background image

Figure 13. Testing detector alarm:

A78-2694-00

[6.2.2.2] RTS451/RTS451KEY Remote Test Station

The RTS451/RTS451KEY Remote Test Station facilitates test 
of the alarm capability of the duct smoke detector as indi-
cated in the RTS451/RTS451KEY manual. The DH100ACDCI 
duct  smoke  detector  can  be  reset  by  the  RTS451/
RTS451KEY.  If  a  system  control  panel  is  used,  the  panel 
itself may also require testing.
To  install  the  RTS451/RTS451KEY,  connect  the  device  as 
shown in Figure 9; wire runs must be limited to 25 ohms 
or less per interconnecting wire. 

Please  note  that  the  magnetic  coil  supplied  with  the 
RTS451  and  RTS451KEY  is  not  required  when  these 
accessories are used with the DH100ACDCI detectors.

 The 

functionality of the magnetic coil has been designed into the 
circuitry of the new Innovair

 duct smoke detectors.

[6.2.2.3] SSK451 Multi-Signaling Accessory

The  System  Sensor  SSK451  Multi-Signaling  accessory  com-
bines  a  sounder  feature  with  a  key  activated  test  and  reset 
function. Green, amber, and red LEDs provide a visual indi-
cation of power, trouble, and alarm respectively. An optional 
strobe (PS24LO) with a smoke lens can be added to conform 
to the codes of certain jurisdictions.
To install the SSK451, connect the device as shown in figure 12.

ALARM SIGNAL (+)

AUX POWER (–)

15

20

(+)

(–)

DUCT DETECTOR

DH100ACDCI

PA400 (OPTIONAL)

AUDIBLE ALERT

ALARM SIGNAL (+)

AUX POWER (–)

15

20

(+)

(–)

DUCT DETECTOR

DH100ACDCI

RA400Z (OPTIONAL)

REMOTE (LED)

ANNUNCIATOR

RED

ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA451
PA400
RA400Z
RTS451/RTS451KEY
SSK451

STANDBY
12.5mA Max.
0mA
0mA
12mA*
5mA Max.

ALARM
30mA Max.
15mA Max.
10mA Max.
7.5mA Max.
30mA Max.

*NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any

 combination of accessories may be used such that the given accessory loads are:

60 mA or less in the standby state;   110 mA or less in the alarm state.

TROUBLE
n/a
n/a
n/a
n/a
9mA Max.

D100-68-00                                                                                               7                                                                                            I56-1684-06R

[6.2.3] Sensitivity Tests
[6.2.3.1] MOD400 or MOD400R Test 

After verification of alarm capability, use the MOD400R test 
module  with  a  voltmeter  to  check  detector  sensitivity  as 
indicated in the test module’s manual. The housing cover 
must be removed to perform this test.

If  test  module  readings  indicate  that  the  detector  head  is 
outside of the acceptable range that is printed on the label 
of the detector, the detector chamber requires cleaning per 
Section [7] of this manual.

[7] Detector Cleaning Procedures

Notify the proper authorities that the smoke detector sys-
tem  is  undergoing  maintenance,  and  that  the  system  will 
temporarily be out of service. Disable the zone or system 
undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department.

[7.1] Air Filters

1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with 

new filters. If they are not heavily coated, use a vacuum 
cleaner or compressed air nozzle to remove dust, then 
reinstall the filters. 

Figure 11. Wiring diagrams for optional accessories:

A78-2692-00

15 

ALARM SIGNAL

 3
14
 2 

RESET

11 

TEST

20 

AUX. POWER (-)

19 

AUX. POWER (+)

SSK451

FIELD INSTALLED

JUMPER FOR

TEMPORAL PATTERN

SUPERVISORY

CONTACT

NO

FIELD INSTALLED

JUMPER

DH100ACDCI

COMMON      3

TEMPORAL SELECT      2

ALARM SIGNAL      1

SUPERVISORY SIGNAL      4

RESET      7

TEST      8

POWER (-)      6

POWER (+)      5

Figure 12. Wiring diagram for  

 

                  DH100ACDCI to SSK451 

A78-2693-00

Archived Document

Содержание InnovAir DH100ACDCI

Страница 1: ...100ACDCI detector is designed to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervisory relay contacts are available for control panel interface alarm initiation HVAC control and other auxilia...

Страница 2: ...mounting location Make sure the template lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 5 2 1 Sampling Tube Installation for Ducts Less Than 1...

Страница 3: ...w moisture drainage away from the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft long must be s...

Страница 4: ...4 inch hole where the flange will be used 5 4 3 Modifications of Sampling Tubes There may be applications where duct widths are not what is specified for the installation In such cases it is permis si...

Страница 5: ...hamber visually identify any obstructions Plug the exhaust and sampling tube holes to prevent ducted air from carrying smoke away from the detector head then blow smoke such as cigarette cotton wick o...

Страница 6: ...ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM...

Страница 7: ...x 10mA Max 7 5mA Max 30mA Max NOTE When a unit is powered at the 120VAC or 220 240VAC input any combination of accessories may be used such that the given accessory loads are 60 mA or less in the stan...

Страница 8: ...20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up time 34 sec max 34 sec max 3...

Отзывы: