6.5 System components
6.5.1 Installation of pressure sensors
If the operating logic requires the installation of pressure sensors in the system, the Manufacturer supplies a kit of measu
-
ring devices to be assembled by the fitter.
The kit consists of:
- 2 pressure sensors;
-
two M-F taps (thread G¼");
- 2 connectors complete with cable.
Fig. 13 Components of the kit
The kit is supplied pre-assembled inside the electrical control panel and electrically connected to the termi-
nal board.
Components must be fitted on the system as illustrated in the hydraulic diagram of the corresponding operating logic.
Two G¼” sleeves (out of supply scope) are required for pressure sensor installation.
Install the sleeves vertically and in a position where the assemblies are not exposed to accidental damage.
Use a suitable sealant to ensure water tightness between the components.
After completing the thermal insulation of the hydraulic circuit, insert the connectors in the sensors and secure the cables
properly.
Fig. 14 Connection of a pressure sensor
It may be necessary to extend the cables.
If the cables are extended, this must be done professionally to ensure a good electrical connection and protection from
moisture over time.
After the sensors have been installed, make sure they are protected from accidental damage and that the
connection cables are secured properly.