background image

SyxthSense Ltd

Copyright © 2020 SyxthSense Ltd. All rights reserved - 11/2020 

PS 

CT2.161

 - 13/34

Online store: 

www.syxthsense.com

Enquiries: T:

  +44 (0)1392 875 414   

E:

 [email protected]

Propor Integral control by changing the Integral Action Time from 0 to a required value. The 
actuator direction can be changed via Output Direction parameter (Direct, Reverse).

In the OFF mode the CO2 loop output is set to 0%. In the ECO mode the CO2 loop operates as in the 
day mode.

VAV Maximum Demand

Each of the analogue outputs can also be configured as "Maximum VAV Demand". In this case the 
corresponding output (Y1, Y2, Y3) takes the maximum of the CO2 Loop and Cooling Temperature 
Loop demand output. This is typically used in demand based ventilation (VAV) to control fresh air 
damper when there is either demand for more fresh air, or demand for temperature cooling (typically 
fresh air cools down the room space).

Maximum Fan Demand

Each of the analogue outputs can be configured ad "Maximum Fan Demand". In this configuration the 
corresponding output (Y1, Y2, Y3) takes the maximum demand of the CO2 Control Loop and Fan 
Speed Control Loop. This can provide fan speed boost at high CO2 level and when the fan speed 
temperature loop has increased the demand.

Humidity Control Loop 
Operation (-RH option)

The RH models can measure and control 
the relative humidity level. This can then be 
used in demand based control applications 
to increase the fresh air supply e.g. in the 
high humidity conditions. The control loop 
has both de-humidification and 
humidification outputs that can be linked to 
any of the physical control outputs Y1, Y2, 
or Y3. The direction of the both outputs can 
also be reversed to driver the actuators 
100-

CONTROL 

OUTPUT

De-humidification

SP= Setpoint e.g. 50%rH

100%

Proportional Band

e.g 5%rH

SP

0%

Humidity %rH

-

+

0%rH

100%rH

LOOP OUTPUT

Humidification

0% instead of 0-100%.

Cleaning Mode

After entering FURTHER INFORMATION screen, by selecting the CLEANING icon, it is possible to 
activate the cleaning mode. The SRC will enter a "Clean Screen" state where all touchscreen presses 
are ignored and 30 second countdown timer is displayed. This allows cleaning of the device itself. 

Lock Mode

After entering FURTHER INFORMATION screen, by selecting the 
LOCK icon it is 

0000

8 9
5 6 -
2 3

Esc

OK

Del

Lock Code

Enter Code

7
4
1
0

possible to lock the device. Now by entering the 

LOCK CODE, the device lock state can be activated. 

The lock mode can be configured to work in different ways as 
described at the below table.

DISABLED: Lock Mode Icon Not Available

ON/OFF ONLY: Allows Mode Buttons Only

ADJUST ONLY: Allows Temperature Adjustment Only

NO INPUT: All Buttons Locked

If the lock code is set to 0000 (default), there is no need to enter the 
lock code and the lock entry screen is bypassed.

Remote Sensor RI1 and RI2 
Inputs

A remote NTC10k3 sensor can be connected to the RI1 and RI2 inputs to be used for different control 
and display purposes. The options are:-

DISABLED; the measurement is disabled

ROOM; the input is used for the main temperature control loop

FLOOR; the input is used for High/Low Limit Control

OUTSIDE: the input is used to show the Outside Temperature

NETWORK NTC10; the resistive input is available over the communication network as tempera-
ture.

NETWORK 0-10V; the input is used as 0.10V network monitoring input (requires AI option)

Lock Mode Options

Icon Active / Visible

Lock

Up and Down

OFF

Fan Speed / 
Schedule / 
Time

Mode Buttons

DISABLED

NO

YES

YES

YES

YES

ON/OFF ONLY

YES

NO

YES

NO

YES

ADJUST ONLY

YES

YES

NO

NO

NO

NO INPUT

YES

NO

NO

NO

NO 

Содержание SRC-P-700 Series

Страница 1: ...ic Summer Winter Time Change Over Product sheet CT2 161 Type SRC P 700 Product Selection Table 1 2 3 4 5 6 1 Device type Touchscreen Room Controller 2RI 1DI 3AO htg clg fan Schedule SRC P 700 Touchscr...

Страница 2: ...maximum 63 devices MAC Addressing 0 127 via Touchscreen Device ID Default 651000 MAC Address Adjustable Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable thr...

Страница 3: ...ommon RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACn...

Страница 4: ...nput 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS TP RS485 A Connection 485B Modbus BAC...

Страница 5: ...n Speed 1 On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac...

Страница 6: ...Ring modulates based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz...

Страница 7: ...in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings and Information The FURTHER SETTINGS screen shows additional user...

Страница 8: ...re to fluctuate around the setpoint without heating or cooling valves starting to open The SRC has a built in lock that prevents cooling and heating demands to be on simultaneously The deadzone has an...

Страница 9: ...target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effective limited setpoint enter Controller Status and Information display Not...

Страница 10: ...C 6 0 0 6 0 1 6 0 2 0 1 0 V d c S R C 6 0 2 P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching p...

Страница 11: ...chedule point regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period i...

Страница 12: ...O MATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY C...

Страница 13: ...e actuators 100 CONTROL OUTPUT D e h u m i d i f i c a t i o n SP Setpoint e g 50 rH 100 Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0...

Страница 14: ...to open the operating mode does not change until the countdown timer has expired DIGITAL INPUT DELAY setting Note Resistive Inputs as a Digital Input operate with approx ten seconds delay and are not...

Страница 15: ...apter 6 PORT REVERSE see 6 PORT VALVE control chapter reverse operation Analogue Output Scaling Output Limitation Each of the analogue outputs Y1 Y2 Y3 can have Output minimum voltage percentage Outpu...

Страница 16: ...The SRC 700 controller can be configured to control Belimo 6 Port valve by selecting 6 Port or 6 Port Reverse mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Ana...

Страница 17: ...ensor 2 Fault The typical alarm reasons are External sensor 1 Res1 fault when activated out of range External sensor 2 Res1 fault when activated out of range Built in sensor fault Digital Input Alarm...

Страница 18: ...of the temperature control loop Set to 0 to disable 0 1 200 seconds Default 600s Heating Stages Number of Heating Stages 0 None 1 1 Stage Default 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Directi...

Страница 19: ...setting Disabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Di...

Страница 20: ...fault Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period SRC 702 SRC 704H 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Страница 21: ...ACnet Baud Rate 0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Defaul...

Страница 22: ...gister Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode...

Страница 23: ...ge Default 2 2 Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Uns...

Страница 24: ...put Y2 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Defau...

Страница 25: ...Unsigned 16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16...

Страница 26: ...ride Level 1 100 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns t...

Страница 27: ...gned 16 0 2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching T...

Страница 28: ...0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16...

Страница 29: ...ue Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humidity Read O...

Страница 30: ...ry Properties 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2...

Страница 31: ...ult Cooling Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Netwo...

Страница 32: ...midity Unsigned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone...

Страница 33: ...seconds Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192...

Страница 34: ...61 34 34 Online store www syxthsense com Enquiries T 44 0 1392 875 414 E info syxthsense com Dimensions 88mm 3 46 14 5mm 0 56 52mm 2 05 43mm 1 69 112mm 4 41 88mm 3 46 52mm 2 05 112mm 4 41 53mm 2 09 49...

Отзывы: