Setting Menu
Page 18/28
Programming instructions of the
SYCLOPE INDIG’O
®
3)
Alarms configuration : Page “Alarms”
This page allow you to define :
Upper alarm threshold : value for the upper alarm threshold with activation of the Alarm relay
after overpassing the value
Lower alarm threshold : value for the lower alarm threshold with activation of the Alarm relay
after overpassing the value
Overdosing delay : Maximum delay (in sec) to reach the setpoint. If overpassing of this delay,
activation of the Alarm relay + stop c display of the pictogram on the main screen
Name
Signification
Setting range
Default
value
Action
Upper
threshold
Upper threshold value
4-20 mA : 2 to 100%*
pH : 0,2 to 14
ORP : -980 to 1000
4-20 mA : 40 %*
pH : 7,70
ORP : 850
Alarm activation
Lower
threshold
Lower threshold value
4-20 mA : 0% to 98%*
pH : 0 to 13,8
ORP : -1000 to 980
4-20 mA : 10 %
pH : 6,80
ORP : 300
Alarm activation
Overdose
Maximum dosing delay
before stopping control
0……9999 s
0 s
Alarm activation
Stop control
(*) : Expressed in % of the measuring range
REG
Free Cl
mg/l
Dosage : 0,00%
Setpoint : 2,00 mg/l
Output : 10,57
mA
4,10
ALR
REG
pH
pH
Dosage : 0,00%
Setpoint : 7,20 pH
Output : 11,43
mA
6,50
ALR
REG
pH
pH
Dosage : 0,00%
Setpoint : 7,20 pH
Ouput : 12,57 mA
7,50
ALR
Upper Alarm
Overdosing
Lower Alarm
Alarms
ation Control
4,00
mg/l
Upper :
1,00
mg/l
Lower :
0
s
Overdose :
Version 4-20 mA
Version pH
Version ORP
ation
850
mV
Upper :
300
mV
Lower :
0
s
Overdose :
ation
7,70
(pH)
Upper :
6,80
(pH)
Lower :
0
s
Overdose :
Alarms
Control
Alarms