background image

[5.4.2] Installation For Ducts More Than 8 Feet Wide

NOTE:

  To install sampling tubes in ducts more than 8 feet 

wide, work must be performed inside the air duct. 
Sampling of air in ducts wider than 8 feet is accom-
plished  by  using  the  ST-10  inlet  sampling  tube.  If 
the  tube  is  shorter  than  the  width  of  the  air  duct, 
install the end cap into the sampling tube as shown 
in  Figure  4  and  support  the  end  opposite  the  duct 
smoke detector.

Install the inlet tube as follows:

1. Drill a 

3

4

 inch hole in the duct directly opposite the hole 

already drilled for the sampling tube. Make sure the hole 
is 1 to 2” below the inlet hole on the opposite side of the 
duct to allow for moisture drainage.

2. Slide the sampling tube with the flange into the housing 

bushing that meets the air flow first. Position the tube so 
that  the  arrow  points  into  the  air  flow.  Secure  the  tube 
flange  to  the  housing  bushing  with  two  #6  self-tapping 
screws.

3. From  inside  the  duct,  couple  the  other  sections  of  the 

sampling tube to the section already installed using the 

1⁄2  inch  conduit  fittings  supplied.  Make  sure  that  the 
holes on both of the air inlet tubes are lined up and fac-
ing into the air flow.

4. Trim the end of the tube protruding through the duct so 

that  1  to  2  inches  of  the  tube  extend  outside  the  duct. 
Plug this end with the end cap and tape closed any holes 
in the protruding section of the tube. Be sure to seal the 
duct when the tube protrudes.

NOTE:

  An  alternate  method  to  using  the  ST-10  is  to  use 

two ST-5 sampling tubes. Remove the flange from 
one  of  the  tubes  and  install  as  described  above. 
After  the  installation,  use  electrical  tape  to  close 
off some of the sampling holes so that there are a 
total of 10 to 12 holes spaced as evenly as possible 
across the width of the duct.

NOTE:

  Air  currents  inside  the  duct  may  cause  excessive 

vibration,  especially  when  the  longer  sampling 
tubes  are  used.  In  these  cases  a  3”  floor  flange 
(available at most plumbing supply stores) may be 
used to fasten the sampling tube to the other side of 
the duct. When using the flange/connector mount-
ing technique, drill a 1 inch to 1

1

4

 inch hole where 

the flange will be used. 

[5.4.3] Modifications of Sampling Tubes

There may be applications where duct widths are not what 
is specified for the installation. In such cases, it is permis-
sible to modify a sampling tube that is longer than neces-
sary to span the duct width.

Use  a  0.193-inch  diameter  (#11)  drill  and  add  the  appro-
priate  number  of  holes  so  that  the  total  number  of  holes 
exposed to the air flow in the duct is 10 to 12. Space the 
additional holes as evenly as possible over the length of the 
tube.

NOTE:

  This procedure should only be used as a temporary 

fix. It is not intended as a permanent substitute for 
ordering the correct length tubes.

[5.5] Install The Filters 

To install the sampling tube filters, simply push the filters 
into  the  sampling  and  exhaust  tube  holes,  as  shown  in 
Figure 6. If a metal sampling tube is used, install the filters 
over the tube ends.

Figure 6. Sampling tube filter installation:

CAUTION

Filters  require  periodic  cleaning  or  replacement,  depend-
ing on the amount of dust and dirt accumulated. Visually 
inspect  the  filters  at  least  quarterly;  inspect  them  more 
often if the dust accumulation warrants it. See Section [6] 
for  more  information.  Replacement  filters  can  be  ordered 
from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. 
(Exhaust tube/intake tube filter P/N F36-09-11)

[5.6] Field Wiring
Installation Guidelines

All  wiring  must  be  installed  in  compliance  with  the 
National Electrical Code and the local codes having juris-
diction. Proper wire gauges should be used. The conduc-
tors used to connect smoke detectors to control panels and 
accessory devices should be color-coded to prevent wiring 
mistakes. Improper connections can prevent a system from 
responding properly in the event of a fire.

For  signal  wiring,  (the  wiring  between  interconnected 
detectors or from detectors to auxiliary devices), it is usu-
ally recommended that single conductor wire be no smaller 
than 18 gauge. The duct smoke detector terminals accom-
modate wire sizes up to 12 gauge. The last foot of conduit 
should  be  flexible  conduit  (available  in  electrical  supply 
houses), which facilitates easier installation and puts less 
strain  on  the  conduit  holes  in  the  housing.  Solid  conduit 
connections may be used if desired.

D100-68-00                                                                                               4                                                                                            I56-1684-06R

A78-2691-00

Archived Document

Содержание InnovAir DH100ACDCI

Страница 1: ...100ACDCI detector is designed to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervisory relay contacts are available for control panel interface alarm initiation HVAC control and other auxilia...

Страница 2: ...mounting location Make sure the template lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 5 2 1 Sampling Tube Installation for Ducts Less Than 1...

Страница 3: ...w moisture drainage away from the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft long must be s...

Страница 4: ...4 inch hole where the flange will be used 5 4 3 Modifications of Sampling Tubes There may be applications where duct widths are not what is specified for the installation In such cases it is permis si...

Страница 5: ...hamber visually identify any obstructions Plug the exhaust and sampling tube holes to prevent ducted air from carrying smoke away from the detector head then blow smoke such as cigarette cotton wick o...

Страница 6: ...ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM...

Страница 7: ...x 10mA Max 7 5mA Max 30mA Max NOTE When a unit is powered at the 120VAC or 220 240VAC input any combination of accessories may be used such that the given accessory loads are 60 mA or less in the stan...

Страница 8: ...20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up time 34 sec max 34 sec max 3...

Отзывы: