5.0 Operation
- 60 -
5.5.5 Hardware Diagnostics
The Hardware Diagnostics screen enables the user to view the current fan speeds, temperatures and power consumption of the receiver.
5.5.5.1 Fan Speed tab
The Fan Speed screen displays the current fan speed of the receiver. The color of each of the up to six gauges changes from green to yellow to red as
fan speed increases. The readings are shown in RPM. The gauges for CPM 1(primary) and CPM 2 (secondary), and Fan Tray 1 and 2 are displayed by
default. To view the other fan trays, scroll using the arrow button.
5.5.5.2 Temperatures tab
The Temperature screen displays the current temperature of each SG-CPM5. Each gauge changes color from green to yellow to red as the temperature
increases. The readings can be displayed in either Celsius or Fahrenheit, and are received approximately every five seconds. Both positive and negative
readings are shown.
Temperature Alert Thresholds:
l
65°C/149°F - Normal state to Warning (generates temperature warning on printer/automation):
l
95°C/203°F - Warning to Alarm (generates temperature alarm on printer/automation):
l
55°C/131°F - Warning to normal (generates temperature restore on printer/automation):
l
85°C/185°F - Alarm to Warning (generates temperature warning on printer/automation):