Fan Speed Source
Unsigned 16
0..11
0 = Heating 1 and Cooling 1 Stage
(Default)
1 = Heating Stage1
2 = Cooling Stage 1
3 = Heating and Cooling Stage 2
4 = Heating Stage 2
5 = Cooling Stage 2
6 = CO2
7 = Humidification
8 = De-Humidification
9 = Maximum VAV (Cooling/CO2)
10 = Maximum Temp/Hum
11 = Aux. Loop
130
Min Fan Level
Unsigned 16
0..100
0...100% (Default 0%)
131
Y1 Output Mode
Default: Modulating Fan
Unsigned 16
0..18
0 = Network Value
1 = Heating Stage 1
2 = Heating Stage 2
3 = Cooling Stage 1
4 = Cooling Stage 2
5 = Modulating Fan (EC)
6 = CO2 Control
7 = Maximum VAV
8 = Maximum Fan
9 = Humidification
10 = De-humidification
11 = Amber / Red
12 = Red
13 = Heating1 Sta
14 = Cooling1 Stat
15 = Fan Stat
16 = Aux. Loop
17 = 6-Port (Valve)
18 = 6-Port Reverse (Valve)
132
Y2 Output Mode
Default: Heating Stage 1
SRC-703 Default: Heating1 Stat
Unsigned 16
0..18
133
Y3 Output Mode
Default: Cooling Stage 1
Unsigned 16
0..18
134
Analogue Output Y1 Override Value
Unsigned 16
0..1000
0..100% (0..10.0V) - Default 0
135
Analogue Output Y2 Override Value
Unsigned 16
0..1000
0..100% (0..10.0V) - Default 0
136
Analogue Output Y3 Override Value
Unsigned 16
0..1000
0..100% (0..10.0V) - Default 0
137
Y1 Minimum Output
Unsigned 16
0..1000
0...100.0 % (Default 0.0%)
138
Y1 Maximum Output
Unsigned 16
0..1000
0...100.0 % (Default 100.0%)
139
Y2 Minimum Output
Unsigned 16
0..1000
0...100.0 % (Default 0.0%)
140
Y2 Maximum Output
Unsigned 16
0..1000
0...100.0 % (Default 100.0%)
141
Y3 Minimum Output
Unsigned 16
0..1000
0...100.0 % (Default 0.0%)
142
Y3 Maximum Output
Unsigned 16
0..1000
0...100.0 % (Default 100.0%)
143
Anti-JAM Time-out
Unsigned 16
0..14
0..14 Days
0 = Disabled (Default)
144
RI1 Mode
Unsigned 16
0..11
0 = Disabled (default)
1 = Room (NTC10 Control)
2 = Floor (NTC10 High/Low Lim)
3 = Aux. Loop
4 = Network NTC10
5 = Network 0-10V
6 = CO2 0-10V (0..2000 =0-10V)
7 = Main Loop (0..50°C=0-10V)
8 = Close for ECO (DI-mode)
9 = Open for ECO (DI-mode)
10 = Close for OFF (DI-mode)
11 = Open for OFF (DI-mode)
145
RI2 Mode
Unsigned 16
0..11
146
Outside Temperature Source
Unsigned 16
0..1
0 = Built-In Sensor (Default)
1 = Network Sensor
147
Outside Air Temperature Network Write
Note: If Outside Temperature Source is set to 1,
and a valid (within range) value is sent to this
parameter the touchscreen starts to show
Outside temperature in the SMALL ACTION
CIRCLE.
Signed 16
-580...1220
-58.0...122.0°C/°F (Default 0.0)
Register
Parameter Description
Data Type
Raw Data
Range