background image

3

1. Please Read Immediately

1.1 Intended Use

1.3 Energy Efficient Use of the Heat Pump

1.4 Inspection of Equipment

1.5 Handling of the Unit

1.6 Unit Protection on Job Site

These devices are only intended for use as specified by the manufactur-

er. Any other use beyond that intended by the manufacturer is prohibited. 

This requires the user to abide by the relevant project planning documents, 

specifications  and  installation  and  operating  instructions.  Please  refrain 

from tampering with or altering the device.

By operating this heat pump you are helping to protect our environment. 

The  heating  system  must  be  properly  designed  and  dimensioned  to 

ensure  efficient  operation.  It  is  particularly  important  to  keep  water  flow 

temperatures as low as possible in heating operation. All connected heat 

emitters  should  therefore  be  suitable  for  low  flow  temperatures.  Raising 

the heating water temperature by 1.8°F (1°C) corresponds to an increase 

in electric energy consumption of approx. 2.5%. Low temperature heating 

systems with flow temperatures between 85°F and 125°F (30°C and 50°C) 

are particularly well-suited for energy efficient operation.

Upon  receipt  of  equipment,  check  the  shipment  against  the  packing  slip 

and the freight company bill of lading.  Verify that all units and packages 

have  been  received.    Inspect  the  packaging  of  each  unit  for  damages.  

Any  damage  should  be  reported  to  the  freight  company  immediately  to 

make sure they can not deny claims.  Notify the wholesaler or party you 

purchased this equipment from of any damages.  It is the responsibility of 

the purchaser to notify relevant parties and file the necessary claims with 

the freight company.
The Heat Pump outdoor unit includes a TiltWatch® label on the packaging to 

monitor if the unit has been tipped more than 45 degrees during shipment.  

If this label has been activated, notify the freight company and contact Taco 

customer service. 

Do not clamp on the sides of either the HydroBox indoor unit or Heat Pump 

outdoor unit when lifting or transporting the units into place.  Damage can 

occur to the panels of the units.  Also take caution during transportation as 

the outdoor unit may be top-heavy.  Both units are too heavy for one person 

to lift.  It is highly recommended to install the HydroBox and heat pump with 

two people.  Use caution not to drop the units, which could cause damage 

to the unit, property and/or sever personal injury.

Keep  both  units  covered  in  the  original  packaging  or  equivalent 

protective  covering  to  protect  the  units  from  damage  and  contamination 

due  to  paint  spray,  plastering  or  other  airborne  materials  that  may  be 

used  during  construction  on  the  job  site. This  is  especially  important  for 

protecting the outdoor unit’s heat exchanger intake and outlet areas.  All 

piping connections should remain capped or recapped until the piping is 

connected.    Precautions  must  be  taken  to  avoid  physical  damage  and 

contamination which may prevent proper start-up and may result in costly 

repair or equipment failure.
Units should be transported and stored in an upright manner at all times 

and should not be stacked.  The HydroBox indoor unit cannot be stored 

outside and should be protected from the elements during shipping.  Excess 

moisture can damage the electronics in the unit.

1.2 Legal Regulations and Directives

The heat pump is designed for use in a domestic environment according to 

Article 1, Paragraph 2 k) of EC directive 2006/42/EC (machinery directive) 

and is thus subject to the requirements of EU directive 2014/35/EU (low-

voltage directive). It is thus also intended for use by non-professionals for 

heating shops, offices and other similar working environments, agricultural 

establishments and hotels, guesthouses and other residential buildings.
The construction and design of the heat pump complies with all relevant 

EU and North American directives, including DIN, VDE, UL, FCC, and CSA 

regulations.
When connecting the heat pump to the power supply, the relevant VDE, EN, 

IEC, UL and CSA standards are to be adhered to. Any further connection 

requirements stipulated by local utility companies or codes must also be 

observed.
When connecting the heating system or cooling system, all country-specific 

and local regulations must also be adhered to.
This unit can be used by children aged 8 and over and by persons with 

limited physical, sensory or mental aptitude or lack of experience and/or 

knowledge, providing they are supervised or have been instructed in the 

safe use of the unit and understand the associated potential dangers.
Children  must  not  play  with  the  device.  Cleaning  and  user  maintenance 

must not be carried out by children without supervision.

Warning!

 This heat pump system must be installed by a licensed 

plumber,  electrician,  and/or  professional  service  technician.  

Improper  installation  and/or  operation  can  cause  a  potentially 

hazardous situation, which, if not avoided, could result in serious 

injury or death, and will void the warranty.

Note:

  When  operating  or  maintaining  a  heat  pump,  the  legal 

requirements of the state or country where the heat pump is operated 

apply. Depending on the refrigerant fill quantity, the heat pump may have 

to be inspected for leaks at regular intervals by a certified technician, and 

these inspections must be recorded. 

Note:

  No  one  but  a  professional  service  technician  should  attempt 

to  install,  service,  or  repair  this  heat  pump  system.    There  are  no 

serviceable parts which can be changed by the user / owner.  User / 

owner should contact the original professional service technician if the 

heat pump system needs repair or maintenance.

Note:

 When servicing the equipment, be sure to disconnect electrical 

power before removing any of the panels from either the HydroBox indoor 

unit or Heat Pump outdoor unit.  There may be multiple disconnects for 

each  unit.    Label  all  wires  while  performing  service  to  ensure  proper 

re-wiring of the units.  Wiring errors can cause improper or dangerous 

operation.  Failure to do so could result in an electrical shock, improper 

heat pump operation, property damage, serious personal injury, or death.

Note:

 Do not use petroleum-based cleaning or sealing compounds in a 

heat pump system.  Gaskets and seals in the system could be damaged.  

This could result in substantial property damage.

Note:

 Chemical imbalance of the water supply may effect efficiency and 

cause  severe  damage  to  the  heat  pump  and  associated  equipment.  

Water quality must be professionally analyzed to determine whether it 

is necessary to adjust water quality.  The water must be potable, free 

of corrosive chemicals, sand, dirt, and other contaminates so as not to 

damage the heat exchanger.  Potable water is defined as drinkable water 

supplied from a utility or well water in compliance with EPA secondary 

maximum contaminant levels (40 CFR 143.3).  Failure of the equipment 

due to lime scale build-up or other chemical imbalance is not covered by 

the warranty.

Note:

 Because water lines run between the HydroBox indoor unit and 

Heat  Pump  outdoor  unit,  proper  freeze  protection  may  be  required 

depending  on  climate.  Never  use  any  toxic  chemical,  including 

automotive,  standard  glycol  antifreeze,  or  ethylene  glycol  made  for 

hydronic (non-potable) systems.  These chemicals can attack gaskets 

and seals in water systems, are poisonous if consumed, and can cause 

personal injury.

Содержание Glen Dimplex System M

Страница 1: ... M Air to Water Heat Pump Outdoor Unit HydroBox Building User Interface Indoor Unit Installation and Operating Instructions Document 802 001 Plant 001 5040 Effective Date July 15 2022 Powered By Glen Dimplex ...

Страница 2: ... Side 6 4 Domestic Hot Water Connection 6 5 Temperature Sensor Connection 6 6 Electrical Connection 7 Touch Screen User Interface and App 7 1 Installing the GDTS Home App 7 2 Set up of the System M 7 3 Navigation of the User Interface UHI 8 AirPurging 9 Cleaning Maintenance 9 1 Maintenance 9 2 Cleaning Heat Pump 9 3 Cleaning the HydroBox 10 Faults Troubleshooting 3 4 5 6 7 8 21 23 23 23 11 Decommi...

Страница 3: ... thus also intended for use by non professionals for heating shops offices and other similar working environments agricultural establishments and hotels guesthouses and other residential buildings The construction and design of the heat pump complies with all relevant EU and North American directives including DIN VDE UL FCC and CSA regulations When connecting the heat pump to the power supply the...

Страница 4: ...orator cools the air i e extracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increasing its pressure with the aid of the electrically driven compressors It is then transferred to the heating water via the liquefier heat exchanger Electrical energy is used to raise the temperature level...

Страница 5: ...ressor 5 Liquefier 3 2 Chiller heat pump manager The chiller heat pump manager included in the scope of supply must be used to operate the reversible air water chiller heat pump The chiller heat pump manager is a convenient electronic reg ulation and control device It controls and monitors the entire heating system based on the outdoor temperature or room temperature as well as domestic hot water p...

Страница 6: ...not be tilted more than 45 in any direction Caution Before commissioning the transport fastening must be removed www glendimplex de 452169 66 04 FD 0007 5 4 Transport 4 1 Monoblock A pallet should be used to transport the chiller heat pump to its final installation location The basic device can be transported with a lift truck hand truck or by means of 3 4 pipes fed through the holes in the basepl...

Страница 7: ...connections can be accessed by removing the left side panel of the HydroBox Although all panels can be removed the HydroBox was designed to be able to access all serviceable components and access all wiring connections by just removing the side panels It must be possible to carry out maintenance work without hindrance This is ensured if the clearance displayed below is maintained The specified dim...

Страница 8: ... condensate pipe laid in an area which is not frost free can destroy the evaporator 1 Supply Connection to HydroBox 1 1 4 NPT 2 Return Connection from HydroBox 1 1 4 NPT 3 Feedthrough for Condensate Hose 4 Feedthrough for Electrical Communications Lines 5 Optional Knockouts for Side Electrical Connections The supply and return piping between the heat pump and the HydroBox should be a minimum of 1 ...

Страница 9: ... floor drain or other means of water collection dispersement as required by code A Taco 4900 Air Separator is internal to the piping and a Taco Hy Vent is connected at the top of the buffer tank Both provide secondary air elimination within the HydroBox Both vents are shipped closed and should not be relied upon for main purging of the distribution system Additional vents should be located at the ...

Страница 10: ...10 Fig 12A System M Heating Cooling DHW Typical Application Mechancial Drawing ...

Страница 11: ...11 Fig 13A System M Heating Cooling DHW Typical Application Electrical Drawing ...

Страница 12: ...12 Fig 12B System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating boiler back up not DHW Mechanical Drawing ...

Страница 13: ...13 Fig 13B System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating boiler back up not DHW Electrical Drawing ...

Страница 14: ...14 Fig 12C System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating DHW boiler back up Mechanical Drawing ...

Страница 15: ...15 Fig 13C System M with Boiler Back Up Either Heat Pump Only or Boiler Only Central heating DHW boiler back up Electrical Drawing ...

Страница 16: ...he DHW tank call always has priority Field wiring is required between the HydroBox indoor unit and the DHW tank sensor shipped with the System M see section 6 6 5 Separate 120v and 240v power connections and a field supplied contactor is also required to activate the SMT85 DHW tank and the immersion heater see section 6 6 1 A domestic hot water recirculation system can be used as part of the overa...

Страница 17: ...ng Mount the outdoor sensor loosen the bottom nut then push the thermostat sensor wire through nut and the into each of the terminal blocks tighten them down with the screws Re tighten the nut Run the wiring back to the HydroBox wiring hub terminals numbers 4 and 5 The connections are not polarity sensitive so either wire can go to either terminal Outdoor Temperature and DHW Sensor Design Paramete...

Страница 18: ...N ACCESSORY BAG WITH THE HEAT PUMP OUTDOOR UNIT CLIP ON FERRITE PART F60 02 TO BE FIELD INSTALLED WITH ON LINE AND NEUTRAL E LEADS OF THE 120V POWER INPUT TO THE HEAT PUMP OUTDOOR UNIT INCLUDED IN ACCESSORY BAG WITH THE HEAT PUMP OUTDOOR UNIT G L1 L2 GND A B 1 2 1 2 1 2 1 2 1 2 DOMESTIC HOT WATER CIRCULATING PUMP M18 1 2 M18 X2 N0 L N PE L N GND J11 Rx T Rx T GND DI8 L N G L N G L G N Y2 N L N L 1...

Страница 19: ...r Unit Indoor Unit Indirect Water Heater w 4 5kW Electrical Back up Immersion Heater Electrical Disconnects per code 240 1 60 L1 L2 PE L1 L2 PE 240 1 60 L1 L2 PE L1 L2 PE 240 1 60 L1 L2 PE L1 L2 PE Optional M13 Heating Cooling Circuit Pump 0 10VDC 15 Amp Circuit Breaker 35 Amp 2 Pole Circuit Breaker 30 Amp 2 Pole Circuit Breaker 30 Amp 2 Pole Circuit Breaker Ethernet Cable Power to Back up Electri...

Страница 20: ... UNIT TERMINAL N0 J11 B 1 2 1 2 1 2 1 2 1 2 N L N L 8 AWG GND GND GND GND L1 L2 OUTDOOR TEMPERATURE SENSOR DHW TEMPERATURE SENSOR HEATING DEMAND SMART GRID 2 FORCED COOLING CHANGE OVER HEAT COOL CIRC PUMP 0 10 VDC SIGNAL POWER OUTPUT CONTACTOR FOR DHW IMMERSION HEATER 120 VAC 1A POWER INPUT 120 VAC 5A GROUND BUFFER TANK IMMERSION HEATER 240 VAC 26A 710 1048 GND A COMMUNICATION TO HEAT PUMP OUTDOOR...

Страница 21: ...tween an external router A350 and the LAN plug on the back panel of the HydroBox indoor unit See section 11 The heat pump circulating pump M16 and domestic hot water tank circulating pump M18 are powered with 120v and designed to be operated in variable speed mode controlled through a 0 10 VDC signal Both circulator pumps are Taco 0034e SF A temperature sensor is installed in the return line befor...

Страница 22: ...Screen Reference Name LOCK1 Lock Screen Clock The default display is a clock showing the date and current outdoor temperature Touch anywhere on the screen to begin If the user interface is left idle for more than 5 minutes it will return to this screen time is adjustable in SETTINGS LS screen LOGIN1 Login Screen Drawn a M pattern starting from the bottom left dot to access the general menu and set...

Страница 23: ...ow is maintained To ensure proper drainage from the condensate tray it must be regularly inspected and cleaned if necessary To prevent faults due to sediment in the heat exchangers care must be taken to ensure that no impurities can enter either the heat source system or the heating system In the event that operating malfunctions due to contamination occur nevertheless the system should be cleaned...

Страница 24: ...44 in F m h Pa gal min psig 1 40 10 600 6 16 1 54 3 4 Sound level according to EN 12102 with A7 W55 in C A45 W131 in F outdoors Normal operation reduced operation 7 dB A 59 57 3 5 Sound level at a distance of 10 m outdoors 8 Normal operation reduced operation 7 dB A 29 27 3 6 Air flow Normal operation reduced operation 7 dB A 3 800 3 000 2 237 1 766 4 Dimensions weight and filling quantity 4 1 Dev...

Страница 25: ... metals powder like substances or chemicals e g in the nearness of livestock breeding hot springs etc 2 For air temperatures between 22 C 7 F and 5 C 23 F flow temperature increasing from 45 C 113 F to 60 C 140 F 3 For details see performance curves General tolerance for heating or cooling capacity power consumption coefficient of performance 10 General tolerance for temperature conditions 2K 4 By...

Страница 26: ...es Hatched area footprint heatpump 55 2 2 70 2 7 110 4 3 1 2 3 4 1 2 Drain pipe P 50 mm flush with foundation 97 3 8 60 2 4 Condensate hose 3 854 33 6 542 21 3 71 2 8 5 13 2 Dimension Drawing Legend 1 Supply Connection to HydroBox 1 1 4 NPT 2 Return Connection from HydroBox 1 1 4 NPT 3 Feedthrough for Condensate Hose 4 Feedthrough for Electrical Communications Lines 5 Optional Knockouts for Side E...

Страница 27: ...O RETURN THE DOCUMENT TOGETHER WITH ALL COPIES MADE IMMEDIATELY WHEN REQUESTED BY TACO APP QA INCHES MM 07 16 2020 aco Inc 4 4 OF SHEET JJK UNLESS OTHERWISE SPECIFIED ANGLES 1 FEATURE CONTROL SYMBOLS PER ANSI Y14 5 R 005 127 TO 015 38 BREAK SHARP EDGES 125 FINISHES FRACTIONS 1 64 397 XX 02 508 XXX 005 127 XXXX 0005 0127 ECO Submittal SCALE 1 4 CI VOL DATE APP ENG APP MFG DR BY PRELIMINARY REV D 1 ...

Страница 28: ...978 34 5 876 33 5 851 10 5 267 29 38 746 59 94 1522 61 44 1561 63 38 1610 ø 28 711 4 102 4 102 8 203 SENSOR WELL 3 4 MNPT FITTING COLD WATER SUPPLY 3 4 MNPT FITTING HOT WATER SUPPLY T P VALVE 4 X4 JUNCTION BOX STEEL ELECTRICAL ENCLOSURE IMMERSION HEATER ANODE DRAIN 1 1 2 MNPT HEAT PUMP SUPPLY RETURN ...

Страница 29: ... 24000 0 0 0 5 1 0 1 5 2 0 m h Pa pressure drop psig monobloc max min 50 60 70 80 90 100 110 120 130 140 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 C C heating water outlet temperature F Water outlet 2 K min Water Inlet 2K 0K The maximum Flowtemperatures are reached by compliance with the minimum heaƟng water Ňow operaƟng envelope 13 8 3 2 7 12 17 22 27 32 37 42 47 ...

Страница 30: ...he shown operating envelope General tolerances 10 0 000 1 000 2 000 3 000 4 000 5 000 6 000 7 000 8 000 9 000 10 000 11 000 12 000 13 000 14 000 15 000 16 000 17 000 0 1 2 3 4 5 kW electrical power consumption BTU h The min and max curve describes the range of the power consumption within the shown operating envelope General tolerances 10 0 1 2 3 0 4000 8000 12000 16000 20000 24000 0 0 0 5 1 0 1 5...

Страница 31: ...tenance so that this can be performed as effectively as possible The data is encrypted on all transmission paths using state of the art encryption methods Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made available to after sales service partners so that they can carry out maintenance and repair services The control and ...

Страница 32: ...ntenna s used for this transmitter must be installed such that a minimum separation distance of 20cm is maintained between the radiator antenna and all persons at all times and must not be co located or operating in conjunction with any other antenna or transmitter Taco Inc Taco or the Company will repair or replace without charge at the Company s option any Taco product or part which is proven de...

Отзывы: