Digital Input Mode
Unsigned 16
0..9
0 = Close for ECO (Default)
1 = Open for ECO
2 = Close for OFF
3 = Open for OFF
4 = Heating/Cooling Change-Over
5 = Disable Cooling
6 = Contact Alarm
7 = Network Measurement
8 = Close for BOOST
9 = Open for BOOST
149
Digital Input Delay
Unsigned 16
0..28,800
0..28,800 seconds (Default 0s)
150
Internal Sensor Calibration
Signed 16
-100..+100
-10.0..+10.0 °C/°F
151
RI1 Calibration
Signed 16
-100..+100
-10.0..+10.0 °C/°F
152
RI2 Calibration
Signed 16
-100..+100
-10.0..+10.0 °C/°F
153
CO2 Calibration
Signed 16
-500..+500
-500...+500 ppm
154
Humidity Calibration
Signed 16
-100..+100
-10.0..+10.0 % rH
155
Lock Mode
Unsigned 16
0..4
0 = Lock mode disabled (default)
1 = On/Off workable only
2 = Temp settings only available
3 = All buttons disabled
156
Lock Mode Password
Unsigned 16
0..9999
0000...9999
157
Boost Time
Unsigned 16
0..480
0 = Permanent (Default 0)
1..480 minutes
158
Boost Target
Unsigned 16
0..5
0 = Nominal SP (Temperature)
1 = CO2 SP
2 = Humidity SP
3 = Dehum SP
4 = Fan Demand
5 = Aux. Temp SP
159
Boost Target Value
Unsigned 16
0..5000
0...5000 (default 25)
160
Mode Display Button
Unsigned 16
0..1
0 = Indication Only
1 = Active (default)
163
Brightness (Backlight Level)
Unsigned 16
0..20
0..20 (default 5)
164
Display Humidity
Unsigned 16
0..1
0 = Disabled
1 = Enabled (default)
165
Show Swap Temperature Units Icon
Unsigned 16
0..1
0 = Disabled (default)
1 = Enabled
166
Zone 1 Room Sensor Text
Unsigned 16
0..16
1 = Room (Default)
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin