[4] Contents Of The Duct Smoke Detector Kit

1.  Complete housing base and cover assembly
2.  Two #10 x 1

1

/

4

” sheet metal screws for mounting

3.  Two sampling tube filters
4.  One test magnet
5.  Drilling template
6.  Two foam gaskets
7.  Four  #6-self  tapping  mounting  screws  for  the  metal 

sampling tube and optional exhaust tube extension

8.  One sampling tube end cap
9.  One plastic sampling tube
10. One #8 self-tapping screw for the plastic sampling tube

NOTE:

  For ducts over 1

1

2

 feet, longer sampling tubes must 

be ordered to complete the installation. They must 
be  the  correct  length  for  the  width  of  the  duct 
where they will be installed. See Table 1 on page 3 
to determine the sampling tube required for differ-
ent duct widths.

[5] Installation Sequence
[5.1] Verify Duct Air Flow Direction And Velocity

Model  DH100ACDCI  detectors  are  designed  to  be  used  in 
air  handling  systems  having  air  velocities  of  500  to  4000 
feet per minute. Be sure to check engineering specifications 
to ensure that the air velocity in the duct falls within these 
parameters. If necessary, use a velocity meter to check the 
air velocity in the duct.

[5.2] Drill The Mounting Holes

Remove  the  paper  backing  from  the  mounting  template 
supplied.  Affix  the  template  to  the  duct  at  the  desired 
mounting  location.  Make  sure  the  template  lies  flat  and 
smooth on the duct. Center punch holes A and B. Drill the 
holes as indicated on the template. 

[5.2.1] Sampling Tube Installation for Ducts Less 
Than 1

1

2

 Feet Wide (see Figure 2)

1. Remove the front cover.
2. Slide  the  plastic  sampling  tube  into  the  housing  bush-

ing.

3. Align  the  holes  in  the  bushing  with  the  holes  in  the 

sampling tube. Make sure there are 6 exposed holes on 
the plastic sampling tube. Secure with the #8 self-tapping 
screw into the bottom of the permanent tube (shown in 
Fig. 1).

NOTE:

  The sampling tube end cap is critical to the proper 

operation of the duct smoke detector. The end cap 
is needed to create the proper air flow to the sensor 
of the duct smoke detector.

NOTE:

  For  ducts  greater  than  1

1

2

  feet  in  width,  refer  to 

sections [5.4.1] and [5.4.2].

Figure 2. Plastic sampling tube
connected to duct smoke detector:

[5.3] Secure The Detector Housing To The Duct

Slide  the  foam  gaskets  over  the  tube  bushings  as  shown 
in Figure 3. Use the two 1

1

/

4

” long sheet metal screws to 

screw the detector housing to the duct. 

CAUTION: Do not overtighten the screws.

D100-68-00                                                                                               2                                                                                            I56-1684-06R

[3] Figure 1: Exploded View Of Duct Smoke Detector Components

FOAM

GASKETS

PLASTIC

SAMPLING TUBE

CONDUIT HOLES

DETECTOR

HOUSING

TERMINAL STRIP

DETECTOR

COVER

SAMPLING TUBE

FILTERS

PLASTIC SAMPLING TUBE

SELF-TAPPING SCREW

POWER BOARD

DETECTOR BOARD

COVER MOUNTING

SCREWS

A78-2690-00

H0110-00

Archived Document

Содержание InnovAir DH100ACDCI

Страница 1: ...100ACDCI detector is designed to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervisory relay contacts are available for control panel interface alarm initiation HVAC control and other auxilia...

Страница 2: ...mounting location Make sure the template lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 5 2 1 Sampling Tube Installation for Ducts Less Than 1...

Страница 3: ...w moisture drainage away from the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft long must be s...

Страница 4: ...4 inch hole where the flange will be used 5 4 3 Modifications of Sampling Tubes There may be applications where duct widths are not what is specified for the installation In such cases it is permis si...

Страница 5: ...hamber visually identify any obstructions Plug the exhaust and sampling tube holes to prevent ducted air from carrying smoke away from the detector head then blow smoke such as cigarette cotton wick o...

Страница 6: ...ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM...

Страница 7: ...x 10mA Max 7 5mA Max 30mA Max NOTE When a unit is powered at the 120VAC or 220 240VAC input any combination of accessories may be used such that the given accessory loads are 60 mA or less in the stan...

Страница 8: ...20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up time 34 sec max 34 sec max 3...

Отзывы: