background image

D100-68-00                                                                                               6                                                                                            I56-1684-06R

24V

120

VAC

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

24V

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY  TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

14

3

3

14

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

ALARM

INITIATION

LOOP

UL LISTED 4-WIRE

CONTROL PANEL

FIRST DETECTOR IN THE LOOP

DH100ACDCI

LAST DETECTOR IN THE LOOP

DH100ACDCI

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR. SEE

SPECIFICATIONS FOR

ADDITIONAL POWER SUPPLY

INFORMATION.

FOR WIRING OF AUXILIARY

DEVICES, REFER TO

MANUFACTURER'S

INSTALLATION INSTRUCTIONS

OR CONTACT MANUFACTURER.

NOTE:

 THE SUPERVISORY RELAY NOW

PROVIDES A "FORM C" CONTACT FOR

CUSTOMIZED APPLICATIONS.

FOR STANDARD APPLICATIONS, ONLY

THE "NO" CONTACT IS USED

POWER INPUTS ACCEPT

24 VDC, 24 VAC  50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ.

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR.      

AUX. CONTACT RATINGS

10A @ 30 VDC RESISTIVE

10A @ 250 VAC

100mA MINIMUM @ 5 VDC

1/4 HP @ 240 VAC

1/8 HP @ 120 VAC

NOT INTENDED FOR

CONNECTION TO CONTROL

PANELS.

TROUBLE CONTACT RATING

2.0 A @ 30 VDC resistive

2.0 A @ 125 VAC resistive

+

120

VAC

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

Figure 8. Wiring diagram for DH100ACDCI to APA451:

H0182-00

H0155-01

Figure 7. System wiring diagram for 4-wire duct smoke detectors:

15

19

14

3

20

1

3

2

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

NOTE: Wiring diagram shown is for DH100ACDCI 4-wire duct

smoke detector system equipped without a control panel.

Alarm

Power

Common

APA451

DH100ACDCI

NOTE: A trouble condition is indicated when the green LED

is not illuminated.

Figure 9. Wiring diagram for DH100ACDCI to 
RTS451KEY:

15

19

14

3

20

2

11

2

6

1

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

Reset

Test

(Red LED) Alarm

(Green LED)
Power

DH100ACDCI

RTS451/RTS451KEY

5

4

3

*

For RTS451KEY
only without a
control panel.

*

Important Interconnect Notes

•   When  using  the  interconnect  feature,  all  inter-

connected  units  must  be  powered  with  the 
same, independent supply.

•  Polarity  must  be  maintained  throughout  the 

interconnect wiring. Connect terminal 12 on unit 
1 to terminal 12 on unit 2 and so on. Similarly, 
connect  terminal  1  on  unit  1  to  terminal  1  on 
unit 2 and so on.

•   Up to 10 units may be interconnected.

Figure 10. Multiple fan shutdown (interconnect):

1

6

12

16

A

B

C

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

DETECTOR 1

C

DETECTOR 2

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

C

DETECTOR 10

OUT TO

10 DETECTORS

MAXIMUM

Archived Document

Содержание InnovAir DH100ACDCI

Страница 1: ...100ACDCI detector is designed to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervisory relay contacts are available for control panel interface alarm initiation HVAC control and other auxilia...

Страница 2: ...mounting location Make sure the template lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 5 2 1 Sampling Tube Installation for Ducts Less Than 1...

Страница 3: ...w moisture drainage away from the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft long must be s...

Страница 4: ...4 inch hole where the flange will be used 5 4 3 Modifications of Sampling Tubes There may be applications where duct widths are not what is specified for the installation In such cases it is permis si...

Страница 5: ...hamber visually identify any obstructions Plug the exhaust and sampling tube holes to prevent ducted air from carrying smoke away from the detector head then blow smoke such as cigarette cotton wick o...

Страница 6: ...ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM...

Страница 7: ...x 10mA Max 7 5mA Max 30mA Max NOTE When a unit is powered at the 120VAC or 220 240VAC input any combination of accessories may be used such that the given accessory loads are 60 mA or less in the stan...

Страница 8: ...20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up time 34 sec max 34 sec max 3...

Отзывы: