensate hose 3 854 33 6 542 21 3 71 2 8 5 13 2 Dimension Drawing Legend 1 Supply Connection to HydroBox 1 1 4 NPT 2 Return Connection from HydroBox 1 1 4 NPT 3 Feedthrough for Condensate Hose 4 Feedthrough for Electrical Communications Lines 5 Optional Knockouts for Side E...

Страница 27: ...O RETURN THE DOCUMENT TOGETHER WITH ALL COPIES MADE IMMEDIATELY WHEN REQUESTED BY TACO APP QA INCHES MM 07 16 2020 aco Inc 4 4 OF SHEET JJK UNLESS OTHERWISE SPECIFIED ANGLES 1 FEATURE CONTROL SYMBOLS PER ANSI Y14 5 R 005 127 TO 015 38 BREAK SHARP EDGES 125 FINISHES FRACTIONS 1 64 397 XX 02 508 XXX 005 127 XXXX 0005 0127 ECO Submittal SCALE 1 4 CI VOL DATE APP ENG APP MFG DR BY PRELIMINARY REV D 1 ...

Страница 28: ...978 34 5 876 33 5 851 10 5 267 29 38 746 59 94 1522 61 44 1561 63 38 1610 ø 28 711 4 102 4 102 8 203 SENSOR WELL 3 4 MNPT FITTING COLD WATER SUPPLY 3 4 MNPT FITTING HOT WATER SUPPLY T P VALVE 4 X4 JUNCTION BOX STEEL ELECTRICAL ENCLOSURE IMMERSION HEATER ANODE DRAIN 1 1 2 MNPT HEAT PUMP SUPPLY RETURN ...

Страница 29: ... 24000 0 0 0 5 1 0 1 5 2 0 m h Pa pressure drop psig monobloc max min 50 60 70 80 90 100 110 120 130 140 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 C C heating water outlet temperature F Water outlet 2 K min Water Inlet 2K 0K The maximum Flowtemperatures are reached by compliance with the minimum heaƟng water Ňow operaƟng envelope 13 8 3 2 7 12 17 22 27 32 37 42 47 ...

Страница 30: ...he shown operating envelope General tolerances 10 0 000 1 000 2 000 3 000 4 000 5 000 6 000 7 000 8 000 9 000 10 000 11 000 12 000 13 000 14 000 15 000 16 000 17 000 0 1 2 3 4 5 kW electrical power consumption BTU h The min and max curve describes the range of the power consumption within the shown operating envelope General tolerances 10 0 1 2 3 0 4000 8000 12000 16000 20000 24000 0 0 0 5 1 0 1 5...

Страница 31: ...tenance so that this can be performed as effectively as possible The data is encrypted on all transmission paths using state of the art encryption methods Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made available to after sales service partners so that they can carry out maintenance and repair services The control and ...

Страница 32: ...ntenna s used for this transmitter must be installed such that a minimum separation distance of 20cm is maintained between the radiator antenna and all persons at all times and must not be co located or operating in conjunction with any other antenna or transmitter Taco Inc Taco or the Company will repair or replace without charge at the Company s option any Taco product or part which is proven de...

Отзывы: