Note 1: If the BACnet object state is overriden locally (e.g. OFF/ECO/Lock locally cancelled), then to 
read the device status in the Present Value field, set all priority inputs to ’null’.

Note 2: Light and AC icons can be locally overridden only if the all Priority inputs are set to ’null’.

Note 3: Set to ’5=none’ to allow users to change the Mode through the screen.

Note 4: The maximum number depends on the selected Fan Speed Mode. E.g if 3-speed is selected, 
then the range is 1..4 (corresponding speeds 0..3).

Device Object Properties

App_Config Object

NOTE: Application Configuration Object exposes the configuration parameters over the 
BACnet. However please check if your BACnet client can support Proprietary Object types to 
be able to access these parameters.  Alternatively set the configuration parameters through 
the SRT touchscreen. 

Property Name /ID

Attributes

Range

Default

Object Identifier

R/W

20

Object Name

R/W

32 Characters Max

Concatenation of product type and MAC 
address i.e. "SRI001"

Object Type

R

Device

System Status

R

STATUS_OPERATIONAL

Vendor Name

R

SyxthSense Ltd

Vendor Identifier

651

Model Name

R

SRI7

Protocol Version

R

1

Protocol Revision

R

10

Max APDU Length

R

480

Segmentation Support

R

No

APDU Timeout

R

6000 ms

Number APDu Retries

R

3

MaxMaster

R

127

Max_Info_Frames

R

1

Database Revision

R

0

Property Name /ID

Attributes

Range

Default

Required 
Object 
Properties

Object Identifier

proprietary-128

Object Name

R/W

"App_Config"

Object Type

R

proprietary-128

Optional 
Properties

None

Property ID

Description

BACnet Data Type

Range

Proprietary 
Properties

40100

Nominal Setpoint

REAL

0.0...99.9°C/°F (Default 70°F)

40101

Setpoint Unit

Unsigned

0 = Temperature (Default)
1 = Percentage

40102

Sensor 3 Source

Unsigned

0 = Buillt-In Sensor (Default)
1 = Network Sensor

40104

Minimum Setpoint

REAL

0.0...99.9°C/°F/% (Default 57°F)

40105

Maximum Setpoint

REAL

0.0...99.9°C/°F/% (Default 86°F)

40107

Sensor 1 Source

Unsigned

0 = RI1
1 = Network Sensor (Default)

Содержание SRI-75 Series

Страница 1: ...h Backlit Touchscreen Display BACnet and Modbus Communication Models P Versions have 7 Day and 5 2 Day Schedule Flush Mounting in the UK EURO and US Wall Mounting Box Attractive Modern Designer Look B...

Страница 2: ...et MS TP Interface RS485 maximum 63 devices segment MAC Addressing 0 to 127 via Touchscreen Device ID Default 651000 MAC Address User Configured Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None...

Страница 3: ...A DI1 RI2 RI1 Wiring Details WARNING Switch off the power before any wiring is carried out RELAYOUT 24VAC 30VDC 5A Relay Contact RELAYCOM 24VAC 30VDC 5A Relay Contact 24V 24Vac dc Supply 0V 0V Supply...

Страница 4: ...1 C SRI 75 WITH ON BLUE DISPLAY SRI 75 WITH FAN SPEED DEG C 21 5 C Room 20 1 C A CONTROL MODE AUTO HEATING COOLING FAN VENTILATION FAN F C F C F C The SRI 75 room interface home screen has four touch...

Страница 5: ...he configuration pages By setting the description to Disabled the sensor reading is not displayed on the screen Note If all sensor displays are Disabled the ACTION CIRCLE displays the last drawn image...

Страница 6: ...r will need to enter the Staff Code to enter the screen Fan Speed Display and Manual Override The SRI75 has fan icon and line bar to indicate the fan speed It is also possible to use the line bar only...

Страница 7: ...e speed set over the network 2 STEP AUTO fan speed rotates between OFF M 3 segments M 6 segments M and Auto A When auto is selected the display returns to show the speed set over the network 3 STEP AU...

Страница 8: ...an be disabled through configuration settings When disabled the user cannot cancel the ECO mode OFF Mode Icon The SRI can be switched to OFF mode via the touchscreen digital volt free input e g time c...

Страница 9: ...t on the relay Frost Icon Frost icon can be set via network to display frost condition or defrosting 71 5 F Room 20 1 F Target A FROST ICON F C Cleaning Mode After entering FURTHER INFORMATION screen...

Страница 10: ...Only SCHEDULES ONLY Allows adjustment of the Programmed Times NO INPUT All Buttons Locked Alarm Display When entering FURTHER INFORMATION AND SETTINGS screen and an alarm is active select the alarm i...

Страница 11: ...reen on power up Calibrate the screen by swiping to the all four edges of the screen and then press OK to accept the new settings Programming Schedule SRI P75 Only The SRI P75 user interfaces have up...

Страница 12: ...dj Maximum Adjustable Setpoint 0 0 99 9 C F Default 86 0 F INPUTS Parameter Name Description Range Sensor 1 Source Sensor 1 Source When set to Hardware reads RI1 status monitoring over the network is...

Страница 13: ...G MODES Parameter Name Description Range DISPLAY Parameter Name Description Range Brightness Backlight Brightness 0 20 default 5 Enable Lights Icon Enable Lights Icon Network Variable 0 Disabled defau...

Страница 14: ...ool 16 Cabin Sensor 2 Text Description for the Sensor2 RI2 Network Default 0 Disabled Note Disabled removes Sensor1 Text and Measurement from Display Sensor 3 Text Description for the Sensor3 Built In...

Страница 15: ...Output Status 0 1 Off On 102 Time Clock Status SRI P70 Only 0 1 Off On 103 Light Switch Status 0 1 Off On 104 A C Switch Status 0 1 Off On 105 OFF Mode Status 0 1 Off On 106 Screen Lock Status 0 1 Of...

Страница 16: ...Default 108 Sensor 1 Network Temperature Signed 16 580 1220 58 0 122 0 C F Default 0 0 109 Fan Manual Control Mode Unsigned 16 0 4 0 Disabled default 1 1 Step 2 2 Step 3 3 Step 4 6 Step 5 1 Step Auto...

Страница 17: ...to None otherwise the user cannot set unset Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 132 Override Lock Mode Note The parameter returns automatically to 0 allowing local control Unsi...

Страница 18: ...t Unsigned 16 0 1 0 1 Default 0 210 Tuesday Weekend Switching Time 1 Unsigned 16 0 2400 0 2400 Default 0600 211 Tuesday Weekend Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 212 Tuesday Week...

Страница 19: ...54 Saturday Switching Time 4 Unsigned 16 0 2400 0 2400 Default 1700 255 Saturday Switching Time 1 Target Unsigned 16 0 1 0 1 Default 0 256 Saturday Switching Time 2 Target Unsigned 16 0 1 0 1 Default...

Страница 20: ...Humidity Measurement AI 3 Sensor 1 RI1 AI 4 Sensor 2 RI2 Analogue Value 5 AV 0 Nominal Setpoint AV 1 Sensor 1 Temp AV 2 Sensor 2 Temp AV 3 Sensor 3 Temp AV 4 Brightness Binary Input 4 BI 0 Digital Inp...

Страница 21: ...guration parameters through the SRT touchscreen Property Name ID Attributes Range Default Object Identifier R W 20 Object Name R W 32 Characters Max Concatenation of product type and MAC address i e S...

Страница 22: ...Enabled 40117 Lock Mode Unsigned 0 Lock mode disabled default 1 On Off Boost workable only 2 Temp settings only available 3 All buttons disabled 40118 Show Unit Swap Icon Unsigned 0 Disabled 1 Enabled...

Страница 23: ...ater 14 Tank 15 Pool 16 Cabin 40140 Sensor 2 Text RI2 Network Default 0 Disabled Note Disabled removes the text and measurement from the display Unsigned 40141 Sensor 3 Text Built in Network Sensor De...

Отзывы: