Technical Data

Power Supply

Power Supply

24VAC/DC -10%/+15%, max. 80mA

Display

Touchscreen

3.5" Backlit Touchscreen, 320 x 480 pixels, 255K colours

Network Signal Outputs

Relay Output

1 x 5A(res.) 24Vac Relay, SPST

Network Signal Inputs

Built-In Sensor

0..50°C (32..122°F) ±0.5°C/±0.9°F @ 25°C (77°F)

External Sensor Inputs

2 x External NTC10K3 Sensors

Digital Input

1 x Digital Input, Volt-Free Contact, Impedance <1KOhm

Optional Sensing 

Humidity (RH Models)

Characteristics

Range

0..100%rH

Accuracy

±2% rH (within 20..80% rh)

Communication

Modbus (-MOD models)

Protocol

Modbus RTU

Interface

RS485; maximum 63 devices per segment

Addressing

1 to 247 via Touchscreen

Communication

9k6/19k2/38k4/57k6/76k8 Baud; Parity None/Even/Odd, 1 or 
2 Stop Bits (adjustable through Touchscreen)

BACnet (-BAC models)

Protocol

BACnet MS/TP

Interface

RS485; maximum 63 devices segment

MAC Addressing

0 to 127 via Touchscreen

Device ID

Default  MAC Address, User Configured

Communication

9k6/19k2/38k4/57k6/76k8 Baud; Parity None/Even/Odd, 1 or 
2 Stop Bits

Connections

Terminal Connections (Relay 
& Power Supply)

Solid and Stranded Cable
Maximum Size: Solid; 0.05-2.5mm

2

, Stranded: 0.05-1.50mm

/ 14 to 30 AWG (UL)
Rising Clamp: Size 2.5 x 2.2mm

Terminal Connections (Low 
Voltage Terminals)

Solid and Stranded Cable; 90° Angle for Wiring
Maximum Size: 0.05 to 1.5mm

2

 (EN ISO) / 14 to 30 AWG (UL)

Rising Clamp: Size 2.5 x 1.9mm

Environmental Conditions

Operating

Temperature

0°C...+50°C (32..122°F)

Humidity

0...95%rh (non-cond.)

Storage

Temperature

-30°C...+70°C (-22..158°F)

Humidity

0...95%rh (non-cond.)

Standards

CE Conformity

CE Directive 2004/108/EC (EMC), 2006/95/EC (LVD) 
EN61000-6-3: 2001 (Generic Emission) 
EN61000-6-1: 2001 (Generic Immunity)

UL Listing

Pending

Degree of Protection

IP20

Housing

Housing Material

Polycarbonate Plastics, Self Extinguishing (V1 rated)

Mounting

Wall or Junction Box Mounting, Silver and Black

Dimensions

W88mm (3.46") x H112mm (4.41") x D43mm (1.68")
Flush: W88mm (3.46") x H112mm (4.41") x D14.5mm (0.57")

Weight

220g

Содержание SRI-75 Series

Страница 1: ...h Backlit Touchscreen Display BACnet and Modbus Communication Models P Versions have 7 Day and 5 2 Day Schedule Flush Mounting in the UK EURO and US Wall Mounting Box Attractive Modern Designer Look B...

Страница 2: ...et MS TP Interface RS485 maximum 63 devices segment MAC Addressing 0 to 127 via Touchscreen Device ID Default 651000 MAC Address User Configured Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None...

Страница 3: ...A DI1 RI2 RI1 Wiring Details WARNING Switch off the power before any wiring is carried out RELAYOUT 24VAC 30VDC 5A Relay Contact RELAYCOM 24VAC 30VDC 5A Relay Contact 24V 24Vac dc Supply 0V 0V Supply...

Страница 4: ...1 C SRI 75 WITH ON BLUE DISPLAY SRI 75 WITH FAN SPEED DEG C 21 5 C Room 20 1 C A CONTROL MODE AUTO HEATING COOLING FAN VENTILATION FAN F C F C F C The SRI 75 room interface home screen has four touch...

Страница 5: ...he configuration pages By setting the description to Disabled the sensor reading is not displayed on the screen Note If all sensor displays are Disabled the ACTION CIRCLE displays the last drawn image...

Страница 6: ...r will need to enter the Staff Code to enter the screen Fan Speed Display and Manual Override The SRI75 has fan icon and line bar to indicate the fan speed It is also possible to use the line bar only...

Страница 7: ...e speed set over the network 2 STEP AUTO fan speed rotates between OFF M 3 segments M 6 segments M and Auto A When auto is selected the display returns to show the speed set over the network 3 STEP AU...

Страница 8: ...an be disabled through configuration settings When disabled the user cannot cancel the ECO mode OFF Mode Icon The SRI can be switched to OFF mode via the touchscreen digital volt free input e g time c...

Страница 9: ...t on the relay Frost Icon Frost icon can be set via network to display frost condition or defrosting 71 5 F Room 20 1 F Target A FROST ICON F C Cleaning Mode After entering FURTHER INFORMATION screen...

Страница 10: ...Only SCHEDULES ONLY Allows adjustment of the Programmed Times NO INPUT All Buttons Locked Alarm Display When entering FURTHER INFORMATION AND SETTINGS screen and an alarm is active select the alarm i...

Страница 11: ...reen on power up Calibrate the screen by swiping to the all four edges of the screen and then press OK to accept the new settings Programming Schedule SRI P75 Only The SRI P75 user interfaces have up...

Страница 12: ...dj Maximum Adjustable Setpoint 0 0 99 9 C F Default 86 0 F INPUTS Parameter Name Description Range Sensor 1 Source Sensor 1 Source When set to Hardware reads RI1 status monitoring over the network is...

Страница 13: ...G MODES Parameter Name Description Range DISPLAY Parameter Name Description Range Brightness Backlight Brightness 0 20 default 5 Enable Lights Icon Enable Lights Icon Network Variable 0 Disabled defau...

Страница 14: ...ool 16 Cabin Sensor 2 Text Description for the Sensor2 RI2 Network Default 0 Disabled Note Disabled removes Sensor1 Text and Measurement from Display Sensor 3 Text Description for the Sensor3 Built In...

Страница 15: ...Output Status 0 1 Off On 102 Time Clock Status SRI P70 Only 0 1 Off On 103 Light Switch Status 0 1 Off On 104 A C Switch Status 0 1 Off On 105 OFF Mode Status 0 1 Off On 106 Screen Lock Status 0 1 Of...

Страница 16: ...Default 108 Sensor 1 Network Temperature Signed 16 580 1220 58 0 122 0 C F Default 0 0 109 Fan Manual Control Mode Unsigned 16 0 4 0 Disabled default 1 1 Step 2 2 Step 3 3 Step 4 6 Step 5 1 Step Auto...

Страница 17: ...to None otherwise the user cannot set unset Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 132 Override Lock Mode Note The parameter returns automatically to 0 allowing local control Unsi...

Страница 18: ...t Unsigned 16 0 1 0 1 Default 0 210 Tuesday Weekend Switching Time 1 Unsigned 16 0 2400 0 2400 Default 0600 211 Tuesday Weekend Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 212 Tuesday Week...

Страница 19: ...54 Saturday Switching Time 4 Unsigned 16 0 2400 0 2400 Default 1700 255 Saturday Switching Time 1 Target Unsigned 16 0 1 0 1 Default 0 256 Saturday Switching Time 2 Target Unsigned 16 0 1 0 1 Default...

Страница 20: ...Humidity Measurement AI 3 Sensor 1 RI1 AI 4 Sensor 2 RI2 Analogue Value 5 AV 0 Nominal Setpoint AV 1 Sensor 1 Temp AV 2 Sensor 2 Temp AV 3 Sensor 3 Temp AV 4 Brightness Binary Input 4 BI 0 Digital Inp...

Страница 21: ...guration parameters through the SRT touchscreen Property Name ID Attributes Range Default Object Identifier R W 20 Object Name R W 32 Characters Max Concatenation of product type and MAC address i e S...

Страница 22: ...Enabled 40117 Lock Mode Unsigned 0 Lock mode disabled default 1 On Off Boost workable only 2 Temp settings only available 3 All buttons disabled 40118 Show Unit Swap Icon Unsigned 0 Disabled 1 Enabled...

Страница 23: ...ater 14 Tank 15 Pool 16 Cabin 40140 Sensor 2 Text RI2 Network Default 0 Disabled Note Disabled removes the text and measurement from the display Unsigned 40141 Sensor 3 Text Built in Network Sensor De...