176 TimeHub 5500 User’s Guide
097-55501-01 Revision M – January 2009
Chapter 4 Testing and Configuring the TimeHub
Provisioning Inputs on a Remote Shelf
The TimeHub Remote shelf can produce outputs in Freerun mode (in other words,
without a qualified input) by using the FREEACT TL1 keyword. The default setting
for FREEACT on a remote shelf is SQUELCH, which means no output is possible
when in Freerun mode. By setting it to CONTINUE output is allowed in when in
Freerun. See the TimeHub 5500
TL1 Reference Manual
for details.
Using TL1 Commands
If you are using terminal software, the general TL1 command format for enabling or
disabling an input is:
ED-SYNC::CLK-a:<ctag>:::ENABLE=b;
where a = 10 or 11 (10 = CC1, 11 = CC2)
b = Y to enable, N to disable the input
1. Enable or disable inputs as appropriate for your installation. For example, to
enable CC1, type:
ED-SYNC::CLK-10:SV460:::ENABLE=Y;
To enable CC2, substitute CLK-11 for CLK-10.
Issue the following TL1 command to verify that the input is enabled:
RTRV-SYNC::CLK-11:SV461:::PARAMETER=ENABLE;
2. Verify that the input is enabled by checking the “E” LED on the front panel of
either Clock card (see
). Note that the Clock panel labeling is to the
right of the LEDs in the INPUTS section. The first row of three LEDs is labeled
CC1. In this step, verify that the “E” LED in that row is lit. Note that when the “E”
LED is lit, the input has been selected as a possible timing reference; it does not
indicate that a valid input is connected.
3. Verify that the input is qualified by checking that the “Q” LED (in the same row as the
“E” LED) is lit. It can take up to several minutes for the “Q” LED to light after the “E”
has lit. When this LED lights, the input meets all requirements for use as a timing
source (signal presence, framing, within frequency pull-in range all confirmed).
If the “Q” LED does not light, there is most likely a problem with the input.
Typical causes are no signal present or improper connection to the Input/Alarm
Connector module.
Note:
You can observe progress toward qualification via either the
local or LAN communications port. The TL1 RTRV-COND command
provides this information (for example, input loss of signal or out of
frame can be observed via RTRV-COND). Refer to the TimeHub 5500
TL1 Reference Manual
for details.
Содержание TimeHub 5500
Страница 1: ...TimeHub 5500 User s Guide Revision M January 2009 Part Number 097 55501 01 ...
Страница 12: ...List of Figures 12 TimeHub 5500 User s Guide 097 55501 01 Revision M October 2008 ...
Страница 14: ...List of Tables 14 TimeHub 5500 User s Guide 097 55501 01 Revision M January 2009 ...
Страница 46: ...46 TimeHub 5500 User s Guide 097 55501 01 Revision M January 2009 Chapter 1 Description TimeScan THC Software ...
Страница 280: ...280 TimeHub 5500 User s Guide 097 55501 01 Revision M January 2009 Chapter 6 Specifications Factory Default Values ...