background image

23

Although  a  high-performance  Taco  4900  Separator  is  installed  in  the 

HydroBox  (vent  shipped  in  the  closed  position),  it  is  recommended  that 

additional  air  vents  be  placed  at  the  high  points  of  the  system  piping, 

including  between  the  HydroBox  and  the  Heat  Pump  and  between  the 

HydroBox  and  domestic  hot  water  tank  to  help  in  purging  air  out  of  the 

system piping. 

9. Cleaning / Maintenance

8. Air Purging

10. Faults / Troubleshooting

11. Decommissioning / 

      Disposal

9.1 Maintenance

9.2 Cleaning the Heat Pump

9.3 Cleaning the HydroBox

To protect the paintwork, avoid leaning anything against putting objects on 

top of either unit. The units can be cleaned and polished with conventional 

agents, e.g. car polish.

The  evaporator,  fan  and  condensate  drain  should  be  cleaned  of 

contamination (leaves, twigs, etc.) before each new heating season.

The  HydroBox  doesn't  require  routine  maintenance.    However,  annual 

visual inspection of the piping, vents, and drip pan's drain connection (see 

Fig 3.2 #10) to make sure it has not become clogged is recommended.
If glycol is being used, follow the glycol manufacturer's recommendations for 

maintenance and testing, which is usually yearly, to maintain the correct pH 

of the system fluid.  Failure to do so can result in performance degradation 

and/or system equipment and piping failures.

To prevent the evaporator and the condensate tray from being damaged, do 

not use hard or sharp objects when cleaning.
Under extreme weather conditions (e.g. snow drifts), ice may form on the air 

intake and air outlet areas in individual cases. If this happens, the ice must 

be removed from the vicinity of the intake and air outlet area to ensure that 

the minimum air flow is maintained.
To ensure proper drainage from the condensate tray, it must be regularly 

inspected and cleaned, if necessary.

To prevent faults due to sediment in the heat exchangers, care must be 

taken to ensure that no impurities can enter either the heat source system 

or  the  heating  system.  In  the  event  that  operating  malfunctions  due  to 

contamination  occur  nevertheless,  the  system  should  be  cleaned  as 

described below.

Note: 

Never use cleaning agents containing sand, soda, acid or chloride, 

as these can damage the surfaces.

Note: 

Personal protective equipment (protective goggles, safety shoes 

and gloves where necessary) must be used when working on the device. 

Components with plastic parts must be protected from impact (e.g. from 

tools) to prevent damage to these components.

Caution:

 Before opening the device, ensure that all circuits are 

disconnected from the power supply. Multiple disconnects might 

be present.

Caution:

  Work  on  the  system  must  only  be  performed  by 

authorized and qualified after-sales service technicians.

Caution:

 Before opening the device, ensure that all circuits are 

disconnected from the power supply. Multiple disconnects may 

be present.

This  heat  pump  is  a  quality  product  and  is  designed  for  trouble-free 

operation. In the event that a fault should occur, it will be indicated on the 

user interface display.
If  you  cannot  correct  the  fault  yourself,  please  contact  your  after-sales 

service technician.

Before removing the heat pump, disconnect the machine from the power 

source  and  close  all  inflow  and  outflow  valves. The  heat  pump  must  be 

dismantled by trained personnel. All environmentally-relevant requirements 

regarding the recovery, recycling and disposal of materials and components 

should be observed in accordance with the applicable standards. Particular 

attention should be paid to the proper disposal of refrigerants and refrigerant 

oils.

Содержание Glen Dimplex System M

Страница 1: ... M Air to Water Heat Pump Outdoor Unit HydroBox Building User Interface Indoor Unit Installation and Operating Instructions Document 802 001 Plant 001 5040 Effective Date July 15 2022 Powered By Glen Dimplex ...

Страница 2: ... Side 6 4 Domestic Hot Water Connection 6 5 Temperature Sensor Connection 6 6 Electrical Connection 7 Touch Screen User Interface and App 7 1 Installing the GDTS Home App 7 2 Set up of the System M 7 3 Navigation of the User Interface UHI 8 AirPurging 9 Cleaning Maintenance 9 1 Maintenance 9 2 Cleaning Heat Pump 9 3 Cleaning the HydroBox 10 Faults Troubleshooting 3 4 5 6 7 8 21 23 23 23 11 Decommi...

Страница 3: ... thus also intended for use by non professionals for heating shops offices and other similar working environments agricultural establishments and hotels guesthouses and other residential buildings The construction and design of the heat pump complies with all relevant EU and North American directives including DIN VDE UL FCC and CSA regulations When connecting the heat pump to the power supply the...

Страница 4: ...orator cools the air i e extracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increasing its pressure with the aid of the electrically driven compressors It is then transferred to the heating water via the liquefier heat exchanger Electrical energy is used to raise the temperature level...

Страница 5: ...ressor 5 Liquefier 3 2 Chiller heat pump manager The chiller heat pump manager included in the scope of supply must be used to operate the reversible air water chiller heat pump The chiller heat pump manager is a convenient electronic reg ulation and control device It controls and monitors the entire heating system based on the outdoor temperature or room temperature as well as domestic hot water p...

Страница 6: ...not be tilted more than 45 in any direction Caution Before commissioning the transport fastening must be removed www glendimplex de 452169 66 04 FD 0007 5 4 Transport 4 1 Monoblock A pallet should be used to transport the chiller heat pump to its final installation location The basic device can be transported with a lift truck hand truck or by means of 3 4 pipes fed through the holes in the basepl...

Страница 7: ...connections can be accessed by removing the left side panel of the HydroBox Although all panels can be removed the HydroBox was designed to be able to access all serviceable components and access all wiring connections by just removing the side panels It must be possible to carry out maintenance work without hindrance This is ensured if the clearance displayed below is maintained The specified dim...

Страница 8: ... condensate pipe laid in an area which is not frost free can destroy the evaporator 1 Supply Connection to HydroBox 1 1 4 NPT 2 Return Connection from HydroBox 1 1 4 NPT 3 Feedthrough for Condensate Hose 4 Feedthrough for Electrical Communications Lines 5 Optional Knockouts for Side Electrical Connections The supply and return piping between the heat pump and the HydroBox should be a minimum of 1 ...

Страница 9: ... floor drain or other means of water collection dispersement as required by code A Taco 4900 Air Separator is internal to the piping and a Taco Hy Vent is connected at the top of the buffer tank Both provide secondary air elimination within the HydroBox Both vents are shipped closed and should not be relied upon for main purging of the distribution system Additional vents should be located at the ...

Страница 10: ...10 Fig 12A System M Heating Cooling DHW Typical Application Mechancial Drawing ...

Страница 11: ...11 Fig 13A System M Heating Cooling DHW Typical Application Electrical Drawing ...

Страница 12: ...12 Fig 12B System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating boiler back up not DHW Mechanical Drawing ...

Страница 13: ...13 Fig 13B System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating boiler back up not DHW Electrical Drawing ...

Страница 14: ...14 Fig 12C System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating DHW boiler back up Mechanical Drawing ...

Страница 15: ...15 Fig 13C System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating DHW boiler back up Electrical Drawing ...

Страница 16: ...he DHW tank call always has priority Field wiring is required between the HydroBox indoor unit and the DHW tank sensor shipped with the System M see section 6 6 5 Separate 120v and 240v power connections and a field supplied contactor is also required to activate the SMT85 DHW tank and the immersion heater see section 6 6 1 A domestic hot water recirculation system can be used as part of the overa...

Страница 17: ...ng Mount the outdoor sensor loosen the bottom nut then push the thermostat sensor wire through nut and the into each of the terminal blocks tighten them down with the screws Re tighten the nut Run the wiring back to the HydroBox wiring hub terminals numbers 4 and 5 The connections are not polarity sensitive so either wire can go to either terminal Outdoor Temperature and DHW Sensor Design Paramete...

Страница 18: ...N ACCESSORY BAG WITH THE HEAT PUMP OUTDOOR UNIT CLIP ON FERRITE PART F60 02 TO BE FIELD INSTALLED WITH ON LINE AND NEUTRAL E LEADS OF THE 120V POWER INPUT TO THE HEAT PUMP OUTDOOR UNIT INCLUDED IN ACCESSORY BAG WITH THE HEAT PUMP OUTDOOR UNIT G L1 L2 GND A B 1 2 1 2 1 2 1 2 1 2 DOMESTIC HOT WATER CIRCULATING PUMP M18 1 2 M18 X2 N0 L N PE L N GND J11 Rx T Rx T GND DI8 L N G L N G L G N Y2 N L N L 1...

Страница 19: ...r Unit Indoor Unit Indirect Water Heater w 4 5kW Electrical Back up Immersion Heater Electrical Disconnects per code 240 1 60 L1 L2 PE L1 L2 PE 240 1 60 L1 L2 PE L1 L2 PE 240 1 60 L1 L2 PE L1 L2 PE Optional M13 Heating Cooling Circuit Pump 0 10VDC 15 Amp Circuit Breaker 35 Amp 2 Pole Circuit Breaker 30 Amp 2 Pole Circuit Breaker 30 Amp 2 Pole Circuit Breaker Ethernet Cable Power to Back up Electri...

Страница 20: ... UNIT TERMINAL N0 J11 B 1 2 1 2 1 2 1 2 1 2 N L N L 8 AWG GND GND GND GND L1 L2 OUTDOOR TEMPERATURE SENSOR DHW TEMPERATURE SENSOR HEATING DEMAND SMART GRID 2 FORCED COOLING CHANGE OVER HEAT COOL CIRC PUMP 0 10 VDC SIGNAL POWER OUTPUT CONTACTOR FOR DHW IMMERSION HEATER 120 VAC 1A POWER INPUT 120 VAC 5A GROUND BUFFER TANK IMMERSION HEATER 240 VAC 26A 710 1048 GND A COMMUNICATION TO HEAT PUMP OUTDOOR...

Страница 21: ...tween an external router A350 and the LAN plug on the back panel of the HydroBox indoor unit See section 11 The heat pump circulating pump M16 and domestic hot water tank circulating pump M18 are powered with 120v and designed to be operated in variable speed mode controlled through a 0 10 VDC signal Both circulator pumps are Taco 0034e SF A temperature sensor is installed in the return line befor...

Страница 22: ...Screen Reference Name LOCK1 Lock Screen Clock The default display is a clock showing the date and current outdoor temperature Touch anywhere on the screen to begin If the user interface is left idle for more than 5 minutes it will return to this screen time is adjustable in SETTINGS LS screen LOGIN1 Login Screen Drawn a M pattern starting from the bottom left dot to access the general menu and set...

Страница 23: ...ow is maintained To ensure proper drainage from the condensate tray it must be regularly inspected and cleaned if necessary To prevent faults due to sediment in the heat exchangers care must be taken to ensure that no impurities can enter either the heat source system or the heating system In the event that operating malfunctions due to contamination occur nevertheless the system should be cleaned...

Страница 24: ...44 in F m h Pa gal min psig 1 40 10 600 6 16 1 54 3 4 Sound level according to EN 12102 with A7 W55 in C A45 W131 in F outdoors Normal operation reduced operation 7 dB A 59 57 3 5 Sound level at a distance of 10 m outdoors 8 Normal operation reduced operation 7 dB A 29 27 3 6 Air flow Normal operation reduced operation 7 dB A 3 800 3 000 2 237 1 766 4 Dimensions weight and filling quantity 4 1 Dev...

Страница 25: ... metals powder like substances or chemicals e g in the nearness of livestock breeding hot springs etc 2 For air temperatures between 22 C 7 F and 5 C 23 F flow temperature increasing from 45 C 113 F to 60 C 140 F 3 For details see performance curves General tolerance for heating or cooling capacity power consumption coefficient of performance 10 General tolerance for temperature conditions 2K 4 By...

Страница 26: ...es Hatched area footprint heatpump 55 2 2 70 2 7 110 4 3 1 2 3 4 1 2 Drain pipe P 50 mm flush with foundation 97 3 8 60 2 4 Condensate hose 3 854 33 6 542 21 3 71 2 8 5 13 2 Dimension Drawing Legend 1 Supply Connection to HydroBox 1 1 4 NPT 2 Return Connection from HydroBox 1 1 4 NPT 3 Feedthrough for Condensate Hose 4 Feedthrough for Electrical Communications Lines 5 Optional Knockouts for Side E...

Страница 27: ...O RETURN THE DOCUMENT TOGETHER WITH ALL COPIES MADE IMMEDIATELY WHEN REQUESTED BY TACO APP QA INCHES MM 07 16 2020 aco Inc 4 4 OF SHEET JJK UNLESS OTHERWISE SPECIFIED ANGLES 1 FEATURE CONTROL SYMBOLS PER ANSI Y14 5 R 005 127 TO 015 38 BREAK SHARP EDGES 125 FINISHES FRACTIONS 1 64 397 XX 02 508 XXX 005 127 XXXX 0005 0127 ECO Submittal SCALE 1 4 CI VOL DATE APP ENG APP MFG DR BY PRELIMINARY REV D 1 ...

Страница 28: ...978 34 5 876 33 5 851 10 5 267 29 38 746 59 94 1522 61 44 1561 63 38 1610 ø 28 711 4 102 4 102 8 203 SENSOR WELL 3 4 MNPT FITTING COLD WATER SUPPLY 3 4 MNPT FITTING HOT WATER SUPPLY T P VALVE 4 X4 JUNCTION BOX STEEL ELECTRICAL ENCLOSURE IMMERSION HEATER ANODE DRAIN 1 1 2 MNPT HEAT PUMP SUPPLY RETURN ...

Страница 29: ... 24000 0 0 0 5 1 0 1 5 2 0 m h Pa pressure drop psig monobloc max min 50 60 70 80 90 100 110 120 130 140 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 C C heating water outlet temperature F Water outlet 2 K min Water Inlet 2K 0K The maximum Flowtemperatures are reached by compliance with the minimum heaƟng water Ňow operaƟng envelope 13 8 3 2 7 12 17 22 27 32 37 42 47 ...

Страница 30: ...he shown operating envelope General tolerances 10 0 000 1 000 2 000 3 000 4 000 5 000 6 000 7 000 8 000 9 000 10 000 11 000 12 000 13 000 14 000 15 000 16 000 17 000 0 1 2 3 4 5 kW electrical power consumption BTU h The min and max curve describes the range of the power consumption within the shown operating envelope General tolerances 10 0 1 2 3 0 4000 8000 12000 16000 20000 24000 0 0 0 5 1 0 1 5...

Страница 31: ...tenance so that this can be performed as effectively as possible The data is encrypted on all transmission paths using state of the art encryption methods Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made available to after sales service partners so that they can carry out maintenance and repair services The control and ...

Страница 32: ...ntenna s used for this transmitter must be installed such that a minimum separation distance of 20cm is maintained between the radiator antenna and all persons at all times and must not be co located or operating in conjunction with any other antenna or transmitter Taco Inc Taco or the Company will repair or replace without charge at the Company s option any Taco product or part which is proven de...

Отзывы: