48
| Adjustment and maintenance operations
F7 — ePM1 60%
F7 CityFlo — ePM1 60%
F8 — ePM1 75%
F9 — ePM1 85%
R.4.1
Bag filters – the number of filters and sizes of frames
Filters in supply air and in extract air are always the same sizes and the same numbers. See the filters in supply or ex-
tract air below.
Size of unit
Numbers and sizes of frames for bag filters (WxH)
10
1x[792x392]
11
2x[490x490]
12
1x[592x490] + 1x[490x490]
14
2x[490x592] + 1x[287x592]
16
3x[490x592]
18
2x[490x392] + 4x[592x392]
20
3x[592x592] + 3x[287x592]
Note:
Special sizes of filters are available from Camfil.
Dept of filter frame must be 25 mm to ensure a complete airtight sealing around the AHU filter frame
R.4.2
Panel filters – the number of filters and the sizes of the frames
Size of unit
Numbers and sizes of frames for panel filters (WxHxD)
10
1x[792x392x48]
11
2x[490x392x48]
12
1x[490x490x48] + 1x[592x490x48]
14
2x[490x592x48] + 1x[287x592x48]
16
3x[490x592x48]
18
2x[490x392x48] + 4x[592x392x48]
20
3x[592x592x48] + 3x[592x287x48]
Note:
Special sizes of filters are available by Camfil.
R.4.3
Video instruction — replace bag filters
Turn the unit off and wait for 2 minutes till unit completely stops. Used filters can be drawn out. Store the used filters
immediately in plastic bags to avoid that dust pollutes the environment. Geniox units are provided with a very corro-
sion-resistant and reliable system, where filters are slid into the air handling units in a lower and upper durable u-profile
of flexible plastic. Check the upper and lower U-profile for damage and check the flexible vertical plastic profiles as well
as the rubber profile that close between filter frame and door for damage.
Note:
Replace the profiles in case of damage.
Note:
The filters must have vertical bags.