37
DAUGHTER BOARD SETUP
4-20mA Input Dip Switch Settings
Warning: Remove power from the system when selecting dip switch setting.
NOTE: The 4-20mA input will control the actuator valve only after flame is proven.
There are 4 pre-defined settings of 4-20mA input, which controls the actuator. The table below shows the
4 different settings that can be selected.
To set up Switch 1 setting, slide the switch 1 to ON position and make sure all other switches stay in OFF
position. At this setting, when the transducer sees pressure of 1.5oz, the system will turn ON the actuator
valve to the open position and keeps the valve open until the pressure drops down to 0.5oz then it will
close the actuator valve. See the table below.
The other 3 settings work in the same way but at different pressure levels. See the table below.
Dip Switch Settings
Dip Switch No
ON
OFF
Dip Switch setting
Switch 1 (ON)
1.5 oz.
0.5 oz.
Switch 2 (ON)
2.0 oz.
0.5 oz.
Switch 3 (ON)
2.5 oz.
0.5 oz.
Switch 4 (ON)
3.0 oz.
1.0 oz.
Содержание iBURNER BMS-100
Страница 1: ...Proudly Made in the USA INSTALLATION OPERATIONS MANUAL PROUDLY MADE IN THE USA...
Страница 16: ...16 INSTALLATION WIRING DIAGRAM...
Страница 17: ...17 1 SureFire Solenoid Fuel Train 1 SOLENOID FUEL TRAIN...
Страница 18: ...18 1 SureFire Solenoid Actuator Fuel Train 1 SOLENOID ACTUATOR FUEL TRAIN...
Страница 19: ...19 1 4 ASCO Solenoid 3PG Valve Actuator Fuel Train 1 4 SOLENOID 3PG ACTUATOR FUEL TRAIN...
Страница 23: ...23 Flowchart without Daughter Board OPERATIONS GUIDE FLOW CHART...
Страница 25: ...25 Flowchart with Safety T C Daughter Board installed OPERATIONS GUIDE FLOW CHART...
Страница 27: ...27 Flowchart with Daughter Board Safety T C and 4 20mA Input OPERATIONS GUIDE FLOW CHART...