Quick User Manual
3 Commissioning
21
Tab. 3-3
Description of Other Lead-acid Battery Parameter
Parameter
Description
Default
Range
Max. Chrg
The upper limit of the
charging current
0.300C
0.05C to 2C
Max. DChrg
The upper limit of the
discharging current
0.300C
0.1C to 2C
Rate Vtg
The rated voltage of the
equipped battery
48.0 V
30 V to 60 V
Capacity
Capacity of the battery tray
200 Ah
10 Ah to1000 Ah
Over Vtg
The upper limit of battery
voltage when charging
58.8 V
48 V to 70 V
Low Vtg
The lower limit of battery
voltage when discharging
42.0 V
26 V to 48 V
Over Temp
The upper limit of battery
temperature
60.0
℃
20
℃
to 70
℃
Low Temp
The lower limit of battery
temperature
-25.0
℃
-30
℃
to 10
℃
CSTVtgChar
The voltage of
constant-voltage charging.
56.4 V
40 V to 63 V
DChrgEndVtg
The voltage at which the
discharging is stopped
43.20 V
30 V to 53 V
Battery usage enabled (Weekend):
In the case of commissioning failure, power off the system and wait 1
minute to commission the system again.
3.3
Result Verification
3.3.1 Meter Installation and Connection
For the single-phase meter, with the signal from the 1-phase sensor, the inverter
determines the energy exchange with the utility grid on one phase.
Содержание SH3K6
Страница 1: ...SH3 6_4 6K QUEN Ver12 201710 Version 1 2 Quick User Manual SH3K6 SH4K6 Grid Connected Hybrid Inverter ...
Страница 2: ......
Страница 4: ...II System Overview ...
Страница 5: ...III ...
Страница 6: ...IV ...
Страница 7: ...V ...
Страница 8: ...VI ...
Страница 28: ...3 Commissioning Quick User Manual 18 Fig 3 2 Initial Settings ...