System Sensor warrants its enclosed air duct smoke detector to be free from defects 

in materials and workmanship under normal use and service for a period of three 

years  from  date  of  manufacture.  System  Sensor  makes  no  other  express  warranty 

for  this  air  duct  smoke  detector.  No  agent,  representative,  dealer,  or  employee  of 

the Company has the authority to increase or alter the obligations or limitations of 

this  Warranty.  The  Company’s  obligation  of  this  Warranty  shall  be  limited  to  the 

repair or replacement of any part of the air duct smoke detector which is found to 

be defective in materials or workmanship under normal use and service during the 

three year period commencing with the date of manufacture. After phoning System 

Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization num-

ber,  send  defective  units  postage  prepaid  to:  System  Sensor,  Repair  Department,

RA  #__________,  3825  Ohio  Avenue,  St.  Charles,  IL  60174.  Please  include  a  note 

describing the malfunction and suspected cause of failure. The Company shall not 

be obligated to repair or replace units which are found to be defective because of 

damage,  unreasonable  use,  modifications,  or  alterations  occurring  after  the  date 

of  manufacture.  In  no  case  shall  the  Company  be  liable  for  any  consequential  or 

incidental damages for breach of this or any other Warranty, expressed or implied 

whatsoever, even if the loss or damage is caused by the Company’s negligence or 

fault.  Some  states  do  not  allow  the  exclusion  or  limitation  of  incidental  or  conse-

quential damages, so the above limitation or exclusion may not apply to you. This 

Warranty gives you specific legal rights, and you may also have other rights which 

vary from state to state.

[9] Model DH100ACDCI Air Duct Smoke Detector Specifications 

Operating Temperature:                  +32° to +131° F                               0° to +55° C
Storage Temperature:                      –22° to +158° F                                –30° to +70° C
Humidity:                                      10% to 93% R.H. noncondensing
Air Velocity:                                   500 to 4000 ft./min.                            2.5 to 20.3 m/sec.
Dimensions:                                   14.38” L x 5.5” W x  2.75” D              37cm L x 14cm W x 7cm D 

 

Weight:                                          3.75 pounds                                       1.7 kg

Electrical Specifications

Power supply voltage:                   20-29 VDC         24 VAC 50-60-Hz       120 VAC 50-60 Hz    220/240 VAC 50-60 Hz
Input capacitance:                        270 µF max.            270 µF max.                     N/A                            N/A
Reset voltage:                              3.0 VDC min.           2.0 VAC min.             10 VAC min.                20 VAC min.
Reset time (with RTS451):            .03 to 0.3 sec.         .03 to 0.3 sec.             .03 to 0.3 sec.              .03 to 0.3 sec.
Reset time (by power down):       0.6 sec. max.           0.6 sec. max.              0.6 sec. max.                0.6 sec. max.
Power up time:                             34 sec. max.           34 sec. max.               34 sec. max.                34 sec. max.
Alarm response time:                   2 to 17 sec.             2 to 17 sec.                2 to 17 sec.                  2 to 17 sec.
Sensitivity Test:                        See detector label   See detector label        See detector label        See detector label

[7.2] Ion Detector Boards 

1. Brush  or  vacuum  inside  area  of  cover.  Chamber  may 

then be blown out using clean, compressed air. 

2. Vacuum sensing chamber before using clean, compressed 

air to loosen and blow out any remaining debris. 

[8.0] Board Replacement
[8.1] Detector Board Replacement (part no. A5052)

1.   Remove the two detector board mounting screws.
2.   Pull gently on the board to remove it. 
3.   To  replace  the  board,  align  the  board  mounting  fea-

tures, holes, and the interconnect terminals. Push the 
board into place.

4.   Secure board with the two mounting screws.

[8.2] Power Board replacement (part no. A5064)

1.   Disconnect wiring from the terminal block.
2.   Remove the two power board mounting screws.
3.   Pull gently on the board to remove it. 
4.   To  replace  the  board,  align  the  board  mounting  fea-

tures, holes, and the interconnect terminals. Push the 
board into place.

5.   Secure board with the two mounting screws.
6.   Re-connect wiring to terminal block.

Power Supply Voltage

20 - 29 VDC

24 VAC 50 - 60 Hz

120 VAC 50 - 60 Hz

220/240 VAC 50 - 60 Hz

CURRENT REQUIREMENTS (USING NO ACCESSORIES)

Max. standby current

15 mA

35 mA RMS

25 mA RMS*

15 mA RMS*

Max. alarm current

70 mA

125 mA RMS

35 mA RMS*

25 mA RMS*

CONTACT RATINGS

Alarm initiation contacts (SPST)

2.0A @ 30 VDC (resistive)

Alarm auxiliary contacts (DPDT)

10A @ 30 VDC
10A @ 250 VAC
1/4 HP @ 240 VAC
1/8 HP @ 120 VAC

Trouble contacts (SPDT)

2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)

Note:

Alarm auxiliary contacts must switch 100 mA minimum at 5VDC. Alarm auxiliary contacts shall not be
connected to inititaing circuits of control panels. Use the alarm initiation contact for this purpose.

* NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any 

  combination of accessories may be used such that the given accessory loads are: 

 

60 mA or less in the standby state,

 

110 mA or less in the alarm state.

ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA451
PA400
RA400Z
RTS451
RTS451KEY
SSK451

STANDBY
12.5mA Max.
0mA
0mA
0mA
12mA*
5mA Max.

ALARM
30mA Max.
15mA Max.
10mA Max.
7.5mA Max.
7.5mA Max.
30mA Max.

TROUBLE
n/a
n/a
n/a
n/a
n/a
9mA Max.

Please refer to insert for Limitations of Fire Alarm Systems.

Archived Document

Содержание InnovAir DH100ACDCI

Страница 1: ...100ACDCI detector is designed to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervisory relay contacts are available for control panel interface alarm initiation HVAC control and other auxilia...

Страница 2: ...mounting location Make sure the template lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 5 2 1 Sampling Tube Installation for Ducts Less Than 1...

Страница 3: ...w moisture drainage away from the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft long must be s...

Страница 4: ...4 inch hole where the flange will be used 5 4 3 Modifications of Sampling Tubes There may be applications where duct widths are not what is specified for the installation In such cases it is permis si...

Страница 5: ...hamber visually identify any obstructions Plug the exhaust and sampling tube holes to prevent ducted air from carrying smoke away from the detector head then blow smoke such as cigarette cotton wick o...

Страница 6: ...ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM...

Страница 7: ...x 10mA Max 7 5mA Max 30mA Max NOTE When a unit is powered at the 120VAC or 220 240VAC input any combination of accessories may be used such that the given accessory loads are 60 mA or less in the stan...

Страница 8: ...20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up time 34 sec max 34 sec max 3...

Отзывы: