background image

SyxthSense Ltd

Copyright © 2020 SyxthSense Ltd. All rights reserved - 11/2020 

PS 

CT2.161

 - 16/34

Online store: 

www.syxthsense.com

Enquiries: T:

  +44 (0)1392 875 414   

E:

 [email protected]

NOTE: With SRC-703 you can also configure Y1 to ’HEATING1 or COOLING1 STAT’. With this 
configuration RELAY3 becomes also as ON/OFF valve output. Therefore the SC-703 controller 
can control both heating and cooling ON/OFF valves (and EC Fan via 0-10Vdc output).

PWM Control / Digital 
Outputs 
(SRC-702/SRC-704H)

The SRC-702/SRC-704H controller has two digital triac outputs. The digital outputs are used for PWM 
control for heating and cooling valves. The PWM period is set in the INPUTS/OUTPUTS PWM Period 
Setting. The below diagram illustrates the principle of the PWM control..

HEA

TING 

ST

AGE1

OUTPUT

HEATING

STAGE 1

calcSP

HDz

°C / °F

100%

0%

+

-

PWM CONTROL EXAMPLE (HEATING STAGE1 - DO1)

HDz = COMFORT Heating Deadzone

CDz

calcSP = Calculated Setpoint

230 Vac L

Transformer

230 Vac N

Fuse

24Vac

0Vac

Clg Actuator
Thermic
(PWM)

Absolute
Max. 27.6VAC

G0

G0

485B-

485A+

Din

RI1

Y1

24V

~/

DO2

DO1

RI2

SRC-602

GO

Htg Actuator

Thermic (PWM)

60%

Example:
Htg1 = 60%

PWM Output
60% of time: ON = 0.6 * 30 = 18s
40% of time: OFF = 0.4 * 30 = 12s

DIGITAL PWM OUTPUT (DO1)

OFF

ON

TIME (seconds)

PWM Period Setting: 30s (Default)

18s

12s

NOTE:With SRC-703/704H analogue outputs Y2 & Y3 are not available. Y1 is available for EC 
Fan control (or other valid output control - see Y1 options). With SRC-704H the Y1 is set as 
default ’Modulating Fan’, and the device does not have 0-10Vdc outputs.

NOTE:Please note that DO1 and DO2 are 24Vac Triacs switching to 0V. Please follow the above 
wiring diagram.

Belimo 6-Port Control Mode

The SRC-700 controller can be configured to control Belimo 6-Port valve by selecting 

6-Port 

or 

6-Port 

Reverse

 mode for the analogue output (Y1/Y2/Y3). The diagram below illustrates the operation.

Note: Analogue Output Scaling/Anti-JAM is not available in the 6-Port and 6-Port Reverse 
modes. Number of Heating and Cooling Stages must be set at minimum to one.

AntiJAM Valve Exercise 
Function

If the AntiJAM function is enabled the controller monitors for inactivity. If the control outputs have been 
fully closed or fully open more than the AntiJAM period, the controller will open/close the outputs to by 
30% for a short period of time. The AntiJAM function is enabled through the configuration parameters 
by selecting the required AntiJAM period by days.

Alarm Display

The SRC-700 controller provides two 
Alarm Modules each of which can be 
configured to detect and display alarm 
condition on either CO2, Humidity or 
Temperature Sensor (internal or external 
depending on which is being used). The 
alarm function can be disabled by setting 
the alarm source as “NONE”. Alarms are 
disabled by default.

CO2 AMBER ALARM

CO2 RED ALARM

Target

21

.5

°C

Target

21

.5

°C

A

A

CO2

950

ppm

CO2

1300

ppm

Each Alarm has three alarm states – No 
Alarm, Amber and Red. When in alarm 
the alarm is displayed by alarm bell in 
ACTION CIRCLE. The ACTION CIRCLE 
rotates all active measurements so the 
alarm is displayed when the 
corresponding measurement is 
displayed.

HIGH LIMIT ALARM

DEMAND

nSP

HDz/CDz = Comfort Zero Energy 
Deadzone (Default 0.5°C)
nSP= Nominal Setpoint (Default 21°C)

HDz

MEASURED 
TEMPERATURE

100%

0%

+

-

CDz

Zero Energy

Deadzone

HEA

TING ST

AGE 1

COOLING ST

AGE 1

2V

7V

5V

10V

SEQUENCE 1

SEQUENCE 2

MAX 
FLOW

MIN 
FLOW

6-WAY VALVE CONTROL 
SIGNAL (Y1/Y2/Y3)

6-WAY; HTG1 = 5V to 2V, CLG1 = 7V to 10V
6-WAY REVERSE; HTG1 = 7V to 10V, 
CLG1 = 5V to 2V

ANALOGUE OUTPUT MODES

Содержание SRC-P-700 Series

Страница 1: ...ic Summer Winter Time Change Over Product sheet CT2 161 Type SRC P 700 Product Selection Table 1 2 3 4 5 6 1 Device type Touchscreen Room Controller 2RI 1DI 3AO htg clg fan Schedule SRC P 700 Touchscr...

Страница 2: ...maximum 63 devices MAC Addressing 0 127 via Touchscreen Device ID Default 651000 MAC Address Adjustable Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable thr...

Страница 3: ...ommon RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACn...

Страница 4: ...nput 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS TP RS485 A Connection 485B Modbus BAC...

Страница 5: ...n Speed 1 On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac...

Страница 6: ...Ring modulates based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz...

Страница 7: ...in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings and Information The FURTHER SETTINGS screen shows additional user...

Страница 8: ...re to fluctuate around the setpoint without heating or cooling valves starting to open The SRC has a built in lock that prevents cooling and heating demands to be on simultaneously The deadzone has an...

Страница 9: ...target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effective limited setpoint enter Controller Status and Information display Not...

Страница 10: ...C 6 0 0 6 0 1 6 0 2 0 1 0 V d c S R C 6 0 2 P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching p...

Страница 11: ...chedule point regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period i...

Страница 12: ...O MATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY C...

Страница 13: ...e actuators 100 CONTROL OUTPUT D e h u m i d i f i c a t i o n SP Setpoint e g 50 rH 100 Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0...

Страница 14: ...to open the operating mode does not change until the countdown timer has expired DIGITAL INPUT DELAY setting Note Resistive Inputs as a Digital Input operate with approx ten seconds delay and are not...

Страница 15: ...apter 6 PORT REVERSE see 6 PORT VALVE control chapter reverse operation Analogue Output Scaling Output Limitation Each of the analogue outputs Y1 Y2 Y3 can have Output minimum voltage percentage Outpu...

Страница 16: ...The SRC 700 controller can be configured to control Belimo 6 Port valve by selecting 6 Port or 6 Port Reverse mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Ana...

Страница 17: ...ensor 2 Fault The typical alarm reasons are External sensor 1 Res1 fault when activated out of range External sensor 2 Res1 fault when activated out of range Built in sensor fault Digital Input Alarm...

Страница 18: ...of the temperature control loop Set to 0 to disable 0 1 200 seconds Default 600s Heating Stages Number of Heating Stages 0 None 1 1 Stage Default 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Directi...

Страница 19: ...setting Disabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Di...

Страница 20: ...fault Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period SRC 702 SRC 704H 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Страница 21: ...ACnet Baud Rate 0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Defaul...

Страница 22: ...gister Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode...

Страница 23: ...ge Default 2 2 Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Uns...

Страница 24: ...put Y2 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Defau...

Страница 25: ...Unsigned 16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16...

Страница 26: ...ride Level 1 100 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns t...

Страница 27: ...gned 16 0 2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching T...

Страница 28: ...0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16...

Страница 29: ...ue Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humidity Read O...

Страница 30: ...ry Properties 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2...

Страница 31: ...ult Cooling Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Netwo...

Страница 32: ...midity Unsigned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone...

Страница 33: ...seconds Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192...

Страница 34: ...61 34 34 Online store www syxthsense com Enquiries T 44 0 1392 875 414 E info syxthsense com Dimensions 88mm 3 46 14 5mm 0 56 52mm 2 05 43mm 1 69 112mm 4 41 88mm 3 46 52mm 2 05 112mm 4 41 53mm 2 09 49...

Отзывы: