Instructions for unloading on the site as well as installation and connection |
23
Rigid duct connection at the Geniox Core unit is available with 20 mm or 30 mm flange for LS profile and screw clamps.
Please check the order confirmation or the data in the annex 2 concerning the size of the flange — 20 mm or 30 mm.
Furthermore the rigid duct connection is always with a
8,5 mm hole in each corner of the flange.
Use 8 mm bolt with nut in each corner and a sufficient
number of screw clamps with
a distance between screw
clamps that not exceeds 300 mm
to hold the duct,
damper, coil or attenuator tight together
Size of duct connections at the 7 sizes of Geniox Core units
Size of unit
Width in mm
Height in mm
10
1000
400
11
1100
450
12
1200
500
14
1400
600
16
1600
700
18
1800
800
20
2000
900
I.2.10.1 Dampers for installation in ducts
If the damper is mounted on the rigid duct connection of the air handling unit, the installer must support the damper
further by brackets or suspension prior to mounting of ducts. Ducts as well as dampers must be insulated according to
local guidelines
I.2.10.2 Coils for installation in ducts
The duct connection is available with 20 mm or 30 mm flange for LS profile and screw clamps. Furthermore always a
8,5 mm hole in each corner of the flange.
output |