12/03/2012
28
GI301
Electrical Installation
WARNING
DISCONNECT ALL ELECTRICAL POWER BEFORE ELECTRICALLY CONNECTING OR
SERVICING THE UNIT. FAILURE TO DISCONNECT THE ELECTRICAL POWER BEFORE
WORKING ON THIS PRODUCT CAN CREATE A HAZARD LEADING TO PERSONAL INJURY
OR DEATH.
Line Voltage
The nameplate and/or Installation and Operating Manual specification page provides RLA, LRA, and total amps
requirement. Select the proper wire size to comply with your type of wire routing and NEC field wiring
requirements.
If field supply is 208V the tap on the transformer primary winding must be switched from orange
tor red. See the wiring diagram.
The field power supply connection is at the compressor contactor, at the end of the line voltage control box.
Disconnect –
field provided external safety disconnect is required, see nameplate max amps.
Loop pumps –
control box, upper right, is the pump relay board with field terminal block connection for the
source loop pump station and where applicable the 2
nd
loop pump (load pump output applies only to water to
water series). These outputs are controlled by GEO Logic, but protected with 10-amp fusing.
Grounding
– route and install the proper size ground conductor between the ground lug above the compressor
contactor and the building service entrance panel ground bus. This must be a conductor wire size according to
NEC code for the total amp rating of the installed model. The conduit is not sufficient ground conductor.
WARNING
USE ONLY COPPER WIRE FOR CONNECTION TO THE CIRCUIT BREAKER TERMINALS
AND INSIDE THIS PRODUCT’S CABINET.
WARNING
TO AVOID THE RISK OF ELECTRIC SHOCK OR DEATH, WIRING TO THE UNIT MUST BE
PROPERLY GROUNDED. FAILURE TO PROPERLY GROUND THE UNIT CAN RESULT IN A
HAZARD LEADING TO PERSONAL INJURY OR DEATH.