83
Fault code
Fault name
Corrective measures
548-563, 580-
595
PV Abnormal
Alarm
Check whether the voltage and current of the in-
verter is abnormal to determine the cause of the
alarm.
1. Check whether the corresponding module is
sheltered. If so, remove the shelter and ensure
module cleanness.
2. Check whether the battery board wiring is
loose, if so, make it reliably connected.
3. Check if the DC fuse is damaged. If so, replace
the fuse.
4. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the alarm
persists.
*The code 548 to code 563 are corresponding to
string 1 to string 16 respectively.
*The code 580 to code 595 are corresponding to
string 17 to string 32 respectively.
37
Excessively High
Ambient
Temperature
Generally, the inverter will resume operation
when the internal or module temperature returns
to normal. If the fault persists:
1. Check whether the ambient temperature of the
inverter is too high;
2. Check whether the inverter is in a well-venti-
lated place;
3. Check whether the inverter is exposed to di-
rect sunlight. Shield it if so;
4. Check whether the fan is running properly. Re-
place the fan if not;
5. Contact Sungrow Power Customer Service if
the fault is due to other causes and the fault
persists.
43
Excessively Low
Ambient
Temperature
Stop and disconnect the inverter. Restart the in-
verter when the ambient temperature rises within
the operation temperature range.
User Manual
Содержание SG250HX-US
Страница 2: ......
Страница 6: ......
Страница 10: ......
Страница 36: ...26 End 4 Mechanical Mounting User Manual...