ECO Mode
The device can be switched to ECO mode via network, via
digital input (e.g. PIR) or via the touchscreen.
ECO MODE
INDICATION
Room
20
.1
°C
Target
21
.5
°C
AUTO
In the ECO mode the controller starts to control to ECO
Heating/Cooling Deadzone and the user setpoint
adjustment (SPA) is removed.
In the ECO mode the CO2 and Humidity loops are
switched to 0%.
The ECO mode can be selected/and cancelled using the
MODE BUTTON (if enabled), The ECO mode is also
indicated by the not showing the setpoint adjustment
buttons.
CONTROL
OUTPUT
calcSP
(Default 4.0°C/9.2°F)
HDz
MEASURED
TEMPERATURE
100%
0%
+
-
eHDz
CDz
eCDz
ECO Deadzone
HEA
TING ST
AGE 1
COOLING ST
AGE 1
HEA
TING ST
AGE 2
COOLING ST
AGE 2
ECO MODE TEMPERATURE CONTROL
calcSP= Calculated Setpoint (Default 21°C/70°F)
eHDz = ECO Mode Heating Deadzone
eCDz = ECO Mode Cooling Deadzone
SRC600/601/602 - 0..10Vdc
SRC600/601/602 - 0..10Vdc
SRC600/601/602 - 0..10Vdc
SRC602 - PWM
SRC600/601/602 - 0..10Vdc
SRC602 - PWM
Note: If the 7 Day Schedule has been activated, the device starts to use the operating mode set at the
next switching point (e.g. if the next switching point is COMFORT MODE, the devices returns to
COMFORT mode).
OFF Mode
The controller can be switched to OFF mode via digital
volt-free input (e.g. PIR), via the MODE BUTTON or
via the communication network (system configuration).
Room
22
.7
°C
Target
8
.0
°C
A
OFF MODE
INDICATION
DIMMED
SCREEN AND
OFF SETPOINT
DISPLAY
In the OFF mode all temperature/CO2/humidity control
outputs are switched off to 0% level.
When in OFF mode if the temperature drops below the
OFF FROST Setpoint, the frost protection is activated,
the SNOWFLAKE icon is displayed on the screen and
the heating stages are switched to 100% and the fan
speed output is switched to 33%. When the
temperature exceeds the OFF FROST setpoint plus 2
degrees, the frost condition is deactivated.
CONTROL
OUTPUT
nSP
nSP= Nominal Setpoint (Default 21°C / 70°F)
MEASURED
TEMPERATURE
100%
0%
+
-
fSP
2°C /
3.6°F
fSP = Frost Setpoint (Default 8°C / 46°F)
OFF MODE TEMPERATURE CONTROL
Note: In frost condition the
Fan Demand is set @ 33%.
Note: If the 7 Day Schedule has been activated, the device starts to use the operating mode set at the
next switching point (e.g. if the next switching point is COMFORT MODE, the devices returns to
COMFORT mode).