5-6
S
UPER
S
ERVER 5028R-WR User's Manual
7. With the CPU in the socket, in-
spect the four corners of the CPU
to make sure that they are flush
with the socket.
8. Close the load plate. Use your
thumb to gently push the lever
labeled 'Close 1st' then the lever
labeled 'Open 1st' down until they
lock.
9. Repeat steps to install to the
remaining CPU socket.
OPEN 1st
Lever Lock
Push down
and lock the
lever labeled
'Open 1st'.
OPEN 1st
Push down and lock the
level labeled 'Close 1st'.
Gently close
the load plate.
Installing and Removing a Passive CPU Heatsink
1. Do not apply any thermal grease to the heatsink or the CPU die; the required
amount has already been applied.
2. Place the heatsink on top of the CPU so that the four mounting holes are
aligned with those on the serverboard and the heatsink bracket underneath.
3. Screw in two diagonal screws (i.e., the #1 and the #2 screws) until just snug
(to avoid possible damage to the CPU, do not over-tighten the screws.)
4. Add the two remaining screws then fully tighten all four screws.
Содержание SuperServer 5028R-WR
Страница 1: ...SUPERSERVER 5028R WR SUPER USER S MANUAL 1 0...
Страница 5: ...Notes Preface v...
Страница 14: ...1 6 SUPERSERVER 5028R WR User s Manual Notes...
Страница 22: ...2 8 SUPERSERVER 5028R WR User s Manual Notes...
Страница 26: ...SUPERSERVER 5028R WR User s Manual 3 4 Notes...
Страница 46: ...4 20 SUPERSERVER 5028R WR User s Manual Notes...
Страница 74: ...5 28 SUPERSERVER 5028R WR User s Manual Notes...
Страница 81: ...Chapter 6 Advanced Chassis Setup 6 7 Figure 6 6 Removing System Cooling Fans...
Страница 126: ...A 2 SUPERSERVER 5028R WR User s Manual Notes...
Страница 129: ...B 3 Appendix B System Specifications Notes...