28
| Instructions for unloading on the site as well as installation and connection
Connection and start-up of the Access control system
with the NaviPad control panel is described in:
Quick guide NaviPad — on 16 pages.
This information is
available on Systemair.com
I.3.5
Lock the doors by using the key
Use the key to lock the doors. The doors are not locked
automatically by turning the handle to the vertical
position.
I.4
Installation – Pipes for water – hot and chilled, valves and drains
I.4.1
Description
If ordered with the unit, the valves and valve motors are stored in a carton box placed inside the unit. Water trap(s) –
standard or optional - is (are) necessary to ensure escape of water from the tray under plate heat exchanger and (or)
cooling coil. Water trap(s) is (are) stored in a carton box placed inside the unit.
I.4.2
Pipe connections
Connection pipes on heating- and cooling coils are provided with external thread. Drainage outlets on drip trays are pro-
vided with straight pipe for quick connect fittings on the pipe with the water trap.
I.4.3
Possibility of extracting components from the unit
Pipes and cables must not obstruct the inspection doors and components which can be extracted from the unit. Poten-
tial components for extraction are filters, fans and rotary heat exchanger.
I.4.4
Pipe connections to batteries
I.4.4.1
Heating coils
Pipes for hot water must be protected by insulation against frost and loss of heat. Further protection against frost can
be obtained by installing electrical heating wires around the pipes and under the insulation combined with temperature
output |