4
WARNING
EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2, GROUPS C AND D, OR UNCLASSIFED APPLICATIONS;
WARNING
EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS;
WARNING
EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING
PROPERTIES OF MATERIALS USED IN THE FOLLOWING DEVICES: HAMLIN ELECTRONICS
RELAY, MODEL HE721A0500, ALLIED ELECRONICS RELAY, MODEL JW2SN-DC12V, AND
PANASONIC RELAY, MODEL DS2E-SL2-DC5V
WARNING
SUBSTITUTION OF THE FOLLOWING COMPONENTS MAY IMPAIR SUITABILITY FOR
DIVISION 2
Reference Designation
Description
Type of Protection
K1, K2, or K3
Relay
Sealed Contacts
CERTIFACTIONS AND WARNINGS
Rated Input Voltage: 12VDC
Wattage: 60.0 MAX/ 7.2 AVG
Amperage: 5.0 amps MAX/0.6 amps AVG
Class 1, Division 2, Groups C and D, or Unclassified Applications, T4
Ambient Temperature Range: -40°F ≤Tamb ≤131°F (-40°C ≤Tamb ≤55°C)
Certified to:
UL 61010 - 1
UL 61010 –2 030
ISA 12.12.01
Содержание iBURNER BMS-100
Страница 1: ...Proudly Made in the USA INSTALLATION OPERATIONS MANUAL PROUDLY MADE IN THE USA...
Страница 16: ...16 INSTALLATION WIRING DIAGRAM...
Страница 17: ...17 1 SureFire Solenoid Fuel Train 1 SOLENOID FUEL TRAIN...
Страница 18: ...18 1 SureFire Solenoid Actuator Fuel Train 1 SOLENOID ACTUATOR FUEL TRAIN...
Страница 19: ...19 1 4 ASCO Solenoid 3PG Valve Actuator Fuel Train 1 4 SOLENOID 3PG ACTUATOR FUEL TRAIN...
Страница 23: ...23 Flowchart without Daughter Board OPERATIONS GUIDE FLOW CHART...
Страница 25: ...25 Flowchart with Safety T C Daughter Board installed OPERATIONS GUIDE FLOW CHART...
Страница 27: ...27 Flowchart with Daughter Board Safety T C and 4 20mA Input OPERATIONS GUIDE FLOW CHART...