Chapter 6 Manual Zero Point Windows display codes
www.supmea.com
- 31 -
to move the ID code, then press the
Enter key again to save the current
parameter in the current ID room.
When selecting "Entry to Load", press
ENT, and the system will read and
calculate the parameters automatically
and display the transducer mounting
spacing in Window M25.
Cross-sectional Area
Holding with Poor Sig
Select "Yes" to hold last good flow
signal displayed if the flowmeter
experiences a poor signal
condition.This function will allow to
calculate flow totalizer data without
interruption.Select "NO", instead.
Empty Pipe Setup
This parameter is used to overcome
the possible problems that usually
show up when the pipe being
measured is empty. Since signals can
be transmitted through the pipe wall,
the flow meter may still read a flow
while measuring an empty pipe.To
prevent this condition from happening,
you can specify a value.When the
Empty Pipe Setup [29
0
Cross - sectional Area
314515.9 mm2
Holding with Poor Sig
NO