12/03/2012
25
GI301
Unit Operating Conditions – Heat
Model
Stage
Source
Temp
Source temp
Δ
GPM
Air temp
Δ
Amps 240
Blower
AMPS
CFM
Discharge
pressure at
68 deg A-RT
Discharge
temp
Sub cool at
TXV
Suction
pressure
at bulb
Suction
temp at
bulb
Super- heat
at bulb
2
32
3.3-5.3
6
26-32
8.6-9.6
1.5
840-880
317-337
161-167
16.3-20.3
80-88
30-36
10.1-14.1
2
50
4.8-6.8
6
34-39
9.7-10.7
1.5
850-890
365-385
161-167
16.4-20.4
115-123
44-50
8.0-12.0
2
68
7.2-9.2
6
41-46
11.0-12.0
1.4
840-880
411-431
167-173
16.4-20.4
146-154
61-67
9.3-13.1
1
41
2.7-4.7
6
22-27
5.8-6.8
1.0
690-730
298-318
148-154
10.8-14.8
100-108
40-46
7.6-11.6
1
50
3.0-5.0
6
27-32
6.1-7.1
1.0
690-730
322-342
148-154
11.8-15.8
119-127
48-54
7.7-11.7
1
68
5.1-7.1
6
33-38
6.4-7.4
1.0
690-730
358-378
150-156
12.1-16.1
151-159
63-69
8.4-12.4
2
32
4.0-6.0
9
24-29
11.4-12.4
2.4
1190-1230
305-325
133-139
15.4-19.4
79-88
31-37
10.9-14.9
2
50
5.4-7.4
9
31-36
12.9-13.9
2.3
1200-1240
345-365
136-142
17.7-21.7
19-117
46-50
9.6-13.6
2
68
8.0-10.0
9
41-46
14.4-15.4
2.2
1190-1230
404-424
143-149
15.5-19.5
148-156
62-69
9.7-13.7
1
41
3.3-5.3
9
24-29
8.1-9.1
1.6
980-1020
298-318
131-137
13.5-17.5
98-106
40-46
8.7-12.7
1
50
3.7-5.7
9
27-32
8.4-9.4
1.6
990-1030
315-335
128-134
13.0-17.0
114-122
45-51
6.9-10.9
1
68
5.6-7.6
9
33-38
9.0-10.0
1.6
970-1010
354-374
133-139
15.1-19.1
150-158
61-68
8.1-12.1
2
32
3.4-7.4
12
26-34
17.0-23.0
3.0
1487-1567
313-353
165-175
14-22
71-91
28-34
7.4-15.4
2
50
5.6-9..6
12
35-43
19.5-25.5
3.0
1485-1565
360-400
167-176
17.8-25.8
106-126
43-49
4.5-12.5
1
41
3.0-7.0
12
26-34
11.4-17.4
2.1
1177-1257
304-344
153-163
8.4-16.4
92-112
39-45
6.1-14.1
1
50
3.4-7.4
12
30-38
11.9-17.9
2.1
1188-1268
325-365
153-163
10.6-18.6
109-129
46-52
5.7-13.7
2
32
3.9-5.9
15
26-31
20.4-21.4
4.7
1850-1890
317-337
161-167
15.3-19.3
73-82
30-36
12.9-16.9
2
50
6.0-8.0
15
34-41
23.0-24.0
4.7
1850-1890
363-383
160-166
17.3-21.3
103-111
43-50
10.3-14.3
2
68
8.0-10.0
15
40-45
25.2-26.2
4.7
1860-1900
408-428
165-171
18.2-22.2
132-140
56-62
10.7-14.7
1
41
4.2-6.2
15
25-30
15.9-16.9
3.6
1590-1630
310-330
153-159
11.8-15.8
95-103
38-45
9.0-13.0
1
50
4.3-6.3
15
28-33
16.3-17.3
3.6
1600-1640
325-345
152-158
12.5-16.5
110-118
45-52
9.1-13.1
1
68
6.4-8.4
15
35-40
17.5-18.5
3.6
1620-1660
367-387
151-157
12.5-16.5
146-154
60-66
7.9-11.9
TST-048
TST-060
TST-024
TST-036
NOTE:
These are nominal expected conditions, will vary from model to model. Refrigeration technician must use his own experience and judgment to verify proper charge and proper setting of TXV.