Turn the thermostat to the off position.
7.
Place the thermostat in the “COOL” position. Turn the thermostat down to activate a 1
st
stage call for
cooling. The compressor will start after a 3 minute ACD period from its last shutdown.
The compressor and furnace/fan coil blower will start.
8.
After the unit has run about 3 minutes.
Check and record the source side supply and return water temperatures.
Check and record the supply and return air temperatures.
Check and record the running voltage.
Check and record the total amp draw.
Check and record the compressor amp draw.
9.
Raise the thermostat only enough to call 2
nd
stage (if applicable)
Check and record the source side supply and return water temperatures.
Check and record the supply and return air temperatures.
Check and record the running voltage.
Check and record the total amp draw.
Check and record the compressor amp draw.
10.
Be sure all operational data has been collected and recorded on the ‘FA Heat Pump Operational
Statistics’ sheet.
11.
Reset the thermostat to normal mode and temperature settings for the season.
12.
Instruct the owner on correct operation of the thermostat and heat pump system.